18
Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03
Table 5. UPS Cabinet Clearances
From Front of Cabinet
914 mm (36") working space
From Top of Cabinet with Top Exhaust
457 mm (18") minimum clearance for ventilation
From Top of Cabinet with Rear Exhaust
457 mm (18”)
From Back of Cabinet with Rear Exhaust
457 mm (18") minimum clearance for ventilation
From Back of Cabinet with Top Exhaust
None Required
From Right Side of Cabinet
None Required
From Left Side of Cabinet
None Required
Figure 4. UPS Cabinet Dimensions (Front and Right Side Views)
Dimensions are in millimeters [inches]
Front View
Side View