• Air outlet is at the top in the rear of the cabinet
Allow clearance in front and rear of each cabinet for proper air circulation. The
clearance required around the accessory cabinets is shown in the following
table.
Table 5: Accessory cabinet minimum clearances
EBC-F [mm]
EBC-G [mm]
TFC-A [mm]
From the top of the cabinet
500
2)
500
2)
500
From the front of the cabinet 900
900
900
From the rear of the cabinet
100
1)
2)
100
1)
2)
300
1)
From the side of the cabinet 0
3)
0
3)
0
3)
1)
Cabling may require more space.
2)
With an optional ventilation tube: 0 mm.
3)
With
optional vibration dampers: 30 mm.
A DC-rated circuit breaker within each battery cabinet provides protection and
service isolation.
Table 6: Molded case circuit breakers (MCCB) for EBC-F and EBC-G
Rating
(A)
Type
Article No
EBC-F
200A
Eaton NZMN2-A200-S07-DC
191233
(P-122000239)
EBC-G
400A
Eaton NZMN3-A400-S07-DC
189599
(P-122000240)
Use the following 24V shunt-release with early-make auxiliary contact with the
above circuit breakers.
Rating (A)
Type
Article No
200, 400
Eaton NZM2/3-XAHIV24AC/DC
259810
(P-122000148)
3.3 Introduction to 9PHD transformer cabinet
The 9PHD external transformer cabinet (TFC-A) can house one or two
transformers for the UPS system. You can use either isolation transformers or
autotransformers.
You can use the transformers for the UPS input line (a single feed that supplies
both rectifier and bypass inputs), rectifier input line, bypass input line or output
lines. Typically the transformer cabinet is used for input and output, or input and
bypass lines.
Eaton 9PHD Accessory Cabinets TFC-A, EBC-F
and EBC-G
User's and installation guide
©
Eaton Corporation plc 2022. All rights reserved.
Document ID: P-164000538