European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)208 743 8880 

                                                                                                                                                            www.e-2-s.com             Fax: +44 (0)208 740 4200 
Document No. D204-00-001-IS 

Issue 1        25-04-2022                         Sheet 2 of 7

 

                                                           

3)  Marking & Rating Information 

 

The GNExCP7-BG Call Points comply with the following standards 
for hazardous locations:  

 

3.1 

Class/Division Ratings for US & Canada 

 

 

 

 
All models are approved for use as Fire Alarm System use: 
 
UL 38 8th Edition 10/4/2013 Manual Signaling Boxes for Fire 
Alarm Systems 
ULC-S528 3rd Edition 2014-10 Manual Stations For Fire 
Alarm Systems, Including Accessories 
 
For Indoor and Outdoor Use 
Pour usage Interier INTÉRIEUR 

 

Ambient Temperature Range: 

-55°C to +70°C  

 

Standards 

UL 60079-0:2017 (Ed 6): Explosive Atmospheres - Part 0: Equipment - 
General requirements  
UL 60079-1:2015 (Ed7): Explosive Atmospheres - Part 1: Equipment 
protection by flameproof enclosures “d” 
UL 60079-31:2012 (Ed 2): Explosive Atmospheres - Part 31: Equipment 
dust ignition protection by enclosure "t" 
 
CSA C22.2 NO. 60079-0:2015 (Ed 3) Explosive Atmospheres – Part 0: 
Equipment – General requirements  
CSA C22.2 NO. 60079-1:2016 (Ed 3): Explosive Atmospheres – Part 1: 
Equipment protection by flameproof enclosures “d” 
CSA C22.2 NO. 60079-31:2015 (Ed 2): Explosive Atmospheres – Part 31: 
Equipment dust ignition protection by enclosure “t” 

Class Division Ratings for US (NEC) & Canada (CEC) 

Model No: 

Rating 

GNExCP7-BG-S 

 

Class I Div 2 Group ABCD T6 Ta -55°C to 
+70°C 
Class II Div 2 Group FG T4 Ta -55°C to 
+70°C 
Class III Div 1 & 2 Ta -55°C to +70°C 

GNExCP7-BG-D 

 

Class I Div 2 Group ABCD T5 Ta -55°C to 
+70°C 
Class I Div 2 Group ABCD T6 Ta -55°C to 
+65°C 
Class II Div 2 Group FG T4 Ta -55°C to 
+70°C 
Class III Div 1 & 2 Ta -55°C to +70°C 

Class Zone Ratings for US (NEC)

 

Model No:

 

Rating

 

GNExCP7-BG-S 
 

Class I Zone 1 AEx db IIC T6 Gb Ta -55°C 
to +70°C 
Zone 21 AEx tb IIIC T110°C Db Ta -55°C to 
+70°C 

GNExCP7-BG-D 

Class I Zone 1 AEx db IIC T5 Gb Ta -55°C 
to +70°C 
Class I Zone 1 AEx db IIC T6 Gb Ta -55°C 
to +65°C 
Zone 21 AEx tb IIIC T135°C Db Ta -55°C to 
+70°C 

Class Zone Ratings for Canada (CEC)

 

Model No:

 

Rating

 

GNExCP7-BG-S 
 

Ex db IIC T6 Gb X Ta -55°C to +70°C 
Ex tb IIIC T110°C Db Ta -55°C to +70°C 

GNExCP7-BG-D 

Ex db IIC T5 Gb Ta -55°C to +70°C 
Ex db IIC T6 Gb Ta -55°C to +65°C 
Ex tb IIIC T135°C Db Ta -55°C to +70°C 

Installation must be carried out in compliance with the National Electric 
Code / Canadian Electric Code 

 
 

3.2 

ATEX / IECEx & UKEx Ratings 

 

Standards 

EN60079-0:2018/IEC60079-0:2017 (ed.7): Explosive Atmospheres - 
Equipment General Requirements. 
EN60079-1:2014/IEC60079-1:2014 (ed.7): Explosive Atmospheres - 
Equipment Protection by Flameproof Enclosures “d”. 
EN60079-31:2014/IEC60079-31:2013 (ed.2): Explosive Atmospheres - 
Equipment Dust Ignition Protection by enclosure “t”.

