background image

 

 

_______________________________________________________________________________________________________________________________ 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)20 8743 8880 

                                                                                                                                                             www.e2s.com             Fax: +44 (0)20 8740 4200 
Document No. IS 4501      Issue G                 13-01-20                       

Sheet 1 of  6

 

INSTRUCTION MANUAL 

IS-A105N 

Intrinsically Safe Sounder

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

1)  Introduction 

 

The  IS-A105N  is  an  ATEX  and  IECEx  certified  intrinsically 

safe  sounder  which  produces  a  loud  warning  signal  in  a 

hazardous  area.  Forty-nine  first  stage  alarm  sounds  can  be 

selected by internal switches and each one can be externally 

changed  to  a  second  or  third  stage  alarm  sound.  The 

sounder may be used in all gas groups IIA, IIB and IIC. The 

IS-A105N  sounder  may  be  used  in  conjunction  with  an  IS-

L101L intrinsically safe beacon, allowing a combined audible 

and visual alarm to be constructed. 
 

2)  Description 

 

Fig  1  shows  a  simplified  block  diagram  of  an  IS-A105N 

sounder.  The  device  operates  immediately  power  is  applied 

to  the  +  and  –  terminals  which  are  duplicated  to  allow  a 

second sounder to be connected in parallel, or for an end of 

line  monitoring  resistor  to  be  installed.  The  output  tone  is 

defined  by the positions  of the six internal  switches and this 

tone can be changed to a second or third stage alarm tone by 

connecting  terminals  S2  or  S3  to  0V.  The  tone  generator  is 

crystal  controlled  to  ensure  that  when  two  sounders  are 

started  at  the  same  time  the  output  tones  remain 

synchronised. 

 

3) 

Supply Voltage

 

 

The  IS-A105N  sounder  has  been  designed  to  operate  in  a 

hazardous area from a 24V dc supply via 28V 93mA resistive 

ATEX  and  IECEx  certified  Zener  Barriers  or  Galvanic 

Isolators. The sounders may be tested or used in safe areas 

without  a  Zener  barrier  or  galvanic  isolator,  but  at  supply 

voltages above 16V the internal current limit will function and 

therefore  it  is  recommended  that  they  are  not  operated 

continuously with a direct supply greater than 16V. 

 

 

 

-
-

IS-A105N Sounder

Volume Control

Tone Selection Switches

Tone Generator

+
+

S2

S3

 

 

Fig 1 Simplified block diagram 

 

4) 

Intrinsic Safety Certification

 

 

4.1 ATEX certificate 

The  IS-A105N  sounder  complies  with  the  following 
standards:-  
 
EN IEC 60079-0:2018 
EN60079-11:2012 
 
 

 

 
The  EC-Type  Examination  Certificate  SIRA  04ATEX2301X 
has  been  issued  by  the  Notified  Body  Sira.  This  confirms 
compliance  with  the  European  ATEX  Directive  94/9/EC  for 
Group  II,  Category  1G  equipment.    The  sounder  carries  the 
Community Mark and subject to local codes of practice, may 
be  installed  in  any  of  the  EEA  member  countries.  This 
instruction  sheet  describes  installations  which  conform  to 
EN60079:Part14:2008  Electrical  Installation  in  Hazardous 
Areas.    When  designing  systems  for  installation  outside  the 
UK, the local Code of Practice should be consulted. 
 
 
 

1) 

The certification marking is as follows:  

 

e

2S

european safety systems ltd. 

SIRA 04ATEX2301X

2813

IS-A105N Sounder

London W3 7QH UK
www.e2s.com

Year / Serial No.  
   09 / 1S00001

WARNINGS:

 

IECEx SIR 04.0038X

Term. + w.r.t. Term. -  Ui = 28V  Ii = 93mA  
                                    Pi = 660mW   Ci = 0   Li = 0
Term. S2&S3 w.r.t. Term. -   Ui = 28V  Ii = 0mA

FM

APPROVED

To avoid a possible electrostatic
charge only clean with a damp cloth 

To prevent ignition of flammable or combustible
 atmospheres, disconnect power before servicing

 

Substitution of components may impair safety 

IS Class I, Zone 0, AEx ia IIC T4
IS Class l, Division 1, Groups A, B, C, D

II 1G   Ex ia IIC T4 Ga (-40ºC <=Ta<= +60°C)

Control Drawing No. D 4528

 

The IS-A105N sounder is CE marked for 

compliance with the European 

Explosive Atmospheres Directive 

94/9/EC and the European EMC 

Directive 89/336/EEC 

II 1G      Ex ia IIC T4 Ga (-40ºC <= Ta <= +60ºC) 

Содержание IS-AL105NL

Страница 1: ...be tested or used in safe areas without a Zener barrier or galvanic isolator but at supply voltages above 16V the internal current limit will function and therefore it is recommended that they are no...

Страница 2: ...l capacitance connected to terminals wrt i e the capacitance of the cable plus any other capacitance shall not exceed 83nF The enclosure is non conducting and may generate an ignition capable level of...

Страница 3: ...manual The power supply terminals and are duplicated so that sounders may be connected in parallel or an end of line monitoring resistor may be fitted d Select the required output tone by positioning...

Страница 4: ...tinuous 2000Hz Intermittent 800Hz 0 25s ON 1s OFF Alternating 544Hz 100ms 440Hz 400ms NFS 32 001 Motor Siren Slow rise to 1200Hz Motor Siren Slow rise to 800Hz Continuous 1200Hz Motor Siren Slow rise...

Страница 5: ...e IS A105N sounder second and third stages may be activated by using Galvanically Isolated Relays that have output parameters within the limits specified in section 4 4 which have been certified Ex ia...

Страница 6: ...er shall ensure that the device that is fitted will provide an ingress protection that is appropriate to the environment in which it is installed i e IP20 or better 4 The enclosure is non conducting a...

Страница 7: ...fe Systems for Hazardous Classified Locations and the National Electrical Code ANSI NFPA 70 5 The resistance between the intrinsically safe ground and the earth ground must be less the 1 ohm 6 The Shu...

Страница 8: ...ne and Group of use 6 The IS A105N Sounder enclosure has an ingress protection rating of IP 66 If supplied without cable entry devices then metallic or plastic cable glands or conduit hubs shall be fi...

Отзывы: