~ 9 ~
Forced
off-grid
mode
During the normal operation of the gird, force to operate in the
off-grid mode
Off--grid mode (no grid)
1.
PV gives priority to supply the power for the backup load,
followed by charging the battery.
2.
If the power from the PV is unavailable or extremely low, PV
and the battery supply the power for the load.
3.4 Operation status of inverter
No.
Status
Description
1
Waiting
mode
Self-check
mode
Waiting period after the inverter is turned
If the condition is met, the inverter enters the self-check mode
In case of a fault, the inverter enters the fault mode.
2
Self-check
mode
Continuous self-check, initialization and so on before the inverter is
started
If the condition is met, the inverter enters and starts to operate in the
grid-tied mode.
If the grid is not detected, the inverter enters and stars to operate in
the off-grid mode; if it has no off-grid function, the inverter enters the
waiting mode.
In case of failure in the self-check, the inverter enters the fault mode.
3
Grid-tied
mode
Grid-tied operation of inverter
If the grid is not detected, the inverter enters the off-grid mode.
If a fault is detected, the inverter enters the fault mode.
If the grid fails to meet the grid-tied requirements and the off-grid
output function is not activated, the inverter enters the waiting mode.