17
3.3 Mechanical installation
1. This series supports two installation modes: Tower installation and rack
installation.
2. Leave at least 500mm of clearance for the front and rear of the module for
ventilation.
3. Do not carry the module by the front/rear panel during installation.
3.3.1 UPS module installation
•
Rack mount:
The UPS is suitable for installation in a 19-inch standard rack cabinet. The
minimum recommended rack depth is 800mm.
1.
Install the optional rail kit. This rail kit is '2U & with screw holes (M5)', the
depth of the rail kit is: 415-763mm.
Fasten the rail kit to the cabinet with 8pcs M5 screws + washers (as
below):