![Eaton 9155 UPS Скачать руководство пользователя страница 33](http://html.mh-extra.com/html/eaton/9155-ups/9155-ups_user-manual_527084033.webp)
Eaton 9155 UPS (8–15 kVA) User’s Guide 164201553—Rev H0
25
Table 5. Input Isolation Transformer Terminal Block Wiring
Wire Function
Terminal
Position
Input Circuit
Breaker Rating
Minimum Wire Size*
Tightening
Torque
Input
L1
TB1-1
8 kVa
10 kVA
12 kVA
15 kVA
60A
80A
100A
100A
3 AWG (26.7 mm
2
)
2 AWG (33.6 mm
2
)
1 AWG (42.4 mm
2
)
1 AWG (42.4 mm
2
)
25 lb in
(2.83 Nm)
L2 (208V)
TB1-2
L2 (240V)
TB1-3
Output
L1
TB1-4
8 kVA
10 kVA
12 kVA
15 kVA
4 AWG (21.2 mm
2
)
3 AWG (26.7 mm
2
)
2 AWG (33.6 mm
2
)
2 AWG (33.6 mm
2
)
25 lb in
(2.83 Nm)
L2
TB1-5
Neutral
TB1-6
Ground
Output
TB1-7
8 AWG
25 lb in
(2.83 Nm)
Input
TB1-8
* Use only 75°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC Code Table 310-16.
Code may require a larger AWG size than shown in this table because of temperature, number of conductors in the conduit, or long
service runs. Follow local requirements.
Table 6. MBM/PDM Terminal Block (TB10) Wiring
Wire
Function
Input Circuit
Breaker Rating
Minimum
Wire Size*
Tightening
Torque
Conduit
Connection
(Entry Size)
Input
Ground
8 AWG
120 lb in
(13.5 Nm)
2” access hole for
1-1/2” conduit
L1
8 kVa
10 kVA
12 kVA
15 kVA
60A
80A
100A
100A
4 AWG (21.2 mm
2
)
3 AWG (26.7 mm
2
)
2 AWG (33.6 mm
2
)
2 AWG (33.6 mm
2
)
Neu-
tral
L2
Output
L1
3 AWG
120 lb in
(13.5 Nm)
2” access hole for
1-1/2” conduit
Neu-
tral
3 AWG
L2
3 AWG
Ground
8 AWG
* Use only 75°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC Code Table 310-16.
Code may require a larger AWG size than shown in this table because of temperature, number of conductors in the conduit, or long
service runs. Follow local requirements.
Содержание 9155 UPS
Страница 1: ...p n 164201553 Revision H0 8 15 kVA User s Guide Eaton 9155 UPS ...
Страница 8: ...viii Eaton 9155 UPS 8 15 kVA User s Guide 164201553 Rev H0 List of Tables ...
Страница 14: ...6 Eaton 9155 UPS 8 15 kVA User s Guide 164201553 Rev H0 Introduction ...
Страница 18: ...10 Eaton 9155 UPS 8 15 kVA User s Guide 164201553 Rev H0 Safety Warnings ...
Страница 60: ...52 Eaton 9155 UPS 8 15 kVA User s Guide 164201553 Rev H0 UPS System Installation ...
Страница 66: ...58 Eaton 9155 UPS 8 15 kVA User s Guide 164201553 Rev H0 UPS Wiring Diagrams and Schematics ...
Страница 86: ...78 Eaton 9155 UPS 8 15 kVA User s Guide 164201553 Rev H0 UPS Operating Instructions ...
Страница 98: ...164201553H0 164201553 H0 ...