background image

3

4

SDM530D

/

SDM530D-2T

Three Phase Four Wires DIN Rail Energy Meter 

7

 Modules

Technical Data

Performance criteria

Operating humidity
Storage humidity
Operating temperature
Storage temperature

International standard

Accuracy class

Ingress protection

Insulating encased meter of
protective class

≤ 

90

%

≤ 95%
-

25

°C - +5

5

°C

-

4

0°C - +70°C

IEC 62053-21
1
IP51
II

Specifications

Nominal voltage(Un)
Operational voltage
Insulation capabilities

- AC voltage withstand
- Impulse voltage withstand

Basic current (Ib)
Maximum rated current (Imax)
Operational current range
Over current withstand
Operational frequency range
Internal power consumption

Pulse

 output flash rate (PULSE LED)

P

ulse output rate (pins 8 & 9)

230/400V AC(3~)

80%~120% Un

4

KV for 1 minute

6KV-1.2

/50µ

S

10A
100A

0.4% Ib-Imax
30Imax for 0.01s
50/60Hz
≤ 2W/10VA/phase
800imp/kWh
800imp/kWh

Basic errors

0.05Ib Cosφ = 1
0.1Ib Cosφ = 0.5L
Cosφ = 0.8C 
0.1Ib – Imax Cosφ = 1
0.2Ib – Imax Cosφ = 0.5L
                     Cosφ = 0.8C

±1%
±1%
±1%
±1%
±1%
±1%

With balanced loads

2

SDM530* Series is a range of 7 modules three phase four wire energy meters.
The series contains 2 models: SDM530D and SDM530D-2T.

SDM530D: measures and displays active energy(kWh)
SDM530D-2T: measures and displays active energy(kWh) in 2 tariffs.

2 tariffs: SDM530D-2T has a time relay inside which can monitor if there is 
external 230V signal input. When It detected an external 230V signal input, the
meter switches to tariff 2 measurement. Otherwise it will measure as tariff 1.

With high accuracy of Class 1, they are widely used to measure three phase 
energy in commercial and industrial applications. A pulse output is provided.

Height
Width
Depth 

100mm
125mm

65mm

Information for your own safety

This manual does not contain all of safety measures for operation of the
equipment (module, device), because special operating conditions, and
local code requirements or regulations may necessitate further measures.
However, it does contain information which must be read for your personal
safety and to avoid material damages. This information is highlighted by a 
warning triangle and is represented as follows, depending on the degree of
potential danger.

Warning

This means that failure to observe the instruction can result in 
death, serious injury or considerable material damage.

Caution

This means hazard of electric shock and failure to take the 
necessary safety precautions will result in death,serious injury 
or considerable material damage.

Qualified personnel

Operation of the equipment (module, device) described in this manual 
may only be performed by qualified personnel. Qualified personnel in 
this manual means person who are authorized to commission, start 
up, ground and label devices,systems and circuits according to safety 
and Regulatory standards.

Use for the intended purpose

The equipment (device, module) may only be used for the application 
specified in the catalogue and the user manual,and only be connected 
with devices and components recommended and approved by EASTRON.

Proper handling

The prerequisites for perfect, reliable operation of the product are proper 
transport, proper storage, installation and assembly, as well as proper 
operation and maintenance. When operating electrical equipment, certain 
parts of this equipment automatically carry dangerous voltages. Improper 
handling can therefore result in serious injuries or material damage.

Use only insulating tools.
Do not connect while circuit is live (hot).
Place the meter only in dry surroundings.
Do not mount the meter in an explosive area or expose the meter 
to dust, mildew and insects.
Make sure the used wires are suitable for the maximum current of 
this meter.
Make sure the AC wires are connected correctly before activating 
the current/voltage to the meter.
Do not touch the meter connecting clamps directly with your bare 
hands, with metal, blank wire or other material as you may get an 
electrical shock.
Make sure the protection cover is placed after installation.
Installation, maintenance and reparation should only be done by 
qualified personnel.
Never break the seals and open the front cover as this might influence 
the functionality of the meter, and will avoid any warranty.
Do not drop, or allow physical impact to the meter as there are high 
precision components inside that may break.

ZHEJIANG

 EASTRON ELECTRONIC CO., LTD.

Add: No.1369 Chengnan Road, Nanhu, Jiaxing, Zhejiang, 314001, China
Tel: +86-573-83698881 /83698882             Fax: +86-573-83698883

Email:[email protected]                   Web:www.eastrongroup.com

Description

Dimensions

Safety Instructions