Resistance Connection

Select item 6 from the item menu to enter the resistance connection

selection screen.Can switch the connection or disconnection of the built-in
resistance.Select item 1 as the internal resistance connection, and item 1 is shown
as "connected"; no need external resistance connection / Select item 2 to disconnect
the internal resistance connection. At this time, item 2 is shown as "disconnected".

十三.

Common troubleshooting solutions

13.1 the communicator is not connected to the meter

1) check whether the loop equipment supports HART function.
2) check the size of the circuit load resistance, load resistance should be

between 250 ~ 500 Ω.

3) check whether the connection of communicator and instrument is correct.
4) check whether the meter is powered correctly.
5) it is possible that the address of the instrument is not 0. Select "multi-point

polling" and conduct polling to find the instrument.
13.2 press the power switch and there is no display

1) check whether the battery has been loaded.
2) check whether the battery is installed correctly.
3) check whether the battery is exhausted.

Содержание HART 475

Страница 1: ...1 HART 475 COMMUNICATOR USER MANUAL Hangzhou Zhongchuang Electron Co Ltd...

Страница 2: ...vironment 4 Keyboard Introduction 4 Establish Connection 4 Funtion Introduction 6 Common Function Operation Example 9 Polling Meter Battery Power 12 Instrument Information 12 Language Selection 12 Res...

Страница 3: ...ilt in 1 3 Dedicated test line 1 4 Charger 1 5 250 ohm resistor 2 6 User manual 1 Production Introduction HART series manual operators are suitable for the communication operation of HART protocol int...

Страница 4: ...g temperature range 0 C 50 C Storage temperature range 20 C 55 C Note Exploding the device in the sun will significantly shorten the life of the LCD panel and accelerate the aging of the button panel...

Страница 5: ...nected or disconnected Set as connectting internal resistance there is no need to connect external resistance When set to disconnect the internal resistance the external resistance should be connected...

Страница 6: ...d well After the meter loop is connected correctly hold down the power button for three seconds and the LCD screen is lit to indicate that the device has been working Hold down the power button for th...

Страница 7: ...e 3 battery power 4 local information 5 language 6 resistance connection For any type of meter you can always return to the item menu by pressing the left arrow key or the Back key several times Ifent...

Страница 8: ...inspection it can achieve equipment self inspection and report the test results Selecting circuit current detection the transmitter can output a fixed current signal to verify whether the whole circu...

Страница 9: ...main menu to enter the detailed Settings menu which provides more configuration information For different HART devices the detailed Settings are quite different Only through the registered device its...

Страница 10: ...ntenance 3 calibration 1 output fine tuning Note the output current fine tuning function can only be performed when HART instrument leaves the factory and is tested periodically The use of this functi...

Страница 11: ...unicator will automatically poll all connected devices from address 0 to address 15 The second item in the menu is single point polling You can choose any address between 0 and 15 for communication If...

Страница 12: ...wer Select the third item from the item menu to enter the display battery power function which will detect the remaining battery power in the current communicator When the battery power is too low ple...

Страница 13: ...ns 13 1 the communicator is not connected to the meter 1 check whether the loop equipment supports HART function 2 check the size of the circuit load resistance load resistance should be between 250 5...

Страница 14: ...pull the data line to avoid the bad contact of the line and the unusable situation 14 4 please press the keyboard lightly to avoid heavy hitting and extend the life of the keyboard 14 5 batteries sho...

Отзывы: