Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01
25
C
Chhaapptteerr 55 O
Oppeerraattiioonn
55..11
S
Sttaarrtt--uupp aanndd N
Noorrm
maall O
Oppeerraattiioonn
NOTE 1
If you ordered a HotSwap MBP, refer to the specific user manual to check the startup
sequence of the UPS with the MBP.
NOTE 2
Verify that the total equipment ratings do not exceed the UPS capacity to prevent an
overload.
To start the UPS:
1.
If optional EBMs are installed, verify that the EBM are connected to the UPS. See
2.
Verify that the UPS terminal blocks are connected to AC source.
3.
Set the upstream circuit breaker (not provided) to the "I" position (On) to switch on the utility power. The
UPS front panel display illuminates and shows EATON logo.
4.
Verify that the UPS status screen shows
, press
to start.
5.
Press the
button on the UPS front panel for at least 3 seconds. The UPS front panel display changes
status to "UPS starting...".
6.
Check the UPS front panel display for active alarms or notices. Resolve any active alarms before
continuing. See section
. If the
indicator is on, do not proceed until all
alarms are clear. Check the UPS status from the front panel to view the active alarms. Correct the alarms
and restart if necessary.
7.
Verify that the
indicator illuminates solid, indicating that the UPS is operating normally and any loads
are powered and protected. The UPS should be in Online mode.
NOTE
The internal batteries charge to 90% capacity in less than 3 hours. However, Eaton
recommends that the batteries charge for 48 hours after installation or long-term
storage.
55..22
S
Sttaarrttiinngg tthhee U
UP
PS
S oonn B
Baatttteerryy
Before using this feature, the UPS must have been powered by utility power with output enabled at least once.
Battery start can be disabled. See Coldstart setting in
To Start the UPS on battery:
1.
Press the
button on the UPS front panel until the UPS front panel display illuminates and shows a
status of "UPS starting...".
The UPS cycles through Standby mode to Battery mode. The
indicator illuminates solid.
The UPS supplies power to your equipment.
2.
Check the UPS front panel display for active alarms or notices. Resolve any active alarms before
continuing. See
.
Check the UPS status from the front panel to view the active alarms. Correct the alarms and restart if
necessary.
Содержание 9PX6KIRTN-L
Страница 16: ...10 Eaton 9PX Lithium Ion User Guide DPD 9PX2205 Rev 01 User Settings ...
Страница 40: ...34 Eaton 9PX Lithium Ion User Guide DPD 9PX2205 Rev 01 Recycling The Used Equipment ...
Страница 44: ...38 Eaton 9PX Lithium Ion User Guide DPD 9PX2205 Rev 01 Compliance Contact ...
Страница 49: ...Eaton 9PX Lithium Ion User Guide DPD 9PX2205 Rev 01 43 Model Specifications EMEA ...
Страница 50: ...DPD 9PX220501 DPD 9PX2205 01 ...