4–20kVA Users Guide P-164000669 4–20kVA Users Guide P-164000669—Rev 09
85
Battery Settings
The Battery Settings Menu provides control of battery tests, warnings and modes.
Figure 67. Battery Settings Menu
Local Settings
In/Out settings
On/Off settings
Battery settings
Input signals
Comm settings
User password enable
User password settings
Settings
ABM On Off
Auto battery test
Low battery warning
Restart batt. Level
Low BTR warning
External battery
Deep disch.protect.
Battery settings
ABM On Off
Auto battery test
Low battery warning
Enabled
√
Disabled
Restart batt.level
20
Battery settings
Low BTR warning
%
Enabled
√
Disabled
%
00
sec
180
Deep. Disch.Protect.
Yes
√
Warranty void if no
No
Auto battery test
Low battery warning
Restart batt. level
Low BTR warning
External battery
External battery
Auto Detection
Auto Detection
Manual EBM set.
Manual batt. set.
External battery
Auto Detection
Auto Detection
Manual EBM set.
Manual batt. set.
External battery
Auto Detection
Auto Detection
Manual EBM set.
Manual batt. set.
External battery
Auto Detection
1 BM
External battery
Manual EBM set.
0 Strings
External battery
Manual batt. set.
0 AH
Advanced Battery Mode
[Enabled] [Disabled]
In ABM cycling mode:
[No test] [Every ABM cycle]
In constant charge mode:
[No test] [Every day]
[Every week][Every month]
Default Value: [Every ABM cycle]/[Every
week]
[Capacity] [0%] … [100%]
[Runtime] [0min] … [60min]
The alarm triggers when the
set percentage of battery capacity
or remaining back-up time is reached.
Default Value: [20%] [3min]
[0%]...[100%]
If set, automatic restart will
occur only when percentage
of battery charge is reached.
Default Value: [0%]
Low Battery Warning:
Below 3 min. or less than
setting capacity thershold.
Default Value: [0%]
[Auto detection]
[Manual EBM set.]
[Manual battery set.]
Default Value: [Auto detection]
Using standard EBM, UPS detects
automatically the number
of EBM connected
[Yes] [No]
If set to Yes, the UPS automatically
prevents battery from deep
discharge by adapting end of
back-up time voltage threshold.
Warranty void if set to No.
Default Value: [Yes]
Select Battery Tests
and Warnings
Select Battery Settings
Содержание 9PXM
Страница 1: ...p n P 164000669 Revision 09 Eaton 9PXM UPS 4 20kVA Users Guide Eaton 9PXM UPS ...
Страница 4: ......
Страница 8: ...viii 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 Table of Contents ...
Страница 12: ...xii 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 List of Figures ...
Страница 14: ...xiv 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 List of Tables ...
Страница 22: ...8 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 Physical Features ...
Страница 74: ...60 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 Connected Battery Cabinet Option ...
Страница 84: ...70 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 Initial Startup Parameters ...
Страница 110: ...96 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 Communication Slots ...
Страница 114: ...100 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 UPS Firmware Upgrade ...
Страница 120: ...106 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 Receptacle Circuit Breaker Ratings ...
Страница 126: ...112 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 09 Service and Support ...
Страница 130: ...P 16400066909 P 164000669 09 ...