 

Model No: 

Rating 

GNExCP7-BG-S 

 

Ex db IIC T6 Gb Ta –55°C to +70°C 
Ex tb IIIC T80°C Db Ta –55°C to +70°C 

GNExCP7-BG-D 
 

Ex db IIC T5 Gb Ta –55°C to +70°C 
Ex db IIC T6 Gb Ta –55°C to +65°C 
Ex tb IIIC T85°C Db Ta –55°C to +70°C 

See Product table for electrical ratings of each unit model 

 
Certificate No.    

DEMKO 19 ATEX 2101X 
IECEx ULD 19.0097X  
UKEx UL UL21UKEX2134X          

Epsilon x 
Equipment Group 
and Category: 

 

II 2G 
II 2D

 

CE Marking and 
Notified Body No. 

 

2813 

UKCA Marking and 
Notified Body No. 

 

 

0518 

 
 

4)  Zones, Gas Group, Category and 

Temperature Classification 

The units can be installed in locations with the following conditions: 
 

Area Classification Gas 

Zone 1 

Explosive gas air mixture likely to occur in normal 
operation. 

Zone 2 

Explosive gas air mixture not likely to occur in normal 
operation, and if it does, it will only exist for a short time. 

Gas Groupings 

Group IIA 

Propane 

Group IIB 

Ethylene 

Group IIC 

Hydrogen and Acetylene 

Temperature Classification for Gas Applications 

T1 450

o

 C  

T2 300

o

 C 

Содержание GNE CP7-BG-D Series

Страница 1: ... 1 0A Max 24Vdc Max 3 33A Max Class Div Zone 5 0 Max ATEX IECEx UKEx Table 1 Electrical Ratings 2 Warnings WARNINGS USE COVER BOLTS CLASS A4 70 DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS PRESENT POTENTIAL ELECTROSTATIC CHARGING HAZARD SEE INSTRUCTIONS FOR INDOOR OR OUTDOOR USE TO REDUCE THE RISK OF IGNITION OF HAZARDOUS ATMOSPHERES CONDUIT RUNS MUST HAVE A SEALING FITTING CONNECTED WITHIN 2 INCHE...

Страница 2: ...to 70 C Class Zone Ratings for US NEC Model No Rating GNExCP7 BG S Class I Zone 1 AEx db IIC T6 Gb Ta 55 C to 70 C Zone 21 AEx tb IIIC T110 C Db Ta 55 C to 70 C GNExCP7 BG D Class I Zone 1 AEx db IIC T5 Gb Ta 55 C to 70 C Class I Zone 1 AEx db IIC T6 Gb Ta 55 C to 65 C Zone 21 AEx tb IIIC T135 C Db Ta 55 C to 70 C Class Zone Ratings for Canada CEC Model No Rating GNExCP7 BG S Ex db IIC T6 Gb X Ta ...

Страница 3: ...sive dust atmospheres 5 Specific Conditions for Safe Use The stainless steel lift flap is not earthed and may generate an ignition capable level of electrostatic charges It has a max capacitance of 6 33pF according to CSA C22 2 NO 60079 0 UL 60079 0 2017 clause 7 5 or EN IEC60079 0 clause 7 5 Equipment is permitted to be wall mounted only in vertical position The enclosure base is permitted in two...

Страница 4: ...tion of Cable Cable Glands Blanking Elements Adapters ATEx IECEx UKEx Installations The equipment must only be installed by suitably qualified personnel in accordance with the latest issues of the relevant standards EN60079 14 IEC60079 14 Explosive atmospheres Electrical installations design selection and erection EN60079 10 1 IEC60079 10 1 Explosive atmospheres Classification of areas Explosive g...

Страница 5: ...d as close as practical to the wall of the enclosure but in no case more than the size of the conduit or 2 of enclosure whichever is the lesser Electrical connections are to be made into the PCB terminal blocks DIN rail provided Internal earthing connections should be made to the Internal Earth terminal on the PCBA The earth conductor should be at least equal in size and rating to the incoming pow...

Страница 6: ... sectional areas such as 2 5mm 13 Testing unit operation The break glass unit can be tested without the need to break replace the frangible glass element A test key Plastic Key Supplied with unit is used to mechanically drop the glass down activating the switch The test key is inserted in the test cam and rotated clockwise by an angle of 90º the glass element will visibly drop down in the viewable...

Страница 7: ...The following table 2 shows limitations for all possible variations EOL End of line device resistor ExxxR diode ED1 zener ExxxZ Series In line device resistor SxxxR diode SD1 zener SxxxZ LED Microswitch 1 M S 1 Microswitch 2 M S 2 Table 2 EOL and Series Devices limits The unit can be wired with a maximum of 4 module devices see wiring diagram D202 06 211 Note The maximum voltage stated must not be...

Страница 8: ...in Operated condition Terminals 4 5 7 8 closed Terminals 4 5 6 open COM N O N C EOL SER NOTE These can be fitted either by customer or pre installed by E2S at point of order When fitting diodes or zener diodes polarity across devices must be observed Resistor polarity is unimportant SERIES EOL Wiring option shown with EOL series devices acting in parallel 3A Circuit as shown in Unoperated conditio...

Страница 9: ... 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 COM N O N C COM N O N C COM N O N C COM N O N C Standard Unit showing positions of optional Series and EOL Devices 1 2 3 4 5 6 M S 1 M S 2 7 8 N O COM 4A Circuit as shown in Unoperated condition Terminals 1 4 M S 1 and 5 8 M S 2 open Terminals 1 3 M S 1 and 5 7 M S 2 closed N C N O COM N C 1 2 3 4 5 6 M S 1 M S 2 7 8 N O COM EOL 4B Circuit as shown in Operated condit...

Страница 10: ... M S 2 7 8 N O COM 4A Circuit as shown in Unoperated condition Terminals 1 4 M S 1 and 5 8 M S 2 open Terminals 1 3 M S 1 and 5 7 M S 2 closed N C N O COM N C 1 2 3 4 5 6 M S 1 M S 2 7 8 N O COM EOL 4B Circuit as shown in Operated condition Terminals 1 4 M S 1 and 5 8 M S 2 closed Terminals 1 3 M S 1 and 5 7 M S 2 open N C N O COM N C SER EOL SER EOL 4A Circuit as shown in Unoperated condition Ter...

Страница 11: ...1 2 3 1 2 3 M S 1 M S 2 5B Circuit as shown in Operated condition Terminals 1 2 M S 1 and 4 5 M S 2 open Terminals 1 3 M S 1 and 4 6 M S 2 closed R N POTTS Optional Single or Double Microswitch Circuit shown with Double Microswitch Unit un operated GNExCP7 PCB Version Devices selected only as example On M S 1 Series resistor and EOL Zener diode On M S 2 EOL resistor with no series device GNExCP7 S...

Страница 12: ...quipment II 2G Ex d IIC T6 T5 Gb II 2D Ex tb IIIC T90 C T80 C Db Standards applied EN 60079 0 2018 EN 60079 1 2014 EN 60079 31 2014 IP6X Dust Protection to EN60079 0 EN60079 31 Directive 2014 30 EU Electromagnetic Compatibility Directive EMC Standards applied EN 61000 6 1 2007 EN 61000 6 2 2005 EN 61000 6 3 2007 A1 2011 AC 2012 EN 61000 6 4 2007 A1 2011 Directive 2011 65 EU Restriction of the use ...

Страница 13: ... d IIC T6 T5 Gb II 2D Ex tb IIIC T90 C T80 C Db Standards applied EN 60079 0 2018 EN 60079 1 2014 EN 60079 31 2014 IP6X Dust Protection to EN60079 0 EN60079 31 Directive 2014 30 EU Electromagnetic Compatibility Directive EMC Standards applied EN 61000 6 1 2007 EN 61000 6 2 2005 EN 61000 6 3 2007 A1 2011 AC 2012 EN 61000 6 4 2007 A1 2011 Directive 2011 65 EU Restriction of the use of certain hazard...

Отзывы: