SDM230A/D/DR/BI

Single Phase Two Wires Din Rail Energy Meter

Technical Data

Safety Instructions

Information for your own safety

This manual does not contain all of the safety measures for operation of 
the equipment(module,device),because special operating conditions,
and local code requirements or regulations may necessitate further 
measures. However,it does contain information which must be read 
for your personal safety and to avoid material damages.This information 
is highlighted by a warning triangle and is represented as follows, 
depending on the degree of potential danger.

Warning

This means that failure to observe the instruction can result in 
death, serious injury or considerable material damage.

Caution

This means hazard of electric shock and failure to take the 
necessary safety precautions will result in death,serious injury 
or considerable material damage.

Qualified personnel

Operation of the equipment (module, device) described in this manual 
may only be performed by qualified personnel. Qualified personnel in 
this manual means person who are authorized to commission, start 
up, ground and label devices,systems and circuits according to safety 
and Regulatory standards.

Use for the intended purpose

The equipment (device, module) may only be used for the application 
specified in the catalogue and the user manual,and only be connected 
with devices and components recommended and approved by EASTRON.

Proper handling

The prerequisites for perfect, reliable operation of the product are proper 
transport, proper storage, installation and assembly, as well as proper 
operation and maintenance. When operating electrical equipment, certain 
parts of this equipment automatically carry dangerous voltages. Improper 
handling can therefore result in serious injuries or material damage.

Use only insulating tools.
Do not connect while circuit is live (hot).
Place the meter only in dry surroundings.
Do not mount the meter in an explosive area or expose the meter 
to dust, mildew and insects.
Make sure the used wires are suitable for the maximum current of 
this meter.
Make sure the AC wires are connected correctly before activating 
the current/voltage to the meter.
Do not touch the meter connecting clamps directly with your bare 
hands, with metal, blank wire or other material as you may get an 
electrical shock.
Make sure the protection cover is placed after installation.
Installation, maintenance and reparation should only be done by 
qualified personnel.
Never break the seals and open the front cover as this might influence 
the functionality of the meter, and will avoid any warranty.
Do not drop, or allow physical impact to the meter as there are high 
precision components inside that may break.

Performance criteria

Operating humidity
Storage humidity
Operating temperature
Storage temperature
Active energy accuracy

Protection against penetration
of dust and water
Insulating encased meter of
protective class
Warm up time
Mechanical environment
Electromagnetic environment
Degree of pollution

≤ 90%
≤ 95%
-25°C - +55°C
-40°C - +70°C
Class B EN50470-1/3
Class 1 IEC 62053-21
IP51

II

10S
M1
E2
2

Specifications

Nominal voltage(Un)
Operational voltage
Insulation capabilities
- AC voltage withstand
- Impulse voltage withstand
Basic current (Ib)
Maximum rated current (Imax)
Operational current range
Over current withstand
Operational frequency range
Internal power consumption
Test output flash rate (PULSE LED)
Test pulse output rate
Max. reading
 

230V AC
80%~120% Un 

4KV for 1 minute
6KV-1.2

µ

S

10A
100A
0.4% Ib~Imax
30Imax for 0.01s
50Hz ± 10%
≤ 2W/10VA/phase
1000imp/kWh
1000imp/kWh
99999.9 (SDM230D)
999999.9(SDM230A/DR/Bi)

Introduction

ZHEJIANG

 EASTRON ELECTRONIC CO., LTD.

Add: No.1369 Chengnan Road, Nanhu, Jiaxing, Zhejiang, 314001, China
Tel: +86-573-83698881 /83698882             Fax: +86-573-83698883

Email:[email protected]                 Web:www.eastron.com.cn   www.eastrongroup.com

Dimensions

The SDM230* series are single phase two wire energy meters “with a 
white back-lighted LCD screen for prefect reading”. they are used to
measure single phase energy in residential and commercial applications.
The series contains 4 models: SDM230A, SDM230D,
                                                     SDM230DR,SDM230Bi

SDM230A   : 1P2W energy meter with analog register  
SDM230D   : 1P2W energy meter with LCD display
SDM230DR: 1P2W energy meter with resettable partial energy
SDM230Bi  :  1P2W energy meter with bi-directional measurement

SDM230DR and SDM230Bi have been MID approved. They measures
both active energy (kWh) and power (W).   There are two buttons on the
front panel, one is used to scroll the info pages, another to reset partial 
energy information.  All models has a pulse output, which is passive type.
The constant is 1000imp/kWh.   

Height
Width
Depth

99mm
36mm
63mm

36m

m

6

3m

m

99m m