background image

CEAG Battery Cabinets

Mounting and Operating Instructions 

CEAG Battery Cabinets

Target group, part 1: Qualified electricans acc. to DIN VDE 0105, part 1
Target group, part 2: Electrical instructed persons

Содержание 26C6

Страница 1: ...CEAG Battery Cabinets Mounting and Operating Instructions CEAG Battery Cabinets Target group part 1 Qualified electricans acc to DIN VDE 0105 part 1 Target group part 2 Electrical instructed persons ...

Страница 2: ...8 With battery set 357 6 Ah 23 3 2 Compact Battery Cabinets 2C3 24 3 2 1 With battery set 5 5 Ah 24 3 2 2 With battery set 8 5 Ah 25 3 2 3 With battery set 14 Ah 26 3 3 Compact Battery Cabinets 10C3 18C3 27 3 3 1 With battery set 5 5 Ah 27 3 3 2 With battery set 8 5 Ah 28 3 3 3 With battery set 14 Ah 29 3 3 4 With battery set 23 3 Ah 30 3 4 Compact Battery Cabinets 10C 31 3 4 1 With battery set 23...

Страница 3: ...inity of the Battery 52 6 2 4 Electrial Requirements Protection Insulation Resistance etc 52 6 2 5 Installation 52 6 3 Preparations 53 6 4 Mounting 53 6 5 Parallel Arrangements 53 6 6 Mounting Positions for AGM Cells and Monoblocs 53 7 Commissioning 54 8 Operating 8 1 Safety Notes 54 9 Maintenance 9 1 Safety Notes 54 9 2 Maintenance 54 9 2 1 General Items and Checks acc to Operating Instructions A...

Страница 4: ...t Protection All information from the contents text drawings pictures and further representations are protected with regard to copy right 1 6 Spare Parts Only use original spare parts from the manufacturer ATTENTION Wrong or faulty spare parts can cause damage failure or col lapse of the system Take care to ensure the same charging state when changing the battery blocs When using unapproved spare ...

Страница 5: ... has approved them 2 4 Responsibility of the Operator Keep the instructions near to the battery system accessible for every person working with the battery and at all times Battery must be in a proper and safe condition when using it Battery has to be checked for intactness before using it Adhere to the information of the instructions completely 2 5 Personnel Requirements Only authorised and skill...

Страница 6: ...3 Ah Rated voltage of all batteries 216 V Number of all batteries 18 á 12 V Battery dimensions in mm L x W x H 168 x 127 x 174 final pole M6 Supply terminals max 35 mm Weight incl Batteries 295 kg Dimensions in mm W x H x D 800 x 2050 x 400 Order no batterie bloc 40066070461 Protection calss IP 20 Wiring Set 4 0071 346 779 included No Length Number 1 300 mm 15 2 1000 mm 2 3 800 mm 1 4 2000 mm 1 1 ...

Страница 7: ...216 V Number of all batteries 18 á 12 V Battery dimensions in mm L x W x H 198 x 168 x 175 final pole M6 Supply terminals max 35 mm Weight incl Batteries 370 kg Dimensions in mm W x H x D 800 x 2050 x 400 Order no batterie bloc 40066070116 Protection calss IP 20 Wiring Set 4 0071 346 779 included No Length Number 1 300 mm 15 2 1000 mm 2 3 800 mm 1 4 2000 mm 1 1 Battery console 1 Battery console 2 ...

Страница 8: ... 216 V Number of all batteries 18 á 12 V Battery dimensions in mm L x W x H 200 x 169 x 176 final pole M M6 Supply terminals max 35 mm Weight incl Batteries 388 kg Dimensions in mm W x H x D 800 x 2050 x 400 Order no batterie bloc 40066041395 Protection calss IP 20 Wiring Set 4 0071 346 779 included No Length Number 1 300 mm 15 2 1000 mm 2 3 800 mm 1 4 2000 mm 1 1 Battery console 1 Battery console...

Страница 9: ...12 V Battery dimensions in mm L x W x H 220 x 172 x 235 final pole F M6 Supply terminals max 35 mm Weight incl Batteries 495 kg Dimensions in mm W x H x D 800 x 2050 x 400 Order no batterie bloc 40066070917 Protection calss IP 20 Wiring Set 4 0071 347 446 included No Length Number 1 360 mm 13 2 800 mm 4 3 800 mm 1 4 2000 mm 1 Right hinge Aperture angle 180 Top view Base fixing 1 Battery console 1 ...

Страница 10: ... 12 V Battery dimensions in mm L x W x H 220 x 172 x 235 final pole F M6 Supply terminals max 35 mm Weight incl Batteries 549 kg Dimensions in mm W x H x D 800 x 2050 x 400 Order no batterie bloc 40066070901 Protection calss IP 20 Wiring Set 4 0071 347 446 included No Length Number 1 360 mm 13 2 800 mm 4 3 800 mm 1 4 2000 mm 1 Right hinge Aperture angle 180 Top view Base fixing 1 Battery console 1...

Страница 11: ...2 V Battery dimensions in mm L x W x H 260 5 x 171 x 239 final pole M M6 Supply terminals max 35 mm Weight incl Batteries 672 kg Dimensions in mm W x H x D 800 x 2050 x 4000 Order no batterie bloc 40066070902 Protection calss IP 20 Wiring Set 4 0071 346 778 included No Length Number 1 440 mm 13 2 800 mm 4 3 800 mm 1 4 2000 mm 1 Right hinge Aperture angle 180 Top view Base fixing 1 Battery console ...

Страница 12: ... 12 V Battery dimensions in mm L x W x H 309 x 172 x 239 final pole M M8 Supply terminals max 35 mm Weight incl Batteries 685 kg Dimensions in mm W x H x D 800 x 2050 x 400 Order no batterie bloc 40066070918 Protection calss IP 20 Wiring Set 4 0071 360 230 included No Length Number 1 350 mm 13 2 800 mm 4 3 800 mm 1 4 2000 mm 1 Right hinge Aperture angle 180 Top view Base fixing 1 Battery console 1...

Страница 13: ... 12 V Battery dimensions in mm L x W x H 307 5x 171 x 239 final pole M6 Supply terminals max 35 mm Weight incl Batteries 750 kg Dimensions in mm W x H x D 800 x 2050 x 400 Order no batterie bloc 40066070821 Protection calss IP 20 Wiring Set 4 0071 360 230 included No Length Number 1 350 mm 13 2 800 mm 4 3 800 mm 1 4 2000 mm 1 Right hinge Aperture angle 180 Top view Base fixing 1 Battery console 1 ...

Страница 14: ...W x H x D 39 8 Ah 200 x 169 x 176 Battery dimensions in mm W x H x D 66 2 Ah 260 5 x 171 x 239 final pole M M6 Supply terminals max 35 mm Weight incl Batteries 1060 kg Dimensions in mm W x H x D 2 x 800 x 2050 x 400 Order no of battery bloc 39 8 Ah 40066041395 Order no of battery bloc 66 2 Ah 40066070902 Protection calss IP 20 Wiring Set 4 0071 346 779 included No Length Number 5 300 mm 15 6 1000 ...

Страница 15: ...ted voltage of all batteries 216 V Number of all batteries 36 á 6 V Battery dimensions in mm L x W x H 272 x 166 x 190 final pole M8 Supply terminals max 35 mm Weight incl Batteries 1200 kg Dimensions in mm W x H x D 2 x 800 x 2050 x 400 Order no batterie bloc 40066070466 Protection calss IP 20 Wiring Set 4 0071 346 775 included No Length Number 1 350 mm 26 2 800 mm 8 3 800 mm 2 4 2000 mm 2 1 Batt...

Страница 16: ...35 Battery dimensions in mm W x H x D 89 4 Ah 307 5 x 171 x 239 final pole F M6 Supply terminals max 35 mm Weight incl Batteries 1300 kg Dimensions in mm W x H x D 2 x 800 x 2050 x 400 Order no of battery bloc 53 7 Ah 40066070901 Order no of battery bloc 89 4 Ah 40066070821 Protection calss IP 20 Wiring Set 4 0071 347 446 included No Length Number 1 360 mm 13 2 800 mm 4 3 800 mm 1 4 2000 mm 1 Wiri...

Страница 17: ... 239 Battery dimensions in mm W x H x D 89 4 Ah 307 5 x 171 x 239 final pole M M6 Supply terminals max 35 mm Weight incl Batteries 1422 kg Dimensions in mm W x H x D 2 x 800 x 2050 x 400 Order no of battery bloc 66 2 Ah 40066070902 Order no of battery bloc 89 4 Ah 40066070821 Protection calss IP 20 Wiring Set 4 0071 346 778 included No Length Number 1 440 mm 13 2 800 mm 4 3 800 mm 1 4 2000 mm 1 Wi...

Страница 18: ... Rated voltage of all batteries 216 V Number of all batteries 36 á 12 V Battery dimensions in mm W x H x D 307 5 x 171 x 239 final pole M6 Supply terminals max 35 mm Weight incl Batteries 1500 kg Dimensions in mm W x H x D 2 x 800 x 2050 x 400 Order no of battery bloc 40066070821 Protection calss IP 20 2 x Wiring Set 4 0071 360 230 included No Length Number 1 350 mm 13 2 800 mm 4 3 800 mm 1 4 2000...

Страница 19: ...erminals max 35 mm Weight incl Batteries 1810 kg Dimensions in mm W x H x D 3 x 800 x 2050 x 400 Order no of battery bloc 39 8 Ah 40066041395 Order no of battery bloc 39 8 Ah 40066070902 Order no of battery bloc 89 4 Ah 40066070821 Protection calss IP 20 Wiring Set 4 0071 346 779 included No Length Number 1 300 mm 15 2 1000 mm 2 3 800 mm 1 4 2000 mm 1 Wiring Set 4 0071 346 778 included No Length N...

Страница 20: ...0 5 x 171 x 239 Ah Final pole M M6 Supply terminals max 35 mm Weight incl Batteries 2172 kg Dimensions in mm W x H x D 3 x 800 x 2050 x 400 Order no of battery bloc 39 8 Ah 40066070902 Order no of battery bloc 89 4 Ah 40066070821 Protection calss IP 20 Wiring Set 4 0071 346 778 included No Length Number 1 440 mm 13 2 800 mm 4 3 800 mm 1 4 2000 mm 1 2 x Wiring Set 4 0071 360 230 included No Length ...

Страница 21: ...tteries 54 á 12 V Battery dimensions in mm L x W x H 307 5 x 171 x 239 Final pole M6 Supply terminals max 35 mm Weight incl Batteries 2250 kg Dimensions in mm W x H x D 3 x 800 x 2050 x 400 Order no of battery bloc 40066070821 Protection calss IP 20 3 x Wiring Set 4 0071 360 230 included No Length Number 1 350 mm 13 2 800 mm 4 3 800 mm 1 4 2000 mm 1 1 Battery console 1 Battery console Right hinge ...

Страница 22: ...1 x 239 Final pole M M6 Supply terminals max 35 mm Weight incl Batteries 2638 kg Dimensions in mm W x H x D 4 x 800 x 2050 x 400 Order no of battery bloc 39 8 Ah 40066041395 Order no of battery bloc 89 4 Ah 40066070821 Protection calss IP 20 Wiring Set 4 0071 346 779 included No Length Number 1 300 mm 15 2 1000 mm 2 3 800 mm 1 4 2000 mm 1 Wiring Set 4 0071 360 230 included No Length Number 1 350 m...

Страница 23: ...Battery dimensions in mm L x W x H 307 5 x 171 x 239 Final pole M6 Supply terminals max 35 mm Weight incl Batteries 3000 kg Dimensions in mm W x H x D 4 x 800 x 2050 x 400 Order no batterie bloc 40066070821 Protection calss IP 20 4 x Wiring Set 4 0071 360 230 included No Length Number 1 350 mm 13 2 800 mm 4 3 800 mm 1 4 2000 mm 1 1 Battery console 1 Battery console 1 Battery console 1 Battery cons...

Страница 24: ...1 2 3 4 Technical Data Type of battery C10 1 8 V Z 20 C 12 V 5 5 Ah Rated voltage of all batteries 216 V Number of all batteries 18 á 12 V Battery dimensions in mm L x W x H 152 x 65 5 x 98 Connectors SR 6 3 mm Faston Supply terminals max 35 mm Weight incl Batteries 100 kg Dimensions in mm W x H x D 600 x 1000 x 300 Order no batterie bloc 40066079643 Wiring Set 4 0071 346 005 included No Length Nu...

Страница 25: ...l Data Type of battery C10 1 8 V Z 20 C 12 V 8 5 Ah Rated voltage of all batteries 216 V Number of all batteries 18 á 12 V Battery dimensions in mm L x W x H 152 x 98 x 98 Connectors SR 6 3 mm Faston Supply terminals max 35 mm Weight incl Batteries 120 kg Dimensions in mm W x H x D 600 x 1000 x 300 Order no batterie bloc 40066079644 Wiring Set 4 0071 346 005 included No Length Number 1 240 mm 15 2...

Страница 26: ... Technical Data Type of battery C10 1 8 V Z 20 C 12 V 14 Ah Rated voltage of all batteries 216 V Number of all batteries 18 á 12 V Battery dimensions in mm L x W x H 181 x 76 x 167 Connectors M6 Supply terminals max 35 mm Weight incl Batteries 220 kg Dimensions in mm W x H x D 600 x 1000 x 350 Order no batterie bloc 40066070825 Wiring Set 400 71 360 242 included No Length Number 1 100 mm 14 2 200 ...

Страница 27: ... 1 2 3 4 Technical Data Type of battery C10 1 8 V Z 20 C 12 V 5 5 Ah Rated voltage of all batteries 216 V Number of all batteries 18 á 12 V Battery dimensions in mm L x W x H 152 x 65 5 x 94 5 Connectors 6 3 mm Faston Supply terminals max 35 mm Weight incl Batteries 150 kg Dimensions in mm W x H x D 600 x 1800 x 350 Order no batterie bloc 40066079643 Wiring Set 4 0071 346 005 included No Length Nu...

Страница 28: ... Rated voltage of all batteries 216 V Number of all batteries 18 á 12 V Battery dimensions in mm L x W x H 152 x 98 x 94 5 Connectors 6 3 mm Faston Supply terminals max 35 mm Weight incl Batteries 170 kg Dimensions in mm W x H x D 600 x 1800 x 350 Order no batterie bloc 40066079644 Wiring Set 4 0071 346 005 included No Length Number 1 240 mm 15 2 900 mm 2 3 600 mm 1 4 1300 mm 1 ZB S 10C3 ZB S 18C3...

Страница 29: ...C10 1 8 V Z 20 C 12 V 14 Ah Rated voltage of all batteries 216 V Number of all batteries 18 á 12 V Battery dimensions in mm L x W x H 181 x 75 x 167 final pole M6 Supply terminals max 35 mm Weight incl Batteries 220 kg Dimensions in mm W x H x D 600 x 1800 x 350 Order no batterie bloc 40066070825 Wiring Set 4 0071 346 779 included No Length Number 1 300 mm 15 2 1000 mm 2 3 800 mm 1 4 2000 mm 1 1 B...

Страница 30: ...C10 1 8 V Z 20 C 12 V 23 3 Ah Rated voltage of all batteries 216 V Number of all batteries 18 á 12 V Battery dimensions in mm L x W x H 168 x 127 x 174 final pole M6 Supply terminals max 35 mm Weight incl Batteries 250 kg Dimensions in mm W x H x D 600 x 1800 x 350 Order no batterie bloc 40066070461 Wiring Set 4 0071 346 779 included No Length Number 1 300 mm 15 2 1000 mm 2 3 800 mm 1 4 2000 mm 1 ...

Страница 31: ...of battery C10 1 8 V Z 20 C 12 V 23 3 Ah Rated voltage of all batteries 216 V Number of all batteries 18 á 12 V Battery dimensions in mm L x W x H 168 x 127 x 174 final pole M6 Supply terminals max 35 mm Weight incl Batteries 295 kg Dimensions in mm W x H x D 800 x 2050 x 400 Order no batterie bloc 40066070461 Wiring Set 4 0071 346 779 included No Length Number 1 300 mm 15 2 1000 mm 2 3 800 mm 1 4...

Страница 32: ...8 V Z 20 C 12 V 32 Ah Rated voltage of all batteries 216 V Number of all batteries 18 á 12 V Battery dimensions in mm L x W x H 198 x 168 x 175 final pole M6 Supply terminals max 35 mm Weight incl Batteries 400 kg Dimensions in mm W x H x D 800 x 2050 x 400 Order no batterie bloc 40066070116 Wiring Set 4 0071 346 779 included No Length Number 1 300 mm 15 2 1000 mm 2 3 800 mm 1 4 2000 mm 1 3 Batter...

Страница 33: ... V Z 20 C 12 V 39 8 Ah Rated voltage of all batteries 216 V Number of all batteries 18 á 12 V Battery dimensions in mm L x W x H 200 x 169 x 176 final pole M M6 Supply terminals max 35 mm Weight incl Batteries 409 kg Dimensions in mm W x H x D 800 x 2050 x 400 Order no batterie bloc 40066041395 Wiring Set 4 0071 346 779 included No Length Number 1 300 mm 15 2 1000 mm 2 3 800 mm 1 4 2000 mm 1 3 Bat...

Страница 34: ... 20 C 12 V 50 4 Ah Rated voltage of all batteries 216 V Number of all batteries 18 á 12 V Battery dimensions in mm L x W x H 220 x 172 x 235 final pole F M6 Supply terminals max 35 mm Weight incl Batteries 495 kg Dimensions in mm W x H x D 800 x 2050 x 400 Order no batterie bloc 40066070917 Wiring Set 4 0071 346 449 included No Length Number 1 300 mm 12 2 440 mm 3 3 700 mm 2 4 300 mm 1 5 1200 mm 1...

Страница 35: ...Circuit Diagrams ZB S 10C EURO ZB 1 200K EURO ZB 1 204K 1 2 3 4 5 Technical Data Type of battery C10 1 8 V Z 20 C 12 V 53 7 Ah Rated voltage of all batteries 216 V Number of all batteries 18 á 12 V Battery dimensions in mm L x W x H 220 x 172 x 235 final pole F M6 Supply terminals max 35 mm Weight incl Batteries 519 kg Dimensions in mm W x H x D 800 x 2050 x 400 Order no batterie bloc 40066070901 ...

Страница 36: ...Type of battery C10 1 8 V Z 20 C 12 V 23 3 Ah Rated voltage of all batteries 216 V Number of all batteries 18 á 12 V Battery dimensions in mm L x W x H 168 x 127 x 174 final pole M6 Supply terminals max 35 mm Weight incl Batteries 320 kg Dimensions in mm W x H x D 800 x 2050 x 600 800x2250x600 for ZB S 26C6 Order no batterie bloc 40066070461 Wiring Set 4 0071 346 779 included No Length Number 1 30...

Страница 37: ...8 V Z 20 C 12 V 32 Ah Rated voltage of all batteries 216 V Number of all batteries 18 á 12 V Battery dimensions in mm L x W x H 198 x 168 x 175 final pole M6 Supply terminals max 35 mm Weight incl Batteries 400 kg Dimensions in mm W x H x D 800 x 2050 x 600 800x2250x600 for ZB S 26C6 Order no batterie bloc 40066070116 Wiring Set 4 0071 346 779 included No Length Number 1 300 mm 15 2 1000 mm 2 3 80...

Страница 38: ...S 10C6 ZB S 18C6 ZB S 26C6 EURO ZB 1 264K EURO ZB 1 264K 2250 1 2 3 4 Technical Data Type of battery C10 1 8 V Z 20 C 12 V 39 8 Ah Rated voltage of all batteries 216 V Number of all batteries 18 á 12 V Battery dimensions in mm L x W x H 200 x 169 x 176 final pole M M6 Supply terminals max 35 mm Weight incl Batteries 409 kg Dimensions in mm W x H x D 800 x 2050 x 600 800x2250x600 for ZB S 26C6 Orde...

Страница 39: ...ZB S 18C6 ZB S 26C6 EURO ZB 1 264K EURO ZB 1 264K 2250 1 2 3 4 5 Technical Data Type of battery C10 1 8 V Z 20 C 12 V 50 4 Ah Rated voltage of all batteries 216 V Number of all batteries 18 á 12 V Battery dimensions in mm L x W x H 220 x 172 x 235 final pole F M6 Supply terminals max 35 mm Weight incl Batteries 505 kg Dimensions in mm W x H x D 800 x 2050 x 600 800x2250x600 for ZB S 26C6 Order no ...

Страница 40: ...10C6 ZB S 18C6 ZB S 26C6 EURO ZB 1 264K EURO ZB 1 264K 1 2 3 4 5 Technical Data Type of battery C10 1 8 V Z 20 C 12 V 53 7 Ah Rated voltage of all batteries 216 V Number of all batteries 18 á 12 V Battery dimensions in mm L x W x H 220 x 172 x 235 final pole F M6 Supply terminals max 35 mm Weight incl Batteries 559 kg Dimensions in mm W x H x D 800 x 2050 x 600 800x2250x600 for ZB S 26C6 Order no ...

Страница 41: ...0C6 ZB S 18C6 ZB S 26C6 EURO ZB 1 264K EURO ZB 1 264K 1 2 3 4 5 Technical Data Type of battery C10 1 8 V Z 20 C 12 V 66 2 Ah Rated voltage of all batteries 216 V Number of all batteries 18 á 12 V Battery dimensions in mm L x W x H 260 5 x 171 x 239 final pole M M6 Supply terminals max 35 mm Weight incl Batteries 672 kg Dimensions in mm W x H x D 800 x 2050 x 600 800x2250x600 for ZB S 26C6 Order no...

Страница 42: ...20 C 12 V 85 7 Ah Rated voltage of all batteries 216 V Number of all batteries 18 á 12 V Battery dimensions in mm L x W x H 309 x 172 x 239 final pole M M8 Supply terminals max 35 mm Weight incl Batteries 685 kg Dimensions in mm W x H x D 800 x 2050 x 600 800x2250x600 for ZB S 26C6 Order no batterie bloc 40066070918 Wiring Set 4 0071 360 231 included No Length Number 1 300 mm 12 2 360 mm 3 3 1500 ...

Страница 43: ...y C10 1 8 V Z 20 C 12 V 89 4 Ah Rated voltage of all batteries 216 V Number of all batteries 18 á 12 V Battery dimensions in mm L x W x H 307 5 x 171 x 239 final pole M6 Supply terminals max 35 mm Weight incl Batteries 750 kg Dimensions in mm W x H x D 800 x 2050 x 600 Order no batterie bloc 40066070821 Wiring Set 4 0071 360 231 included No Length Number 1 300 mm 12 2 360 mm 3 3 1500 mm 2 4 400 mm...

Страница 44: ...Circuit Diagrams 4 1 Wiring 5 5 Ah to 89 4 Ah 4 2 Wiring 118 Ah IMPORTANT NOTE Only one temperature sensor per charger has to be installed A series or parallel connection of the temperature sensor can cause an improper charging of the battery Battery supply line Battery supply line Temperature sensor Temperature sensor ...

Страница 45: ...y Distribution Panel see separate installation instruction 30080001443 IMPORTANT NOTE Only one temperature sensor per charger has to be installed A series or parallel connection of the temperature sensor can cause an improper charging of the battery Battery supply line Dimensions L W D 600 x 170 x 300 PE conductor rail conductor rail conductor rail Temperature sensor ...

Страница 46: ...stribution Panel see separate installation instruction 30080001443 IMPORTANT NOTE Only one temperature sensor per charger has to be installed A series or parallel connection of the temperature sensor can cause an improper charging of the battery Battery supply line Temperature sensor Dimensions L W D 600 x 170 x 300 PE conductor rail conductor rail conductor rail ...

Страница 47: ...ution Panel see separate installation instruction 30080001443 IMPORTANT NOTE Only one temperature sensor per charger has to be installed A series or parallel connection of the temperature sensor can cause an improper charging of the battery Battery supply line Temperature sensor Dimensions L W D 900 x 170 x 300 PE conductor rail conductor rail conductor rail ...

Страница 48: ...oods Code IATA The International AirTransportation Association world wide ICAO Civil Aviation Organization sTechnical Instructions for the Safe Transport of Dangerous Goods by Air 5 6 Transport Inspection Check delivery on receipt for completeness and for transport damages immediately If external damage is detected do not accept the delivery except under protest 5 7 Packaging If no return agreemen...

Страница 49: ...orage period of 6 months then every 3 months afterwards storage at 30 C after a storage period of 4 months then every 2 months afterwards When measured open circuit voltage is 2 11V C battery has to be recharged Trickle charging should be considered necessary when the measured open circuit voltage OCV is 2 11 V C Trickle charging means continuous charge at a low rate approximately equivalent to th...

Страница 50: ...ists of abridgements from national and international standards and guidelines See EN 50272 2 for further information Also observe Ope rating Instructions and Installation Instructions 6 2 1 Temperature AGM batteries are developed to be operated within a wide temperature range 15 C and 55 C The battery room temperature should be between 10 C and 30 C The optimum operating temperature is the nominal...

Страница 51: ... voltage 500 V 100 kOhm R 10 MOhm Note 1 To make the first part of the requirement effective personnel shall wear anti static footwear when carrying out mainte nance work on the battery The footwear shall comply with EN 345 Note 2 Arm s reach 1 25 m distance Definition of arm s reach see HD 384 4 41 Room inlets and outlets The layout for air circulation should be as shown below 6 2 3 Ventilation B...

Страница 52: ... The dispersion of explosive gas depends on the gas release rate and the ventilation close to the source of release 6 2 4 Electrical requirements protection insulation resistance etc To prevent a build up of static electricity when handling batte ries clothing materials safety boots and gloves are required to have a surface resistance 108 Ohm and an insulation resistance of 105 Ohm From EN 50272 2...

Страница 53: ...allation work is completed lightly coat the connec tion surfaces with the terminal grease supplied This prevents corrosion but is not mandatory Check total battery voltage which should correspond to the number of monoblocs connected in series The open circuit voltage of single cells should not vary from each other by more than 0 02V among each other For monobloc batteries the following maximum dif...

Страница 54: ...ge and current settings the discharge conditions the temperature levels the storage conditions the cleanliness of the battery and equipment and other conditions relevant to safety issues and battery s service life battery room ventilation for example Periodic discharges can be used to assess the available operating endurance to detect faulty cells monoblocs and ageing symptoms of the battery in or...

Страница 55: ...rs can cause serious damage to the battery Ensure the same char ging state when changing the battery blocs RECOMMENDATION not more than 25 of the battery packs of a battery set should be replaced Therefore with 18 packs not more than 5 packs should be replaced When 50 of the expected service life is exceeded and single battery packs fail the complete set should be replaced 11 1 Ordering Spare Part...

Страница 56: ...ned by date Security signs attached by date 1 Start Up Check all cells blocks for mechanical damage correct polarity and firmly seated connectors T orques as shown in table 1 apply for screw connectors Before installation the supplied rubber covers should be fitted to both ends of the connector cables pole covers Control of insulation resistance New batteries 1M Ù Used batteries 100 Ù Volt Connect...

Страница 57: ... 2 32 20 A 400 FT 2 29 2 32 20 A 500 2 30 2 35 20 A 600 2 27 2 30 20 A 700 2 27 2 30 20 T able 4 Charge voltage in buffer operation d Battery operation charge discharge operation The load is only supplied by the battery The charging process depends on the application and must be carried out in accordance with the recommendations of the battery manufacturer 2 3 Maintaining the full charge float cha...

Страница 58: ...tage by more than the values given in table 7 or if the surface temperature dif ference between cells blocks exceeds 5K the service agent should be contacted Deviations of the battery voltage from the value given in table 2 acc to the number of cells must be corrected Annual visual check Screw connections Screw connections without locking devices have to be checked for tightness Battery installati...

Страница 59: ...59 Mounting and Operating Instructions CEAG Battery Cabinets 40071860035 N March 2016 www ceag de ...

Страница 60: ...vide a reliable efficient and safe power supply where it is needed most Eaton s experts have comprehensive in depth specialist knowledge in the area of energy management in the most diverse of sectors and therefore they are able to provide customer specific inte grated solutions to meet the most challenging demands of its customers It is our highest priority always to find the right solution for e...

Отзывы: