![Eaton 9155 UPS Скачать руководство пользователя страница 95](http://html.mh-extra.com/html/eaton/9155-ups/9155-ups_user-manual_527084095.webp)
Eaton 9155 UPS (8–15 kVA) User’s Guide 164201553—Rev H0
87
Table 17. Model Specifications (Continued)
15 kVA Model
DC Voltage (Supply)
192
192
192
192
192
* Input current for the input isolation transformer is 4% higher than for the UPS.
Table 18. Battery Specifications
Battery Type
9 Ah sealed, valve-regulated lead acid (VRLA), maintenance-free, minimum 3-year float service
life at 25°C (77°F), voltage 192 Vdc (96 cells per string)
Number of Strings
Maximum of 22 strings per full configuration, including UPS batteries
(4 EBM-64 cabinets or 3 EBM-96 cabinets, plus UPS batteries)
UPS-32: 2 strings; UPS-64: 4 strings
EBM-64: 4 strings; EBM-96: 6 strings
Battery Replacement
Must be replaced by a qualified service technician
Charger
Service configurable 0.5 34A per string, with overall maximum of 34A (limited by input current).
Default: 3.4A per string
Charging
Internal battery: approximately 3 hours to 80% usable capacity at nominal line voltage after full
load discharge
External battery: no more than 10x discharge time to 90% usable capacity at nominal line voltage
after full load discharge
Start-on-Battery
Allows start of UPS without utility input
Performance
ABM technology increases battery service life, optimizes recharge time, and provides a warning
before the end of useful battery life
Protection
Extended Battery Module output protected by 100A circuit breaker
Table 19. Battery Runtimes (in Minutes) at Full Load
2-High Cabinets
Load
32 Internal UPS
Batteries
(1) EBM-64
(2) EBM-64
(3) EBM-64
(4) EBM-64
15 kVA/13.5 kW
4
23
43
65
88
12 kVA/10.8 kW
6
30
56
85
116
10 kVA/9 kW
8
37
69
106
144
8 kVA/7.2 kW
11
49
91
139
189
3-High Cabinets
Load
64 Internal UPS
Batteries
(1) EBM-96
(2) EBM-96
(3) EBM-96
15 kVA/13.5 kW
13
43
76
113
12 kVA/10.8 kW
18
56
101
149
10 kVA/9 kW
22
69
124
184
Содержание 9155 UPS
Страница 1: ...p n 164201553 Revision H0 8 15 kVA User s Guide Eaton 9155 UPS ...
Страница 8: ...viii Eaton 9155 UPS 8 15 kVA User s Guide 164201553 Rev H0 List of Tables ...
Страница 14: ...6 Eaton 9155 UPS 8 15 kVA User s Guide 164201553 Rev H0 Introduction ...
Страница 18: ...10 Eaton 9155 UPS 8 15 kVA User s Guide 164201553 Rev H0 Safety Warnings ...
Страница 60: ...52 Eaton 9155 UPS 8 15 kVA User s Guide 164201553 Rev H0 UPS System Installation ...
Страница 66: ...58 Eaton 9155 UPS 8 15 kVA User s Guide 164201553 Rev H0 UPS Wiring Diagrams and Schematics ...
Страница 86: ...78 Eaton 9155 UPS 8 15 kVA User s Guide 164201553 Rev H0 UPS Operating Instructions ...
Страница 98: ...164201553H0 164201553 H0 ...