EASTRON SDM630-Mbus V2 User Manual 

                                                                                                                               

 

EASTRON Germany @ B+G e-tech GmbH 

 Franz-Mehring Str. 36 

 01979 Lauchhammer 

WEB:    www.eastron-germany.de      Mail:    [email protected]      Fax:    +49 3574 4675519

 

 

 

SDM630-Mbus V2 

DIN Rail Smart Meter for Single and Three Phase Electrical Systems 

 

                           

 

 
                                                                                       

 

Measures kWh Kvarh, KW, Kvar, KVA, P,   

        F, PF, Hz, dmd, V, A, etc.   

 

Bi-directional measurement IMP & EXP 

 

Two pulse outputs 

 

Mbus 

 

Din rail mounting 35mm 

 

100A direct connection 

 

Better than Class 1 / B accuracy   

                                                     

 

 

USER MANUAL   

                            2016 V1.2

Содержание SDM630-Mbus V2

Страница 1: ... Mail info bg etech de Fax 49 3574 4675519 SDM630 Mbus V2 DIN Rail Smart Meter for Single and Three Phase Electrical Systems Measures kWh Kvarh KW Kvar KVA P F PF Hz dmd V A etc Bi directional measurement IMP EXP Two pulse outputs Mbus Din rail mounting 35mm 100A direct connection Better than Class 1 B accuracy USER MANUAL 2016 V1 2 ...

Страница 2: ...haracteristics The Unit can measure and display Line voltage and THD total harmonic distortion of all phases Line Frequency Currents Current demands and current THD of all phases Power maximum power demand and power factor Active energy imported and exported Reactive energy imported and exported The unit has password protected set up screens for Changing password Supply system selection 1p2w 3p3w ...

Страница 3: ...ild number 3 The interface performs a self test and indicates the result if the test passes After a short delay the screen will display active energy measurements Measurements The buttons operate as follows 1 Selects the Voltage and Current display screens In Set up Mode this is the Left or Back button 2 Select the Frequency and Power factor display screens In Set up Mode this is the Up button 3 S...

Страница 4: ...w eastron germany de Mail info bg etech de Fax 49 3574 4675519 3 Voltage and Current Each successive pressing of the button selects a new range 1 1 Phase to neutral voltages 3p4w 1 2 Phase to neutral voltages 3p3w 2 Current on each phase 3 1 Phase to neutral voltage THD 3p4w 3 2 Phase to neutral voltage THD 3p3w ...

Страница 5: ...WEB www eastron germany de Mail info bg etech de Fax 49 3574 4675519 4 4 Current THD for each phase Frequency and Power factor and Demand Each successive pressing of the button selects a new range 1 Frequency and Power Factor total 2 Power Factor of each phase 3 Maximum Power Demand 4 Maximum Current Demand ...

Страница 6: ...fo bg etech de Fax 49 3574 4675519 5 Power Each successive pressing of the button select a new range 1 Instantaneous Active Power in kW 2 Instantaneous Reactive Power in kVAr 3 Instantaneous Volt amps in KVA 4 Total kW kVArh kVA Energy Measurements Each successive pressing of the button selects a new range 1 1 Imported active energy in kWh ...

Страница 7: ...hring Str 36 01979 Lauchhammer WEB www eastron germany de Mail info bg etech de Fax 49 3574 4675519 6 1 2 Exported active energy in kWh 2 1 Imported reactive energy in kVArh 2 2 Exported reactive energy in kVArh 3 1 Total active energy in kWh 3 2 Total reactive energy in kVArh ...

Страница 8: ... Methods Some menu items such as password require a four digit number entry while others such as supply system require selection from a number of menu options Menu Option Selection 1 Use the and buttons to select the required item from the menu Selection does not roll over between bottom and top of list 2 Press to confirm your selection 3 If an item flashes then it can be adjusted by the and butto...

Страница 9: ...ed Digits are set individually from left to right The procedure is as follows 1 The current digit to be set flashes and is set using the and buttons 2 Press to confirm each digit setting The SET indicator appears after the last digit has been set 3 After setting the last digit press to exit the number setting routine The SET indicator will be removed Change password 1 Use the and to choose the cha...

Страница 10: ...etting routine and return to the Set up menu SET will be removed DIT Demand Integration Time This sets the period in minutes over which the current and power readings are integrated for maximum demand measurement The options are 0 5 8 10 15 20 30 60 minutes 1 From the set up menu use and buttons to select the DIT option The screen will show the currently selected integration time 2 1 Press to ente...

Страница 11: ...ttable Default lasting time is 60minutes For example if it s set as 5 the backlit will be off in 5minutes from the last time operation on the meter 2 Press to enter the selection routine The current time interval will flash The options can be 0 always on 5 10 30 60 120minutes Use and buttons to select the time required Press to confirm the set up Supply System Use this section to set the type of p...

Страница 12: ...s to confirm the selection SET indicator will appear Press to exit the system selection routine and return to the menu SET will disappear and you will be returned to the main Set up Menu Pulse output This option allows you to configure the pulse output 1 The output can be set to provide a pulse for a defined amount of energy active or reactive Use this section to set up the pulse output for Total ...

Страница 13: ...o choose kWh or kVArh On completion of the entry procedure press to confirm the setting and press to return to the main set up menu Pulse rate Use this to set the energy represented by each pulse Rate can be set to 1 pulse per dFt 0 01 0 1 1 10 100kWh kVArh It shows 1 impulse 10kWh kVArh 1 From the Set up menu use and buttons to select the Pulse Rate option 2 Press to enter the selection routine T...

Страница 14: ...ress to return to the main set up menu Pulse Duration The energy monitored can be active or reactive and the pulse width can be selected as 200 100 default or 60ms It shows pulse width of 200ms 1 1 From the Set up menu use and buttons to select the Pulse width option 1 2 Press to enter the selection routine The current setting will flash Use and buttons to choose pulse width On Completion of the e...

Страница 15: ... For Mbus communication parameters are selected from Front panel RS485 Address The range is from 001 to 250 1 From the Set up menu use and buttons to select the Address ID 2 1 Press button to enter the selection routine The current setting will be flashing 2 2 Use and buttons to choose Modbus Address 001 to 250 2 3 Mbus secondary address It ranges from 00 00 00 01 to 99 99 99 99 On completion of t...

Страница 16: ...ud Rate 1 From the Set up menu use and buttons to select the Baud Rate option 2 1 Press to enter the selection routine The current setting will flash 2 2 Use and buttons to choose Baud rate 0 3k 0 6k 1 2k 2 4k 4 8k 9 6k Default is 2 4k On completion of the entry procedure press to confirm the setting and press to return to the main set up menu Parity 1 From the Set up menu use and buttons to selec...

Страница 17: ...ll flash 2 2 Use and buttons to choose Parity EVEN ODD NONE On Completion of the entry procedure press to confirm the setting and press to return to the main set up menu Stop bits 1 From the Set up menu use and buttons to select the Stop Bit option 2 1 Press to enter the selection routine The current setting will flash 2 2 Use and buttons to choose Stop Bit 2 or 1 On completion of the entry proced...

Страница 18: ...he main set up menu Note Default is 1 and only when the parity is NONE that the stop bit can be changed to 2 CLR The meter provides a function to reset the maximum demand value of current and power 1 From the Set up menu use and buttons to select the reset option 2 Press to enter the selection routine The MD will flash Press to confirm the setting and press to return to the main set up menu ...

Страница 19: ...ge voltage THD between phases three phase supplies only Current THD for each phase Power factor and Frequency and Max Demand Frequency in Hz Instantaneous power Power 0 to 99999 W Reactive Power 0 to 99999 VAr Volt amps 0 to 99999 VA Maximum demanded power since last Demand reset Power factor Maximum neutral demand current since the last Demand reset for 3p4w supply only Energy Measurements Import...

Страница 20: ...Bus EN13757 3 protocol an Pulse output Pulse 1 indicating real time measured energy configurable an Pulse output Pulse 2 400imp kWh The Modbus configuration Baud rate etc and the pulse output assignments kW kVArh import export etc are configured through the Set up screens Pulse Output The unit provides two pulse outputs Both pulse outputs are passive type Pulse output 1 is configurable The pulse o...

Страница 21: ...of Influence Quantities Influence Quantities are variables that affect measurement errors to a minor degree Accuracy is verified under nominal value within the specified tolerance of these conditions Ambient temperature 23 C 2 C Input frequency 50Hz 60Hz 2 Input waveform Sinusoidal distortion factor 0 005 Magnetic field of external origin Terrestrial flux Environment Operating temperature 25 C to ...

Страница 22: ...EASTRON SDM630 Mbus V2 User Manual EASTRON Germany B G e tech GmbH Franz Mehring Str 36 01979 Lauchhammer WEB www eastron germany de Mail info bg etech de Fax 49 3574 4675519 21 Dimensions ...

Страница 23: ... SDM630 Mbus V2 User Manual EASTRON Germany B G e tech GmbH Franz Mehring Str 36 01979 Lauchhammer WEB www eastron germany de Mail info bg etech de Fax 49 3574 4675519 22 Wiring diagram Three Phase Three Wires ...

Страница 24: ...EASTRON SDM630 Mbus V2 User Manual EASTRON Germany B G e tech GmbH Franz Mehring Str 36 01979 Lauchhammer WEB www eastron germany de Mail info bg etech de Fax 49 3574 4675519 23 Three Phase Four Wires ...

Страница 25: ...EASTRON SDM630 Mbus V2 User Manual EASTRON Germany B G e tech GmbH Franz Mehring Str 36 01979 Lauchhammer WEB www eastron germany de Mail info bg etech de Fax 49 3574 4675519 24 Single Phase two Wires ...