
Rectifier input
UPS output / bypass
Battery
Rated
power
[kW]
Rated
voltage
[V]
Rated
current
[A]
Maximum
current
[A]
Rated
current
[A]
Maximum
current
[A]
Rated
current
[A]
Maximum
current
[A]
30
380
48
56
46
67
82
98
400
45
53
44
64
82
98
415
44
51
43
61
82
98
40
380
64
75
62
89
110
131
400
60
71
59
85
110
131
415
58
69
57
82
110
131
Notes:
1.
Maximum rectifier current calculated at the -15% voltage tolerance and 102% con-
tinuous overload.
2.
Maximum output/bypass current calculated at continuous 125% overload and at
-15% voltage tolerance.
3.
Maximum battery current calculated at rated load and 1.67 V cell voltage for the
default 32 block string length.
Eaton 93PS UPS 8–40 kW
User's and installation guide
©
Eaton Corporation plc 2016. All rights reserved.
Revision: 003
Document ID: P-164000493
42 (104)