Follow the precautions and only perform the described operations. Any
deviation from the instructions can be dangerous to the user or cause
accidental load loss.
.
DANGER
Do not open any other screws in the unit than those holding the cover
plates of the MiniSlots and the MBS locking plate. Failure to recognize
the electrical hazards can prove fatal.
2.4
Environment
The UPS must be installed according to the recommendations in this
document. Never install the UPS in an airtight room, in the presence of
flammable gases, or in an environment exceeding the specifications.
Ensure sufficient amount of ventilation air flow preferably by natural
ventilation. Otherwise, forced (artificial) ventilation must be
implemented. Where forced ventilation is used, the air extracted from
the battery room must be exhausted to the atmosphere outside the
building.
The air inlet and outlet must be located at the best possible location to
create ideal conditions for the exchange of air, i.e. with:
•
Openings on the opposite walls
•
A minimum separation distance of 2 meters when openings on the
same wall
•
It is recommended to locate the air inlet at the floor level and the air
outlet close to the ceiling level.
•
It is recommended to create an airflow scheme for installation of
multiple UPSs.
•
It is recommended to configure the installation layout with cold
aisles and hot aisles due to the UPS front-to-rear airflow protocol.
•
For the free cooling applications, the cooling plan based on the
psychometric chart is highly recommended. The UPS specifications
must not be exceeded.
Excessive amount of dust in the operating environment of the UPS may
cause damage or lead to malfunction. Always protect the UPS from the
outside weather and sunshine. In order to maximize internal battery
Содержание 93E