EAE 48074 Скачать руководство пользователя страница 17

PRODUCT MANUAL LC100 

EAE KNX LINE COUPLER 

 

 

 

 

 

 

         

LC100  R0 

 

©

EAE Technology 

 

 

www.eaetechnology.com  

 

               Page 17 / 17 

7.3. Subline 

 

For Group Telegrams and Physical Telegrams the  setting “transmit all” is intended only for testing 

purposes. Please do not use for normal operation. 

Picture 3: Subline Tab Parameters 

 

ETS-Text 

Range 

[Default value] 

Comment 

Telegram routing 

Group and Physical: route 
configure 

[Group and Physical: route] 

route: 

all telegrams are routed 

configure: 

The  following  parameters  must 
be set manually. 

Physical telegrams 

transmit all 
block 

[transmit all]

 

 

Physical telegrams are all routed. 

 

Physical telegrams are all blocked.

 

Physical telegrams: 

Repetition  

if errors on main line 

no 
up to 3 repetitions 
only one repetition 

[only one repetition]

 

After main line transmission error (e.g. due to 
missing receiver) Physical telegrams 

 

are not repeated. 

 

are repeated max. 3 times. 

 

are repeated once.

 

Group telegrams: 

Repetition  

if errors on main line 

no 
up to 3 repetitions 
only one repetition 

[only one repetition]

 

After main line transmission error (e.g. due to 
missing receiver) Group telegrams 

 

are not repeated. 

 

are repeated max. 3 times.  

 

are repeated once.

 

Telegram confirmation 

on main line 

If routed 
always 

[always]

 

 

Routed  telegrams  to  the  subline  are 
confirmed by an ACK on the main line. 

 

Each telegram on the mainline is confirmed 
by an ACK.

 

Send confirmation on 

own telegrams 

yes 
no 

[yes]

 

 

Telegrams  sent  out  to  the  mainline  are 
confirmed by added ACK. 

 

No ACK confirmation. 

Table 3: Subline Tab Parameter Settings 

Содержание 48074

Страница 1: ...PRODUCT MANUAL LC100 EAE KNX LINE COUPLER LC100 R0 EAE Technology www eaetechnology com Page 1 17 EAE KNX LINE COUPLER Product Order Nr 48074...

Страница 2: ...Programming Interface 4 1 3 Feature Summary 4 2 Device Technology 5 2 1 Commissioning 5 2 2 Device Peripherals 6 2 3 Function Button 7 2 4 Physical Addressing Mode 8 2 5 KNX Topology 9 2 6 LC100 as T...

Страница 3: ...ilt in filter tables for group communication Group oriented Telegrams For detailed diagnosis all operational modes states are shown by a duo LED display Programming on main line from the subline can b...

Страница 4: ...ons can be configured for both Physical Telegrams and Group Telegrams via ETS to ease troubleshooting E g after an IACK response no repetition is following and the negative IACK BUSY failure mechanism...

Страница 5: ...orized personnel For planning and construction of electric installations the appropriate specifications guidelines and regulations in force of the respective country have to be complied For mounting u...

Страница 6: ...nect Main KNX Main line OK Manual Function Active No KNX Main Line connection Connect Sub KNX Sub line OK No KNX Sub Line connection Tx Rx Main Traffic on KNX Main line Transmissio n Error on KNX Main...

Страница 7: ...KNX line parameter Manual override functionality is configured in General parameters NOTE The latest downloaded settings parameters and filter table are still available after switching back from Manua...

Страница 8: ...g Mode LED addressing mode Off normal operating mode On addressing mode After receiving the physical address the LC100 automatically returns from addressing mode to the normal operating mode Button ad...

Страница 9: ...ers a line can theoretically be extended to 255 bus devices This means up to four line segments form a single KNX TP line But it is common practice on exceeding 64 bus devices to insert a new line ins...

Страница 10: ...ddresses are entered in its filter table If a telegram is routed by LC100 without receiving the corresponding acknowledgement i e due to a missing receiver or to a transmission error the telegram will...

Страница 11: ...to a missing receiver or to a transmission error the telegram will be repeated up to three times depending on the ETS setting With the parameters Repetitions if errors this function can be configured...

Страница 12: ...main line up to 3 repetitions Group Repetition if errors on main line up to 3 repetitions Telegram confirmations on main line if routed Send confirmation on own telegrams no Subline Group telegrams 0...

Страница 13: ...ysical address For special modes Temperature range Ambient 5 C 45 C Storage 25 C 55 C Transport 25 C 70 C Humidity max air humidity 95 no moisture condensation Dimensions 90x36x71 mm Weight 62g Box Pl...

Страница 14: ...PRODUCT MANUAL LC100 EAE KNX LINE COUPLER LC100 R0 EAE Technology www eaetechnology com Page 14 17 5 Technical Drawing...

Страница 15: ...ent Manual Function disabled pass all telegrams pass all Physical telegrams pass all Group telegrams pass all telegrams Configuration setting for telegram routing when the Manual Function is active Sw...

Страница 16: ...smit all block transmit all Physical telegrams are all routed Physical telegrams are all blocked Physical telegrams Repetition if errors on main line no up to 3 repetitions only one repetition only on...

Страница 17: ...ion if errors on main line no up to 3 repetitions only one repetition only one repetition After main line transmission error e g due to missing receiver Physical telegrams are not repeated are repeate...

Отзывы: