DIN Rail Energy Meter for Single and Three Phase Electrical Systems 

 

 

 

 

 

 

 

 

 

 
 
 
 
 

                                                                           

 

 
 

 

Measures kWh Kvarh, KW, Kvar, KVA, P,   

        F, PF, Hz, dmd, V, A, THD,etc.   

 

Bi-directional measurement IMP & EXP 

 

Two pulse outputs 

 

RS485 Modbus 

 

Din rail mounting 35mm 

 

1/5A CT connection 

 

Better than Class 1 / B accuracy

   

 

                                                 

USER MANUAL   

                                                          2016 V4.8

 

Содержание SDM630MCT V2

Страница 1: ... de SDM630MCT V2 DIN Rail Energy Meter for Single and Three Phase Electrical Systems Measures kWh Kvarh KW Kvar KVA P F PF Hz dmd V A THD etc Bi directional measurement IMP EXP Two pulse outputs RS485 Modbus Din rail mounting 35mm 1 5A CT connection Better than Class 1 B accuracy USER MANUAL 2016 V4 8 ...

Страница 2: ...protected This unit can be powered from a separate auxiliary AC or DC supply Alternatively it can be powered from the monitored supply where appropriate Unit Characteristics The Unit can measure and display Line voltage and THD total harmonic distortion of all phases Line Frequency Currents Current demands and current THD of all phases Power maximum power demand and power factor Active energy impo...

Страница 3: ...mp kWh Terminals 11 12 The pulse width for pulse 1 Terminals 9 10 can be set from the set up menu Start Up Screens 1 The first screen lights up all display segments and can be used as a display check 2 The second screen indicates the firmware installed in the unit and its build number 3 The interface performs a self test and indicates the result if the test passes After a short delay the screen wi...

Страница 4: ...ck button 2 Select the Frequency and Power factor display screens In Set up Mode this is the Up button 3 Select the Power display screens In Set up Mode this is the Down button 4 Select the Energy display screens In Set up mode this is the Enter or Right button Voltage and Current Each successive pressing of the button selects a new range 1 1 Phase to neutral voltages 3p4w 1 2 Phase to neutral vol...

Страница 5: ...info bg etech de 4 3 1 Phase to neutral voltage THD 3p4w 3 2 Phase to neutral voltage THD 3p3w 4 Current THD for each phase Frequency and Power factor and Demand Each successive pressing of the button selects a new range 1 Frequency and Power Factor total 2 Power Factor of each phase ...

Страница 6: ...GmbH www stromzähler eu info bg etech de 5 3 Maximum Power Demand 4 Maximum Current Demand Power Each successive pressing of the button select a new range 1 Instantaneous Active Power in kW 2 Instantaneous Reactive Power in kVAr 3 Instantaneous Volt amps in KVA ...

Страница 7: ...mzähler eu info bg etech de 6 4 Total kW kVArh kVA Energy Measurements Each successive pressing of the button selects a new range 1 1 Imported active energy in kWh 1 2 Exported active energy in kWh 2 1 Imported reactive energy in kVArh 2 2 Exported reactive energy in kVArh ...

Страница 8: ...in kVArh Setting Up To enter set up mode pressing the button for 3 seconds until the password screen appears Setting up is password protected so you must enter the correct password default 1000 before processing If an incorrect password is entered the display will show PASS Err To exit setting up mode press repeatedly until the measurement screen is restored ...

Страница 9: ...selection The SET indicator will appear 5 Having completed a parameter setting press to return to a higher menu level The SET indicator will be removed and you will be able to use the and buttons for further menu selection 6 On completion of all setting up press repeatedly until the measurement screen is restored Number Entry Procedure When setting up the unit some screens require the entering of ...

Страница 10: ...nter the change password routine The new password screen will appear with the first digit flashing 2 2 Use and to set the first digit and press to confirm your selection The next digit will flash 2 3 Repeat the procedure for the remaining three digits 2 4 After setting the last digit SET will show Press to exit the number setting routine and return to the Set up menu SET will be removed ...

Страница 11: ...and measurement The options are off 5 8 10 15 20 30 60 minutes 1 From the set up menu use and buttons to select the DIT option The screen will show the currently selected integration time 2 1 Press to enter the selection routine The current time interval will flash 2 2 Use and buttons to select the time required 2 3 Press to confirm the selection SET indicator will appear Press to exit the DIT sel...

Страница 12: ...t as 0 the backlit will always be on 2 Press to enter the selection routine The current time interval will flash The options can be 0 5 10 30 60 120minutes Use and buttons to select the time required Then press to confirm the set up Supply System Use this section to set the type of power supply being monitored 1 From the Set up menu use and buttons to select the System option The screen will show ...

Страница 13: ...d to the main Set up Menu CT The CT option sets the secondary current CT2 1A or 5A of the current transformer CT that wires to the meter 1 From the Set up menu use and buttons to select the CT option 2 Secondary CT setting Press to enter the CT secondary current selection routine 5A 1A 3 Set CT Ratio value Press to enter the CT Ratio setting screen The range is from 0001 to 9999 Example If set the...

