Effective February 2018
Supersedes July 2011
Instructions and Operation
P20442
Heavy Duty Oiltight Selector Switch
Units - 10250T/91000T or E34
®
Underwriters Laboratories Listed
For use on a flat surface of Type
1, 2, 3, 3R, 4, 4X, 12 and 13
enclosures. IP 65
ASSEMBLY INSTRUCTIONS
1. Select the desired schematic circuit function from the chart below and
note in your cam column the type of contacts, N.O. or N.C., the “A” and
“B” circuit locations, and any series or parallel jumper connections the may
be required.
2. Choose contact blocks that have the required schematic circuits and
assemble in any convenient sequence that fulfills the “A” and “B” circuit
location requirements.
NOTE: Single circuit contact blocks, if used, must be last in the stack and
positioned so that the plunger motion is transmitted through.
3. Make the indicated series or parallel jumper connections.
(10250T/91000TA70,TA71).
4. If this operator was received without an operating cap, assemble the
separately purchased cap, assemble the separately purchased cap and secure
with the screws provided.
NOTES: Single, double and 2NO-2NC contact blocks are available. Six contacts
can be stacked in each of the two circuit locations making a maximum of
twelve circuits possible.
For additional selector switch explanation ask for manual NU-118.
The two sections of the operating cam of this selector switch work
independently, so it is important that the contact blocks be oriented with
their plungers in the correct “A” and “B” circuit locations. The sketch below
identifies these positions with respect to the locatin nib or marked top.
Sketch shows
VERTICAL MOUNTING
. For
HORIZONTAL MOUNTING
loosen the set screw and assemble so that the locating nib is at the left.
ILLUMINATED GASKET INSTRUCTIONS
This operator was shipped with
the gasket oriented for
VERTICAL MOUNTING
using lever lens and the
new type knob lens.
For
HORIZONTAL MOUNTING
(or VERTICAL MOUNTING using the old
type knob) carefully peel the lens gasket, rotate it 90°, and press onto the
operator. (Lens screws will now thread into alternate holes).
LAMB REMOVAL TOOL For Trans. Type Cat. No. 10250TA74 for Full Voltage
Type E30KV1.
1. Drill mounting hole for vertical or horizontal mounting per one of the figures
above.
2. ensure sealing gasket is in the place on the operator. Align location nib
of the operator with notch in the panel and insert operator through mount-
ing hole.
3. Place legend plate and mounting nut over operator. Tighten mounting
nut. If applicable assemble buttons to operator. Tighten securely (5 ft-lbs)
(6.8 Nm).
4. Torque terminals to 12 in/lbs (1.4 Nm).
For ease of assembly, we recommend the following tools:
91000T/10250TA95 (for 10250T/91000T octagonal nut, E29 and E30 line)
E22CW (for 10250T/91000T octagonal nuts, E22, E30 and E34)
5. Torque contact block stacking screws to 5-7 in/lbs (0.57- 0.79 Nm)
The selector switch operator in this package may not be complete. A knob,
lever, coin slot or knob type lens operating cap is required wich may be
merchandised and packaged separately.
WIRING INSTRUCTIONS
The illustration shows the circuit conditions that result for each position of
the selector switch.
Heavy lines indicates
costumers connections.
Light lines are factory
installed jumpers
X=circuit closed
O=circuit open
L=Left
C=Center
R=Right
1-2-3-4=4 position switch
ASSEMBLY INSTRUCTIONS
US 60/75°C COPPER CONDUCTORS ONLY
LIGHT MODULE OF CONTACT BLOCK
Vertical Mounting
Lever
New
Knob
For Replacement Gasket Order PT #32-803
Grounding nibs
Locating nib
or top
Set screw
Use 1/16”
Allen Wrench
Circuit
“A”
Circuit
“B”
Retaining Nut
To be changed in Coin
Slot Assembly
Operating cab
Knob, Lever, Coin, Slot, Key or Knob
Type Lense
1A
1B
X O
O X
L R
10250T/91000T20
SERIES OR E34
1A
1B
X O O
L C R
COM
10250T/91000T21
SERIES OR E34
O O X
10250T/91000T22
SERIES OR E34
X O O
O O X
COM
L C R
O X O
10250T/91000T46
SERIES OR E34
O O O X
O O X O
O X O O
X O O O
COM
1 2 3 4
.60 (15.2 mm)
1.20 (30.5 mm)
.136 (3.5 mm) dia. hole or
.180 (4.6 mm) rectangular
notch
VERTICAL MOUNTING
HORIZONTAL MOUNTING