Installation Plan and Unpacking
3-18 Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev
7
www.eaton.com/powerquality
NOTE
The UL 924 Emergency Lighting UPS utilizes the SIAC-B for maintenance purposes
only. The SIAC-B is not used for protection of conductors and is utilized as a
switching component only. Use the tables provided in the applicable Eaton 93PM
UPS Installation and Operation manual, listed in paragraph 1.7, for the appropriate
conductor and upstream breaker size.
Table 3-5. External Power Wiring Requirements for the Eaton 93PM 150 kW Four-Wire SIAC-B and 93PM 200 kW
Four-Wire SIAC-B – Four Breaker Maintenance Bypass
Basic Unit Rating
Units
Rating 60 Hz
kW
150
200
Input/Output Voltage
Volts
480/480
480/480
AC Input to
Maintenance Bypass
(3) Phases, (1) Neutral – see Note, (1) Ground
A
Maximum Amps
218
291
Minimum Conductor Size (Phase A, B, and C and Neutral)
Number per Phase
AWG or kcmil
(each)
3/0
(2)
300
(2)
Minimum Conductor Size (Ground)
Number per Phase
—
AWG or kcmil
(each)
4
(1)
3
(1)
AC Input to RIB
(3) Phases, (1) Ground
B
Maximum Amps
218
291
Minimum Conductor Size (Phase A, B, and C)
Number per Phase
AWG or kcmil
(each)
2/0
(2)
4/0
(2)
Minimum Conductor Size (Ground)
Number per Phase
—
AWG or kcmil
(each)
4
(1)
3
(1)
AC Output to Critical Load
Full Load Current
(3) Phases, (1) Neutral – see Note, (1) Ground
C
Maximum Amps
180
240
Minimum Conductor Size (Phase A, B, and C and Neutral)
Number per Phase
AWG or kcmil
(each)
2/0
(2)
4/0
(2)
Minimum Conductor Size (Ground)
Number per Phase
—
AWG or kcmil
(each)
4
(1)
3
(1)
Building and Inter-Cabinet Ground
Minimum Conductor Size (Ground)
Number per Phase
—
AWG or kcmil
(each)
4
(1)
4
(1)
NOTE
Callout letters
A
,
B
and
C
map to Figure 5-3 and Figure 5-9.
NOTE
The neutral conductor is sized the same as the phase conductor for balanced and resistive loads. Non-linear loads, up to the
maximum of 1.5x the load current, require a larger neutral conductor and should be sized in accordance with NFPA NEC 70 Article
310.15(B)(5).