CLINK II SCU MANAGER
troubleshooting guide
version 5.0
62
Table 58: Fault type classification
Fault type
Description
Minor Recoverable fault
The device detected a problem with itself, which is thought to be recovera-
ble. The problem does not cause the device to go into one of the faulted
states. See 6.2.
Minor Unrecoverable Fault
The device detected a problem with itself, which is thought to be unrecov-
erable. The problem does not cause the device to go into one of the
faulted states. See 6.2.
Major Recoverable Fault
The device detected a problem with itself, which caused the device to go
into the “Major Recoverable Fault” state. See 6.2.
Major Unrecoverable Fault
The device detected a problem with itself, which caused the device to go
into the “Major Unrecoverable Fault” state. See 6.2.
Table 59: SCU fault messages
Name
Range
Description
Param
eter
type
Major Recoverable Fault
0 - 10
0
=
No Fault
Actual
1
=
Duplicate Digital Input Function
2
=
Duplicate Digital Output Function
3
=
Invalid Current Configuration
4
=
Invalid Nominal Current
=
=
5
=
Invalid Nominal Power
6
=
Invalid Motor Weight
7
=
Invalid Stall Time
8
=
Invalid Trip Time At 1.5 In
9
=
Invalid Warning Temperature Rise
10
=
General Configuration Failure