UPS Operating Instructions
Eaton 93PM UPS (20–50 kW, 480V Four Wire – 50 kW Frame) Installation and Operation Manual P-164000540—Rev 4
www.eaton.com/powerquality
6-33
6.4.17 Using the LOAD OFF Command
An UPS shutdown is initiated by the
LOAD OFF
command on the UPS Control screen. The UPS
LOAD OFF
controls the UPSs output by powering down all of the UPSs and de-energizing the critical load.
The UPSs (including Bypass) remains off until restarted.
To use the
LOAD OFF
command:
1.
Tap the
CONTROLS
tab on the main menu navigation bar. The System Control screen is displayed.
CAUTION
All power to the critical load is lost when LOAD OFF is selected in the following step. You should
use this feature only when you want to de-energize the critical load.
2.
Tap the
LOAD OFF
button.
An action confirmation screen is displayed. Follow the on screen prompts to shut down the UPS or to
cancel the shutdown. Selecting
YES
will immediately shut down the UPS and de-energize the critical load.
Selecting
NO
will abort the shutdown
CAUTION
Do not attempt to restart the system after Load Off until the cause of the shutdown has been
identified and cleared.
3.
To restart the UPS after using the
LOAD OFF
follow the procedure in paragraph 6.4.1 or 6.4.2.
WARNING
Power is present inside the UPS cabinet until the upstream input feeder circuit breakers and
battery breakers are opened.
Содержание 93PM UPS
Страница 1: ...Eaton 93PM UPS 20 50 kW 480V Four Wire 50 kW Frame Installation and Operation Manual...
Страница 2: ......
Страница 3: ...Eaton 93PM UPS 20 50 kW 480V Four Wire 50 kW Frame Installation and Operation Manual...
Страница 25: ...Section 1 Installation...
Страница 26: ......
Страница 87: ...Section 2 Operation...
Страница 88: ......
Страница 145: ......
Страница 146: ...P 164000540 4 P 164000540 4...