4
basic insulation requirements for pollution degree 2).
⚫
Disconnection and overcurrent protection devices shall be provided by others
for permanently connected AC input (Normal AC / Bypass AC) and AC output
circuits.
⚫
Check that the indications on the rating plate correspond to your AC powered
system and to the actual electrical consumption of all the equipment to be
connected to the system.
⚫
For PLUGGABLE EQUIPMENT, the socket-outlet shall be installed near the
equipment and shall be easily accessible
⚫
Never install the system near liquids or in an excessively damp environment.
⚫
Never let a foreign body penetrate inside the system.
⚫
Never block the ventilation grates of the system.
⚫
Never expose the system to direct sunlight or source of heat.
⚫
If the system must be stored prior to installation, storage must be in a dry
place.
⚫
The admissible storage temperature range is -25°C to +60°C without battery (-
15°C to +40°C with battery).
Special precautions
⚫
The unit is heavy: wear safety shoes and use vacuum lifter preferentially for
handling operations.
⚫
All handling operations will require at least two people (unpacking, lifting,
installation in rack system).
⚫
Straps are provided only for unpacking the unit manually from the carton;
don’t use the straps to carry the unit around. The unit may slip from the
straps during handling (risk of injury and product damage):
- keep 12” / 30cm minimum distance between the straps
- lift the unit carefully and keep it at a low height
- keep the unit horizontal during unpacking.
⚫
Before and after the installation, if the UPS remains de-energized for a long
period of time, the UPS must be energized for a period of 24 hours, at least
once every 6 months (for a normal storage temperature less than 25°C). This
charge the batteries, thus avoiding possible irreversible damage.
⚫
During the replacement of the Battery Module, it is imperative to use the same
type and number of elements as the original Battery Module provided with
the UPS to maintain an identical level of performance and safety.