European Safety Systems Ltd.
Impress House, Mansell Road, Acton, London W3 7QH
www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D209-00-201-IS
Issue 1
20-08-22
Sheet 1 of 5
INSTRUCTION MANUAL
E2xB05 & E2xB10 Xenon Beacons
For use in Hazardous Locations
E2XB1X05
E2XB1X10
1) Product Table
Ensure the system power supply is capable of providing the maximum current required for all units. Review associated cable
size, length and quantity of units on each circuit.
2) Warnings
DO NOT OPEN WHEN AN EXPLOSIVE
ATMOSPHERE IS PRESENT
DO NOT OPEN WHEN ENERGISED
POTENTIAL ELECTROSTATIC CHARGING
HAZARD - CLEAN ONLY WITH A DAMP
CLOTH
HIGH VOLTAGE SHOCK HAZARD. WAIT 5
MINUTES AFTER REMOVING POWER
BEFORE OPENING THE ENCLOSURE
Avertissement:
NE PAS OUVRIR UN PRESENCE
D’ATMOSPHERE EXPLOSIVE
NE PAS OUVRIR ENERGIE
DANGER POTENTIEL CHARGE
ÉLECTROSTATIQUE - NETTOYER
UNIQUEMENT AVEC UN CHIFFON HUMIDE
HAUT TENSION, RISK DE CHOC.
ATTENDEZ 5 MINUTES APRES AVOIR
DEBRANCHE L’ALIMENTATION AVANT
D’OUVRIR LA BOITIER
3) Rating & Marking Information
3.1. ATEX / IECEx / UKEx certification
Standards
EN IEC 60079-0:2018 / IEC60079-0:2017 (Ed 7):
Explosive Atmospheres - Equipment. General Requirements
EN IEC 60079-7:2015 +A1:2018 / IEC 60079-7:2018 (Ed. 5.1):
Explosive Atmospheres - Equipment Protection by Increased
Safety "e"
EN 60079-31:2014 / IEC 60079-31:2013 (Ed 2):
Explosive Atmospheres - Equipment Dust Ignition Protection
by Enclosure "t"
Ratings
E2XB05 :
Ex ec IIC T3 Gc Ta -20°C to +40°C
Ex ec IIC T2 Gc Ta -20°C to +55°C
Ex tc IIIC 85°C Dc Ta -20°C to +40°C
Ex tc IIIC 100°C Dc Ta -20°C to +55°C
E2XB10 :
Ex ec IIC T2 Gc Ta -20°C to +55°C
Ex tc IIIC 105°C Dc Ta -20°C to +40°C
Ex tc IIIC 120°C Dc Ta -20°C to +55°C
Model
Nom. Voltage
Voltage Range
Operating
rms Current
E2xB05DC012
12Vdc
10-14Vdc
520mA
E2xB05DC024
24Vdc
20-28Vdc
275mA
E2xB05DC048
48Vdc
42-54Vdc
145mA
E2xB05AC115
115Vac
N/- 10%
80mA
E2xB05AC230
230Vac
N/- 10%
30mA
E2xB10DC024
24Vdc
20-28Vdc
560mA
E2xB10DC048
48Vdc
42-54Vdc
260mA
E2xB10AC115
115Vac
N/- 10%
185mA
E2xB10AC230
230Vac
N/- 10%
107mA
The current levels shown above are for the worst-case input voltage resulting in max. current.
Table 1: Electrical Ratings.