Страница 14: ...etting Press to enter the PT secondary voltage selection routine The range is from 100 to 500V 3 Set PT ratios value Press to enter the PT ratio screen The range is from 0001 to 9999 For example if set the ratio to be 100 it means the primary voltage equals secondary voltagex100 Pulse output This option allows you to configure the pulse output The output can be set to provide a pulse for a defined...

Страница 15: ...nd buttons to choose kWh or kVArh On completion of the entry procedure press to confirm the setting and press to return to the main set up menu Pulse rate Use this to set the energy represented by each pulse Rate can be set to 1 pulse per 0 01kWh 0 1kWh 1kWh 10kWh 100 1000kWh It shows 1 impulse 10kWh kVArh 1 From the Set up menu use and buttons to select the Pulse Rate option ...

Страница 16: ... to confirm the setting and press to return to the main set up menu Pulse Duration The energy monitored can be active or reactive and the pulse width can be 200 100 or 60ms It shows pulse width of 200ms 1 1 From the Set up menu use and buttons to select the Pulse width option 1 2 Press to enter the selection routine The current setting will flash Use and buttons to choose pulse width On completion...

Страница 17: ... parameters are selected from Front panel RS485 Address The range is from 001 to 247 1 From the Set up menu use and buttons to select the Address ID 2 1 Press button to enter the selection routine The current setting will be flashing 2 2 Use and buttons to choose Modbus Address 001 to 247 On completion of the entry procedure press button to confirm the setting and press button to return the main s...

Страница 18: ...From the Set up menu use and buttons to select the Baud Rate option 2 1 Press to enter the selection routine The current setting will flash 2 2 Use and buttons to choose Baud rate 2 4k 4 8k 9 6k 19 2k 38 4k On completion of the entry procedure press to confirm the setting and press to return to the main set up menu ...

Страница 19: ...From the Set up menu use and buttons to select the Parity option 2 1 Press to enter the selection routine The current setting will flash 2 2 Use and buttons to choose Parity EVEN ODD NONE Default is NONE On completion of the entry procedure press to confirm the setting and press to return to the main set up menu ...

Страница 20: ...ons to select the Stop Bit option 2 1 Press to enter the selection routine The current setting will flash 2 2 Use and buttons to choose Stop Bit 2 or 1 On completion of the entry procedure press to confirm the setting and press to return to the main set up menu Note Default is 1 and only when the parity is NONE that the stop bit can be changed to 2 ...

Страница 21: ... From the Set up menu use and buttons to select the reset option 2 Press to enter the selection routine The MD will flash Press to confirm the setting and press to return to the main set up menu Reverse connected current inputs correction set up 1 use and buttons to select page SET sys cont 2 1 Press to enter Phase A the default is Frd forward 2 2 use and buttons to Phase B or C setting pages ...

Страница 22: ...omzähler eu info bg etech de 21 How to operate if phase A is reversely connected 1 Go to phase A setting page 2 Press to enter the selection routine The Frd will flash Use button to change Frd to Rev Press to confirm the setting and press to return to the main set up menu ...

Страница 23: ...e last Demand reset Power factor Maximum neutral demand current since the last Demand reset for three phase supplies only Energy Measurements Imported Exported active energy 0 to 9999999 9 kWh Imported Exported reactive energy 0 to 9999999 9 kVArh Total active energy 0 to 9999999 9 kWh Total reactive energy 0 to 9999999 9 kVArh Measured Inputs Voltage inputs through 4 way fixed connector with 2 5m...

Страница 24: ...gnments kW kVArh are configured through the Set up screens Pulse Output The unit provides two pulse outputs Both pulse outputs are passive type Pulse output 1 is configurable The pulse output can be set to generate pulses to represent total kWh or kVarh The pulse constant can be set to generate 1 pulse per 0 01 10 Wh VArh 0 1 100 Wh VArh 1 1 kWh kVArh 10 10 kWh kVArh 100 100 kWh kVArh 1000 1000 kW...

Страница 25: ...s Ambient temperature 23 C 1 C Input frequency 50 or 60Hz 2 Input waveform Sinusoidal distortion factor 0 005 Auxiliary supply voltage Nominal 1 Auxiliary supply frequency Nominal 1 Auxiliary supply waveform if AC Sinusoidal distortion factor 0 05 Magnetic field of external origin Terrestrial flux Environment Operating temperature 25 C to 55 C Storage temperature 40 C to 70 C Relative humidity 0 t...

Страница 26: ...B G e tech and EASTRON SDM630MCT V2 User Manual B G e tech GmbH www stromzähler eu info bg etech de 25 Dimensions ...

Страница 27: ...B G e tech and EASTRON SDM630MCT V2 User Manual B G e tech GmbH www stromzähler eu info bg etech de 26 Installation Three phase four wire ...

Страница 28: ...B G e tech and EASTRON SDM630MCT V2 User Manual B G e tech GmbH www stromzähler eu info bg etech de 27 three phase three wire X ...

Страница 29: ...B G e tech and EASTRON SDM630MCT V2 User Manual B G e tech GmbH www stromzähler eu info bg etech de 28 Single phase two wire ...

Отзывы: