Instructional Leaflet

 P26841

Effective August 2014
Supersedes July 2014

Contact

Blocks

2

1

Adapter

Locating

Nib

Operator

Ratings

Hazardous Location Class I Division 2 pushbuttons and indicat-

ing lights include both the 10250T and E34 corrosion-resistant 

product lines. The 10250T1H (CBFS) factory-sealed contact 
blocks have one NO and one NC contact.

For use on a flat surface of Type 1, 2, 3, 3S*, 3R, 4, 4X,

12 and 13 enclosures.

* Applies to indicating lights only.

UL Listed and CSA Certified for Class I Division 2

Groups B, C, D, and Class I Zone 2, Group IIB + H2.

WARNING

A LENS MUST BE ATTACHED TO ALL ILLUMINATED 

DEVICES

10250T/E34 Pushbuttons and Indicating Lights Class I 

Division 2 Application and Installation Instructions

Contact Ratings

 ............................................. A600, Q300

Ingress Protection

 ..................................................... IP65

Temperature Codes 

per NEC Table 500-5(d) for indicating 

lights and illuminated operators having a maximum tempera-

ture over 100°C: 

10250T

E34

Temp. code

201H

RB120H

T3C

471H

SB120H

T3C

80H

-

T3C

All selector switches with lamp 120MB

T3C

202H

RB240H

T3A

472H

SB240H

T3B

81H

-

T3B

All illuminated devices with lamp 1835

T4A

WARNING

TOUT DISPOSITIF LUMINEUX DOIT COMPORTER UNE 

LENTILLE

Operator And Adapter Assembly

1.  Assemble adapter to operator or light unit and torque 

mounting screws to 7 – 9.5 lb-in (0.8 – 1.07 Nm).

2.  Assemble contact block to adapter and torque mounting 

screws to 12 – 16 lb-in (1.36 – 1.81 Nm). Contact block 
mounting location “1” is referenced to the panel locat-
ing nib on operator. See illustrations.

®

       IND. CONT. EQ.

FOR HAZARDOUS 

     LOCATIONS.

           A162

®