background image

                  

CREATED ON: May 18, 2017

 

                                                

Instruction Manual

 

 

 

 

 

S1DC8–M3

 

COMBINATION TIMER WITH 8 CHANNELS 

 

                                         

 

                            

 

                                                                      

                                                            

EAPL

 

 

 

  Introduction 

On power application and shorting of S1 & S2 terminals, the timing starts, 

each of the relays comes ON after the preset delay timing and remain 

ON till the Preset ON timing. All 8 relays switches ON & OFF in different 

combinations as per the program. After completion of all combinations 

clock resets to zero and depending on the status of C1-C2, timer 

continues to execute the same program or waits for fresh start signal. If 

Run/Prog switch is slided from program mode to run mode, timer waits 

for fresh start signal.      

 

 

    
 
 
 
 
 
 
 
 

 

 

       Box Accessories

 

            One (1) S1DC8–M3COMBINATION TIMER WITH 8 CHANNELS 

 
    One (1) Instruction manual 

 

 

 

Safety Precautions 

 
Read and follow all the safety precautions and instructions before 
installing and working with the equipment. 

 

 

Shorting of C1-C2, S1-S2, and I1-I2 & R1-R2 shall be potential free; 

applying power to these terminals will damage the timer permanently. 

 

Timing not initiated. 

 

S1- S2 signal shall be applied.  

 

  I1- I2 shall be open.- 

 

                         !   

DANGER 

HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH 

 

Apply appropriate personal protective equipment(PPE) and follow 

safety work practices 

 

Only qualified electrical workers should install this equipment. Such work 

should be performed only after reading this entire set of instructions. 

 

If the equipment is not used in the manner specified by the 

manufacturer, the protection provided by the equipment may be 

impaired. 

 

NEVER work alone. 

 

The successful operation of this equipment depends upon proper 

handling, installation and operation. Neglecting fundamental installation 

requirements may lead to personal injury as well as damage to 

electrical equipment or other property. 

 

NEVER bypass external fusing. 

Failure to follow these instructions will result in death or serious injury. 

 

EAPL is not responsible for any consequential damages arising out of use 

of our products, though the technology is cautiously chosen and 

implemented like any other well designed good electric device.  

   Tools and Fasteners 

    Kindly use star – type screw driver for tightening the screws. 
 

NOTE:

  Installation should include a disconnecting device, like switch or 

circuit breaker, with clear ON/OFF markings, to turn-off the auxiliary 
supply (control power).The disconnecting device should be within the 
reach of the equipment and the operator

.

 

 

 

 
Dimension 

      

        

 

Note: All Dimensions are in mm. 

  Front Panel 

 

 

   Terminal Details 

 

A1,A2 : Source 

 

S1-S2  : Start signal for a minimum of 150mS. 
C1-C2  : SHORT – Single cycle operation 
               (i.e. timer stops at  the end of first cycle) 
              OPEN – Cyclic operation  
               (i.e. timer continues to operate). 

 

I1-I2      :  Time Pause Input. By shorting these terminals timing is 
temporarily stopped and relay status is maintained,  
again by opening timing continues. 

 

R1– R2  :  PROGRAM  RESET: 
After shorting these terminals slide PROG/RUN switch to  
PROG mode. This will erase all previously programmed  
On time & delay time settings. 

 

HOLD MODE: Continue the timing after resumption of   interrupted 
power & balance time is executed. 

 

RESTART MODE: After the resumption of interrupted power, 
 timer waits for fresh start signal.

 

Page 1 of 2 

OD RS AN 210001 REV 01/18-05-17 

 

Отзывы: