Eaton 9395XC UPS 1200kW/1200kVA, 1350kW/1350kVA or 1500kW/1500kVA 164001079—Rev 01
Table 4. 480V Air Conditioning and Ventilation Requirements During Full Load Operation
Model
Rating
Input/
Output
Voltage
Heat Rejection BTU/hr
x1000 (kg-cal/hr)
Ventilation Required for
Cooling Air Exhaust
Eaton 9395XC
1200 kW
1200 kVA
480/480
75.08 (256.2)
Approximately 4250 liter/sec
(9000 CFM)
1350 kW
1350 kVA
480/480
84.46 (288.2)
1500 kW
1500 kVA
480/480
93.85 (320.2)
Figure 3. UPS Cabinet Dimensions – HD (Front View)
1999
[78.7]
2688
[105.8]
Dimensions are in millimeters [inches]