Installation Plan and Unpacking
3-2 Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7
www.eaton.com/powerquality
The basic environmental requirements for operation of the SIAC-B are:
l
Ambient Temperature Range: 5–40
C (41–104
F)
l
Recommended Operating Range: 5–40
C (41–104
F)
l
Maximum Relative Humidity: 95%, noncondensing
The SIAC-B operating environment must meet the weight requirements shown in Table 3-1. The SIAC-B size
requirements are shown in Figure 3-1 through Figure 3-3 or Figure 3-4 through Figure 3-6. Dimensions are in
millimeters (inches).
The clearances required around the SIAC-B are the same as the attached UPS.
Table 3-1. SIAC-B Cabinet Weights
Model
Weight
kg (lb)
Shipping
Installed
Point Loading
Eaton 93PM-150-1 Capacity Three-Wire UPS with Left-Mounted or Right-Mounted Three-Wire SIAC-B (2-Breaker)
572 (1259)
541 (1192)
8 at 68 (149)
Eaton 93PM-150-2 Capacity Three-Wire UPS with Left-Mounted or Right-Mounted Three-Wire SIAC-B (2-Breaker)
635 (1399)
604 (1332)
8 at 76 (167)
Eaton 93PM-150-3 Capacity Three-Wire UPS with Left-Mounted or Right-Mounted Three-Wire SIAC-B (2-Breaker)
699 (1540)
668 (1473)
8 at 84 (184)
Eaton 93PM-150-1 Capacity Three-Wire UPS with Left-Mounted or Right-Mounted Three-Wire SIAC-B (4-Breaker)
585 (1289)
554 (1222)
8 at 69 (153)
Eaton 93PM-150-2 Capacity Three-Wire UPS with Left-Mounted or Right-Mounted Three-Wire SIAC-B (4-Breaker)
649 (1430)
618 (1363)
8 at 77 (170)
Eaton 93PM-150-3 Capacity Three-Wire UPS with Left-Mounted or Right-Mounted Three-Wire SIAC-B (4-Breaker)
713 (1570)
682 (1503)
8 at 85 (188)
Eaton 93PM-150-1 Capacity Four-Wire UPS with Left-Mounted or Right-Mounted Four-Wire SIAC-B (2-Breaker)
600 (1322)
569 (1255)
8 at 71(157)
Eaton 93PM-150-2 Capacity Four-Wire UPS with Left-Mounted or Right-Mounted Four-Wire SIAC-B (2-Breaker)
664 (1462)
633 (1395)
8 at 79 (174)
Eaton 93PM-150-3 Capacity Four-Wire UPS with Left-Mounted or Right-Mounted Four-Wire SIAC-B (2-Breaker)
727 (1603)
696 (1536)
8 at 87 (192)
Eaton 93PM-150-1 Capacity Four-Wire UPS with Left-Mounted or Right-Mounted Four-Wire SIAC-B (4-Breaker)
614 (1352)
583 (1285)
8 at 73 (161)
Eaton 93PM-150-2 Capacity Four-Wire UPS with Left-Mounted or Right-Mounted Four-Wire SIAC-B (4-Breaker)
677 (1492)
646 (1425)
8 at 81 (178)
Eaton 93PM-150-3 Capacity Four-Wire UPS with Left-Mounted or Right-Mounted Four-Wire SIAC-B (4-Breaker)
741 (1633)
710 (1566)
8 at 89 (196)
Eaton 93PM-200-1 Three-Wire UPS with Left-Mounted or Right-Mounted Three-Wire SIAC-B (2-Breaker)
624 (1374)
593 (1307)
8 at 74 (163)
Eaton 93PM-200-2 Three-Wire UPS with Left-Mounted or Right-Mounted Three-Wire SIAC-B (2-Breaker)
687 (1514)
656 (1447)
8 at 82 (181)
Eaton 93PM-200-3 Three-Wire UPS with Left-Mounted or Right-Mounted Three-Wire SIAC-B (2-Breaker)
751 (1655)
720 (1588)
8 at 90 (199)
Eaton 93PM-200-4 Three-Wire UPS with Left-Mounted or Right-Mounted Three-Wire SIAC-B (2-Breaker)
815 (1795)
784 (1728)
8 at 98 (216)
Eaton 93PM-200-1 Three-Wire UPS with Left-Mounted or Right-Mounted Three-Wire SIAC-B (4-Breaker)
637 (1404)
606 (1337)
8 at 76 (167)
Eaton 93PM-200-2 Three-Wire UPS with Left-Mounted or Right-Mounted Three-Wire SIAC-B (4-Breaker)
701 (1544)
670 (1477)
8 at 84 (185)
Eaton 93PM-200-3 Three-Wire UPS with Left-Mounted or Right-Mounted Three-Wire SIAC-B (4-Breaker)
765 (1685)
734 (1618)
8 at 92 (202)
Eaton 93PM-200-4 Three-Wire UPS with Left-Mounted or Right-Mounted Three-Wire SIAC-B (4-Breaker)
828 (1825)
797 (1758)
8 at 100 (220)
Eaton 93PM-200-1 Four-Wire UPS with Left-Mounted or Right-Mounted Four-Wire SIAC-B (2-Breaker)
658 (1449)
627 (1382)
8 at 78 (173)
Eaton 93PM-200-2 Four-Wire UPS with Left-Mounted or Right-Mounted Four-Wire SIAC-B (2-Breaker)
721 (1589)
690 (1522)
8 at 86 (190)
Eaton 93PM-200-3 Four-Wire UPS with Left-Mounted or Right-Mounted Four-Wire SIAC-B (2-Breaker)
785 (1730)
754 (1663)
8 at 94 (208)
Eaton 93PM-200-4 Four-Wire UPS with Left-Mounted or Right-Mounted Four-Wire SIAC-B (2-Breaker)
849 (1875)
818 (1808)
8 at 102 (288)
Eaton 93PM-200-1 Four-Wire UPS with Left-Mounted or Right-Mounted Four-Wire SIAC-B (4-Breaker)
871 (1479)
640 (1412)
8 at 80 (226)
Eaton 93PM-200-2 Four-Wire UPS with Left-Mounted or Right-Mounted Four-Wire SIAC-B (4-Breaker)
735 (1619)
704 (1552)
8 at 88 (194)
Eaton 93PM-200-3 Four-Wire UPS with Left-Mounted or Right-Mounted Four-Wire SIAC-B (4-Breaker)
799 (1760)
768 (1693)
8 at 96 (212)
Eaton 93PM-200-4 Four-Wire UPS with Left-Mounted or Right-Mounted Four-Wire SIAC-B (4-Breaker)
862 (1900)
831 (1833)
8 at 104 (229)