background image

Effective February 2018
Supersedes July 2011

Instructions and Operation

 P20442

Heavy Duty Oiltight Selector Switch

Units - 10250T/91000T or E34

®

Underwriters Laboratories Listed

For use on a flat surface of Type 

1, 2, 3, 3R, 4, 4X, 12 and 13 

enclosures. IP 65

ASSEMBLY INSTRUCTIONS

1. Select the desired schematic circuit function from the chart below and 

note in your cam column the type of contacts, N.O. or N.C., the “A” and 

“B” circuit locations, and any series or parallel jumper connections the may 

be required.

2. Choose contact blocks that have the required schematic circuits and 

assemble in any convenient sequence that fulfills the “A” and “B” circuit 

location requirements.

NOTE: Single circuit contact blocks, if used, must be last in the stack and 

positioned so that the plunger motion is transmitted through.

3. Make the indicated series or parallel jumper connections.

(10250T/91000TA70,TA71).

4. If this operator was received without an operating cap, assemble the 

separately purchased cap, assemble the separately purchased cap and secure 

with the screws provided.

NOTES: Single, double and 2NO-2NC contact blocks are available. Six contacts 

can be stacked in each of the two circuit locations making a maximum of 

twelve circuits possible.

For additional selector switch explanation ask for manual NU-118.

The two sections of the operating cam of this selector switch work 

independently, so it is important that the contact blocks be oriented with 

their plungers in the correct “A” and “B” circuit locations. The sketch below 

identifies these positions with respect to the locatin nib or marked top.

Sketch shows 

VERTICAL MOUNTING

. For 

HORIZONTAL MOUNTING 

loosen the set screw and assemble so that the locating nib is at the left.

ILLUMINATED GASKET INSTRUCTIONS

 This operator was shipped with 

the gasket oriented for 

VERTICAL MOUNTING

 using lever lens and the 

new type knob lens.
For 

HORIZONTAL MOUNTING

 (or VERTICAL MOUNTING using the old 

type knob) carefully peel the lens gasket, rotate it 90°, and press onto the 

operator. (Lens screws will now thread into alternate holes).
LAMB REMOVAL TOOL For Trans. Type Cat. No. 10250TA74 for Full Voltage 

Type E30KV1.

1. Drill mounting hole for vertical or horizontal mounting per one of the figures 

above.

2. ensure sealing gasket is in the place on the operator. Align location nib 

of the operator with notch in the panel and insert operator through mount-

ing hole.

3. Place legend plate and mounting nut over operator. Tighten mounting 

nut. If applicable assemble buttons to operator. Tighten securely (5 ft-lbs) 

(6.8 Nm).

4. Torque terminals to 12 in/lbs (1.4 Nm).

For ease of assembly, we recommend the following tools:

   91000T/10250TA95     (for 10250T/91000T octagonal nut, E29 and E30 line) 

             E22CW              (for 10250T/91000T octagonal nuts, E22, E30 and E34)

5. Torque contact block stacking screws to 5-7 in/lbs (0.57- 0.79 Nm)

The selector switch operator in this package may not be complete. A knob, 

lever, coin slot or knob type lens operating cap is required wich may be 

merchandised and packaged separately.

WIRING INSTRUCTIONS 

The illustration shows the circuit conditions that result for each position of 

the selector switch.

Heavy lines indicates 

costumers connections.

Light lines are factory 

installed jumpers

X=circuit closed

O=circuit open

L=Left

C=Center

R=Right

1-2-3-4=4 position switch

ASSEMBLY INSTRUCTIONS

 

US 60/75°C COPPER CONDUCTORS ONLY

LIGHT MODULE OF CONTACT BLOCK

Vertical Mounting

Lever

New 

Knob

For Replacement Gasket Order PT #32-803

Grounding nibs

Locating nib 

or top

Set screw

Use 1/16” 

Allen Wrench

Circuit 

“A”

Circuit 

“B”

Retaining Nut

To be changed in Coin 

Slot Assembly

Operating cab 

Knob, Lever, Coin, Slot, Key or Knob

Type Lense

1A

1B

X       O

O       X

L      R

10250T/91000T20

SERIES OR E34

1A

1B

X    O    O

L    C  R

COM

10250T/91000T21

SERIES OR E34

O    O    X

10250T/91000T22

SERIES OR E34

X    O  O

O    O  X

COM

L    C  R

O    X  O

10250T/91000T46

SERIES OR E34

O  O  O  X

O  O  X  O

O  X  O  O

X  O  O  O

COM

1  2  3  4

.60 (15.2 mm)

1.20 (30.5 mm)

.136 (3.5 mm)  dia. hole or

.180 (4.6 mm) rectangular

notch

VERTICAL MOUNTING

HORIZONTAL MOUNTING