Eaton 93PM Universal Integrated Battery Cabinet (IBC-LW and IBC-LHW) Installation Manual P-164000541—Rev 04
49
Figure 23. Interface Terminal Locations – Eaton 93PM IBC-LW or Eaton 93PM IBC-LHW
TB2
Interface Terminal
Location
Table 12. Eaton 93PM IBC-LW or Eaton 93PM IBC-LHW – TB2 Interface Connections
Terminal TB2
Name
Description
10
Thermal Sensor (Optional)
Contacts used to signal a battery temperature out of specification and to
turn off the battery charger to prevent thermal runaway.
9
Thermal Sensor (Optional)
8
Not Used
7
To Next IBC TB2-2
Contacts used to open battery breaker or disconnect on second, third
and fourth IBCs.
6
To Next IBC TB2-1
5
Battery Detect
Contacts used to indicate whether UPS battery breaker is open or
closed.
4
Battery Detect Common (UPS)
3
Not Used