INSTRUCTION MANUAL 

STExS2 
Alarm Horn Sounder

 

For use in Flammable Gas and Dust Atmospheres

 

 

E2S Warning Signals

      Impress House, Mansell Road, Acton, London W3 7QH

 

www.e2s.com

 

Tel: +44 (0)208 743 8880

 

Document No. D199-00-051-IS

 

Issue 3

 

13-05-22

 

 

Sheet 1 of 8

 

 

 
 

 

               STExS2F 

STExS2H 

 
 

1)  Product Table 

 

Standards  Unit Type Code 

Nominal 

Input Voltage 

Nominal 

Input Current 

Voltage 

Range 

Max. 

Current 

Sound 

Pressure Level 

P2, dB(A) 

Sound 

Pressure Level 

P3, dB(A) 

P2 

P3 

P2 

P3 

Max* 

Nom

.†

 

Max* 

Nom

.†

 

 

STExS2FDC024 

12Vdc 

289mA 

356mA 

11.5-54Vdc  324mA  740mA 

120 

115 

123 

118 

A

T

E

X

 /

 I

E

C

E

x

 /

 U

K

E

x

 /

 

N

E

C

 /

 C

E

C

 

24Vdc 

324mA 

740mA 

48Vdc 

195mA 

391mA 

STExS2FAC230 

115Vac 

125mA 

282mA 

100-240Vac 

50/60Hz 

138mA  325mA 

120 

115 

123 

118 

230Vac 

78mA 

167mA 

STExS2HDC024 

12Vdc 

289mA 

356mA 

11.5-54Vdc  324mA  740mA 

124 

119 

127 

122 

24Vdc 

324mA 

740mA 

48Vdc 

195mA 

391mA 

STExS2HAC230 

115Vac 

125mA 

282mA 

100-240Vac 

50/60Hz 

138mA  325mA 

124 

119 

127 

122 

 

230Vac 

78mA 

167mA 

*Max = Tone 4 

Nom. = Tone 44 

 
The table shows the input current taken by the various sounders. 
The current levels shown above are for the 440Hz Continuous tone @ nominal input voltage at P2 and P3 power setting.  
Nominal current at nominal voltage. 
Max rated current at worst case supply voltage. 

Table 1: Product table 

 

Ensure the system power supply is capable of providing the maximum current required for all beacons. Review associated cable size, 
length and quantity of beacons on each circuit. 
 
 
 
 
 
 
 

 

Содержание STExS2

Страница 1: ... 391mA STExS2FAC230 115Vac 125mA 282mA 100 240Vac 50 60Hz 138mA 325mA 120 115 123 118 230Vac 78mA 167mA STExS2HDC024 12Vdc 289mA 356mA 11 5 54Vdc 324mA 740mA 124 119 127 122 24Vdc 324mA 740mA 48Vdc 195mA 391mA STExS2HAC230 115Vac 125mA 282mA 100 240Vac 50 60Hz 138mA 325mA 124 119 127 122 230Vac 78mA 167mA Max Tone 4 Nom Tone 44 The table shows the input current taken by the various sounders The cu...

Страница 2: ...CEC Ratings Gas Class I All models are approved for use as Alarm Horns also comply with the following standards for signalling equipment UL464A CSA C22 2 NO 205 17 NEC Class Zone Ratings US Codes Standards UL 60079 0 Ed 7 04 15 2020 Explosive Atmospheres part 0 Equipment General Requirements UL 60079 1 Ed 7 2015 Explosive Atmospheres Part 1 Equipment Protection by Flameproof Enclosures d Ratings S...

Страница 3: ...ust Applications ATEX IECEx UKEx only STExS2 DC 94ºC AC 84ºC Equipment Category 2G 2D Equipment Level Protection Gb Gc Db Dc Ambient Temperature Range 50 C to 70 C IP Rating IP6X to EN IEC60079 0 IP66 to EN60529 5 Special Conditions for Safe Use Repair of the flameproof threaded joints and cemented joints is not permitted Figure 1 Flame Path The plastic horn is not anti static and the metallic enc...

Страница 4: ... the relevant standards ATEX IECEx UKEx Installation Standards EN60079 14 IEC60079 14 Explosive atmospheres Electrical installations design selection and erection EN60079 10 1 IEC60079 10 1 Explosive atmospheres Classification of areas Explosive gas atmospheres EN60079 10 2 IEC60079 10 2 Explosive atmospheres Classification of areas Explosive dust atmospheres The installation of the units must als...

Страница 5: ...o secure the earth conductor under the earth clamp The earth conductor should be at least equal in size and rating to the incoming power conductors but at least a mini mum of 0 82mm2 18AWG in size 7 3 Cable Glands Blanking Elements Adapters Follow the minimum temperature ratings of cables and cable glands according to the approvals applied ATEX IECEx UKEx Requirements Only For high ambient tempera...

Страница 6: ...hat stopping plugs cannot be fitted onto adapters only directly onto the M20 entries Any other adapters used must be suitably rated and certified adapters 8 Settings Following illustrations show the different settings available for STExS2 Alarm Horn Sounders See schematic diagrams D190 06 001 for DC units and D190 06 005 for AC units 8 1 SPL Configuration See Table 1 for product power supply and S...

Страница 7: ...onitoring 4 DC Two Stage Configuration Line Stage Monitoring Use suitable monitoring relays modules Not to be used in reverse polarity monitoring Custom Y 5 DC Two Three Stage Voltage Free Activation Configuration Custom K 6 DC Three Four Stage Configuration Independent Stage Input Line Stage Monitoring Use suitable monitoring relays modules Positive Switching Default Custom V See documents D190 0...

Страница 8: ...l 12 Way Terminal Module 10 Maintenance Overhaul and Repair Maintenance repair and overhaul of the equipment should only be carried out by suitably qualified personnel in accordance with the current relevant standards ATEX IECEx UKEx Requirements Only EN60079 19 IEC60079 19 Explosive atmospheres Equipment repair overhaul and reclamation EN 60079 17 IEC60079 17 Explosive atmospheres Electrical inst...

Отзывы: