DPD-9E2305
26
9.3 Battery
Internal batteries
EBM
Specifications
9E1000IR: 36Vdc - 3 x 12V, 7Ah (9Ah max)
9E2000IR: 72Vdc - 6 x 12V, 7Ah (9Ah max)
9E3000IR: 72Vdc - 6 x 12V, 9Ah
9EEBM72R: 72Vdc - 2 string of 6 x 12V, 18Ah
Type
Sealed, maintenance-free, valve-regulated, lead-acid, with minimum 3-5 year float service life at 25°C
(77°F).
9.4 Environmental and safety
Standards
IEC/EN 62040-1 Safety
IEC/EN 62040-2 Electromagnetic Compatibility EMC
IEC/EN 62040-3 Performance
EMC (Emissions)
CISPR32 Class B (for output cable < 10m)
IEC/EN 61000-3-2 Flickers
IEC/EN 61000-3-3 Harmonics
EMC (Immunity)
IEC 61000-4-2, (ESD): 8 kV Contact Discharge / 15 kV Air Discharge
IEC 61000-4-3, (Radiated field): 10 V/m
IEC 61000-4-4, (EFT): 4 kV
IEC 61000-4-5, (Surges): 2 kV Differential Mode / 4 kV Common Mode
IEC 61000-4-6, (Electromagnetic field): 10 V
IEC 61000-4-8, (Conducted magnetic field): 30 A/m
UPS enclosure IP rating
IP20
Earthing system
This UPS can be connected to TN, TT, IT electrical supply system, same
system is supplied to the load.
Operating temperature
0 to 40 °C (32 to 104 °F) in Online mode, with linear derating for altitude
Note: thermal protection switches load to Bypass in case of
overheating.
Storage temperature
0 to 40 °C (32 to 104 °F) with batteries
-25 to 55 °C (-13 to 130 °F) without batteries
Relative humidity
0 to 96 % (without condensation)
Operating altitude
Up to 3,000 meters (9,843 ft) above sea level, no derating for 40°c
(104°F) room temperature
Transit altitude
Up to 10,000 meters (32,808 ft) above sea level
Transit temperature
-25 to 55 °C (-13 to 130 °F)
Audible noise
< 50 dBA at 1 meter typical