INSTRUCTION MANUAL
STExS2
Alarm Horn Sounder
For use in Flammable Gas and Dust Atmospheres
E2S Warning Signals
Impress House, Mansell Road, Acton, London W3 7QH
www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D199-00-051-IS
Issue 3
13-05-22
Sheet 1 of 8
STExS2F
STExS2H
1) Product Table
Standards Unit Type Code
Nominal
Input Voltage
Nominal
Input Current
Voltage
Range
Max.
Current
Sound
Pressure Level
P2, dB(A)
Sound
Pressure Level
P3, dB(A)
P2
P3
P2
P3
Max*
Nom
.†
Max*
Nom
.†
STExS2FDC024
12Vdc
289mA
356mA
11.5-54Vdc 324mA 740mA
120
115
123
118
A
T
E
X
/
I
E
C
E
x
/
U
K
E
x
/
N
E
C
/
C
E
C
24Vdc
324mA
740mA
48Vdc
195mA
391mA
STExS2FAC230
115Vac
125mA
282mA
100-240Vac
50/60Hz
138mA 325mA
120
115
123
118
230Vac
78mA
167mA
STExS2HDC024
12Vdc
289mA
356mA
11.5-54Vdc 324mA 740mA
124
119
127
122
24Vdc
324mA
740mA
48Vdc
195mA
391mA
STExS2HAC230
115Vac
125mA
282mA
100-240Vac
50/60Hz
138mA 325mA
124
119
127
122
230Vac
78mA
167mA
*Max = Tone 4
†
Nom. = Tone 44
The table shows the input current taken by the various sounders.
The current levels shown above are for the 440Hz Continuous tone @ nominal input voltage at P2 and P3 power setting.
Nominal current at nominal voltage.
Max rated current at worst case supply voltage.
Table 1: Product table
Ensure the system power supply is capable of providing the maximum current required for all beacons. Review associated cable size,
length and quantity of beacons on each circuit.