manualshive.com logo in svg
background image

Instruction Leafl et IL17000

Effective  May 2011
Supersedes January  1994

A200  Size 4, 3 Pole 
Motor Controller

THE CONTROLLER

The A200 motor controller, when wired as shown in Figures 
5 and 6, will operate as a full voltage starter and will give 
protection against overload, but not against short circuit 
currents, when wired and provided with overload relay (OlR) 
heaters as listed in heater selection tables or when used 
with any means of inherent protection activated by motor 
temperature.

The controller should be protected against short circuits 
by providing branch circuit protection not to exceed the 
maximum protective device ratings listed in Table I. 

This industrial type control is designed to be installed, 
operated, and maintained by adequately trained workmen. 
These instructions do not cover all details, variations, 
or combinations of the equipment, its storage, delivery, 
installation, check out, safe operation, or maintenance. Care 
must be exercised to comply with local, state, and national 
regulations, as well as safety practices, for this class of 
equipment.

AUXILIARY CONTACTS - TYPE J

A J20 with two normally open poles is supplied mounted 
in the upper left hand corner recess of the contactor. One 
pole is used as the holding circuit auxiliary.

Отзывы: