10 Wiring
ESR5-NO-41-24VAC-DC
12/19 MN049009EN
www.eaton.com
15
10.1 Signal generator connection versions
▶
Connect suitable signal generators to S11/S12.
Figure 9: Signal generator connection versions
a
Single-channel connection
10.2 Start and feedback circuit connection variants
Automatic start
▶
Bridge the contacts S33/S34.
Manual start
▶
Connect a reset button to contacts S33/S34.
A connected reset button is not monitored.
Start and feedback circuit
▶
Place the relevant N/C contact in path S33/S34 to monitor external
contactors or extension devices with force-guided contacts.
Figure 10:Start and feedback circuit connection variants
a
Automatic start
b
Manual start with monitored contact extension
c
Manual start
①
S11
S12
( )
( )
①
③
③
S34
S33
S34
S33
S34
S33
K4
K3
24 V DC
24 V DC