Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03
129
CAUTION
In Bypass mode, the critical load is not protected from commercial power interruptions and abnormalities.
1.
Tap the
CONTROLS
tab on the main menu navigation bar. The System Control screen is displayed.
2.
Tap the
GO TO BYPASS
button.
The UPS transfers to Bypass mode. and the critical load is immediately supplied by the bypass source. If
the bypass source is not available, the power module remains on and an alarm sounds.
The
BYPASS
status indicator is illuminated. The power module remains on.
WARNING
Power is present inside the UPS cabinet.
66..33..66
TTrraannssffeerr ffrroom
m B
Byyppaassss ttoo D
Doouubbllee C
Coonnvveerrssiioonn M
Mooddee
To transfer the critical load to Normal mode:
1.
Tap the
CONTROLS
tab on the main menu navigation bar. The System Control screen is displayed.
2.
Tap the
GO ONLINE
button.
The UPS transfers to Double Conversion mode. If the power module is not available, the system remains
on bypass and an alarm sounds.
The
NORMAL
status indicator is illuminated.
66..33..77
TTrraannssffeerr ffrroom
m EES
SS
S M
Mooddee ttoo D
Doouubbllee C
Coonnvveerrssiioonn M
Mooddee
To transfer the load to Standard Normal mode:
1.
Tap the
CONTROLS
tab on the main menu navigation bar. The Control screen is displayed.
2.
Tap the
EAA CONTROLS
tab on the secondary Control menu navigation bar. The
EAA CONTROLS
screen
is displayed.
3.
Tap the
DISABLE ESS
button.
The UPS transfers to Double Conversion mode.
The
NORMAL
status indicator is illuminated.
66..33..88
TTrraannssffeerr ffrroom
m D
Doouubbllee C
Coonnvveerrssiioonn M
Mooddee ttoo EES
SS
S M
Mooddee
To transfer the load to HE Normal mode:
1.
Tap the
CONTROLS
tab on the main menu navigation bar. The Control screen is displayed.
2.
Tap the
EAA CONTROLS
tab on the secondary Control menu navigation bar. The
EAA CONTROLS
screen
is displayed.
3.
Tap the
ENABLE ESS
button.
The UPS transfers to ESS mode if no abnormal power conditions are detected. If abnormal power
conditions are detected, the UPS will wait and transfer to ESS mode when conditions are cleared.
The
NORMAL
status indicator is illuminated.
66..33..99
TTrraannssffeerr ffrroom
m D
Doouubbllee C
Coonnvveerrssiioonn ttoo B
Byyppaassss M
Mooddee aanndd S
Shhuutt D
Doow
wnn U
UP
PM
Mss
To transfer the critical load to Bypass mode and shut down the UPMs:
Содержание 93PM-L 60-1
Страница 1: ...p n P 164000711 Revision 03 20 60 kW 208V UPS Installation and Operation Manual Eaton 93PM L UPS ...
Страница 4: ......
Страница 12: ...xii Eaton 93PM L 20 60 kW 208V UPS Installation and Operation Manual P 164000711 Rev 03 List of Tables ...
Страница 22: ...10 Eaton 93PM L 20 60 kW 208V UPS Installation and Operation Manual P 164000711 Rev 03 Introduction ...
Страница 112: ...100 Eaton 93PM L 20 60 kW 208V UPS Installation and Operation Manual P 164000711 Rev 03 UPS System Installation ...
Страница 156: ...144 Eaton 93PM L 20 60 kW 208V UPS Installation and Operation Manual P 164000711 Rev 03 Communication ...
Страница 164: ...P 16400071103 P 164000711 03 ...