10
Led indicator
The following table shows the indicator status and description :
Indicator
Status
Description
Green
On
The UPS is "ON" and the load is protected.
Orange
On
The UPS is in battery mode and the load is protected.
Orange
On
The UPS is in bypass mode.
Red
On
The UPS has an active alarm or fault. See troubleshooting page for additional
information.
5.2 LCD description
①
Operation status
②
Load/equipment status
By default, or after 5 minutes of inactivity, the LCD displays the screen saver.
The backlight LCD automatically dims after 5 minutes of inactivity. Press any button to restore the screen.
Note. If other indicator appears, see troubleshooting page for additional information.
The following table describes the
①
Operation status information provided by the UPS :
①
Operation
status
Description
Action
STANDBY MODE
The UPS is OFF, waiting for start-up
command from user.
Equipment is not powered until button
is pressed
during start up and the green "normal mode" LED
indicator is illuminated.
ONLINE MODE
The UPS is operating normally.
The UPS is powering and protecting the equipment.
BATTERY MODE
A utility failure has occurred, and the
UPS is operating in Battery mode.
The UPS is powering the equipment with battery
power. Prepare your equipment for shutdown.