KNX TP Main Line
KNX TP Sub Line
2. Device Technology
2.1. Commissioning
Please note for commissioning with default settings:
•
All telegrams are blocked because the filter table is not defined
•
The Manual Function switch-off time is 120 min
•
Physical address is 15.15.0
Please read carefully before first use:
•
After connection to the KNX bus system, the device works with its default settings
•
Warning: Do not connect to 230 V. The device is supplied by the KNX bus and does not require
any additional external power supply
•
The device may only be installed and put into operation by qualified electrician or authorized
personnel
•
For planning and construction of electric installations the appropriate specifications,
guidelines and regulations in force of the respective country have to be complied
•
For mounting use an appropriate equipment according to IEC60715
•
Installation on a 35 mm DIN rail (TH35)
•
Connect the KNX bus line as for common KNX bus connections with a KNX bus cable, to be
stripped and plugged into a KNX TP connector
•
Do not damage electrical insulations during connecting
•
Installation only in dry locations
•
Accessibility of the device for operation and visual inspection must be provided
•
For changing the configuration use the ETS
•
The housing must not be opened
•
Protect the device from moisture, dirt and damage
•
The device needs no maintenance
•
If necessary, the device can be cleaned with a dry cloth
•
In the case of damage (at storage, transport) no repairs may be carried out by unauthorized
personnel