100 (133)
13.
Select the CONTROLS symbol in the main menu bar.
The System Control screen is displayed.
14.
If not already selected, select UPS in the System Control screen.
15.
In the UPS System Control screen, select the LOAD OFF
→
BYPASS command and press the
push button.
7.3.2
Starting the UPS in the standard normal mode (default mode)
To start the UPS system:
1.
To unfasten the front door, lift the latch from the bottom, turn it to
the right (counter-clockwise) and swing the door open (see Figure
35).
2.
Make sure that the maintenance bypass switch is open and the
neutral switch is closed.
3.
Close the UPS input feeder circuit breaker.
4.
If the UPSs are wired for dual input, close the UPS bypass input
feeder circuit breaker.
5.
Make sure that the rectifier input switch is closed.
6.
Make sure that the bypass input switch is closed.
7.
Make sure that the output switch is closed.
8.
Make sure that the MBS cover is installed.
9.
Close the door and secure the latch.
10.
Close the internal and external battery breakers.
11.
Wait until the UPS control panel display becomes active and
indicates logic power.
12.
Check that there are no alarms active.
13.
Select the CONTROLS symbol in the main menu bar.
The System Control screen is displayed.
14.
If not already selected, select UPS in the System Control screen.
15.
In the UPS System Control screen, select the LOAD OFF
→
NORMAL command and press the
push button.