background image

__________________________________________________________________________________________________________________ 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)208 743 8880 

                                                                                                                                                             www.e2s.com             Fax: +44 (0)208 740 4200 
Document No. D211-00-611-IS-SC      Issue:  E         02-03-2020               Sheet 3 of 13 

147,0mm [5,73in.]

116,0mm [4,52in.]

213,3m

m [8,

32in

.]

165,6mm [6,46in.]

9,7mm [0,38in.]

6,7mm

 [0,26

in.]

Ø6,9mm [Ø0,27in.]

310,3m

m [12,1

0

in

.]

125,0mm [4,88in.]

168,0mm [6,55in.]

147,0mm [5,73in.]

116,0mm [4,52in.]

213

,3

mm [

8,

32in.]

165,6mm [6,46in.]

9,7mm [0,38in.]

6,7

m

m

 [0,

26

in.]

Ø6,9mm [Ø0,27in.]

31

0,

3m

m [

12,

10

in

.]

125,0mm [4,88in.]

179,3mm [6,99in.]

Beacon 
Cover 
 
M4 Screws 
(4-off) 
 
 
 
M5 Earth 
Stud 

Sounder 
Cover 
 
M4 
Screws 
(4-off) 

 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

Fig. 1a Fixing locations Public Mode Alarm. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Fig. 1b Fixing locations Private Mode Alarm. 

 

5) 

Access to the Enclosure 

 

 

 

 

 

To access the enclosure, loosen the four M4 posi pan head 
screws and withdraw the cover 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Fig. 2 Accessing the Enclosure

 

To replace cover, check that the ‘O’ ring seal is in place. 
Carefully push the cover in place. Insert M4 screws with fiber 
washers and tighten to 3Nm torque. 

 

6) 

Selection of Cable, Cable Glands, Blanking 

Elements & Adapters 

 

When selecting the cable size, consideration must be given to 
the input current that each unit draws (see Table 1), the number 
of beacons on the line and the length of the cable runs. The 
cable size selected must have the necessary capacity to provide 
the input current to all of the sounders connected to the line.  
 
When selecting the cable size consideration must be given to 
the voltage drop over the length of the cable run to ensure the 
min. input voltage at the point of use (voltage range, see section 
13) 
 
The voltage drop depends on: 

The total current draw if the devices installed on this 
cable run 

-  The wire size and total length of the cable run, 

determining the total resistance of this cable run 

The minimum output voltage supplied by the power 
supply 

 
The voltage drop and input voltage at the point of use can be 
calculated as follows (for guidance on the resistance of different 
wire sizes see section 14) 
 
Total Wire resistance =  
Wire resistance / 1000ft x length of cable run x 2 
 
(length of cable run needs to be multiplied by two to account for 
two wires going to and from the unit) 
 
Total current draw = 
Current draw per unit x number of units 
 
Voltage Drop = Total current draw x Total wire resistance 
 
Minimum output of power supply = 
Min. voltage at point of use + voltage drop 
 
For ambient temperatures over +45ºC the cable entry 
temperature may 70ºC. Therefore suitable heat 
resisting cables and cable glands, rated to min. 75ºC must be 
used. 
 
If a high IP (Ingress Protection) rating is required then a suitable 
sealing washer must be fitted under the cable glands or 
blanking plugs. 
 
For use in explosive dust atmospheres, a minimum ingress 
protection rating of IP6X must be maintained. 
 
For use in explosive gas atmospheres, a minimum ingress 
protection rating of IP54 must be maintained. 
 
NPT plugs should be greased before insertion. 
 

7) 

Cable Connections 

 

Electrical connections are to be made into the terminal blocks 
on the PCBA located in the enclosure. See section 5 of this 
manual for access to the enclosure.  

 

Wires having a cross sectional area between 0.5 mm² to 
2.5mm² can be connected to each terminal way. If an input and 
output wire is required the 2-off Live/Neutral or +/- terminals can 
be used. If fitting 2-off wires to one terminal way the sum of the 

Warning – High voltage may be present, 
risk of electric shock. DO NOT open when 
energised, disconnect power before 
opening. 

Warning –

 

Hot surfaces. External surfaces 

and internal components may be hot after 
operation, take care when handling the 
equipment. 

Содержание D2xC2LD2 Series

Страница 1: ...om UL464 92 2dB A at 10 feet reverberation room Testing of synchronization requirements of UL1971 UL1638 CAN ULC S526 were conducted by UL using a total of 6 units connected to the same wire run Auto...

Страница 2: ...e rating per UL50E NEMA250 4 4X 3R 13 To maintain the ingress protection rating the cable entries must be fitted with suitably rated certified cable entry and or blanking devices during installation 2...

Страница 3: ...on this cable run The wire size and total length of the cable run determining the total resistance of this cable run The minimum output voltage supplied by the power supply The voltage drop and input...

Страница 4: ...Simply connect the supply voltage to the L and N supply terminals see fig 3a b The Strobe is powered via factory installed wires connected to the sounder The wires connecting the alarm horn and strob...

Страница 5: ...their supply input lines An end of line monitoring resistor can be connected across the ve and ve terminals If an end of line resistor is used it must have the following values 24V DC Alarm Horn and...

Страница 6: ...ip Switch 1 ON 0 OFF Example shown 100000 Flashing 1Hz Default setting 13 Interchangeable Spare Parts The Beacon lens cover is interchangeable contact E2S Ltd for a replacement lens cover available in...

Страница 7: ...out to the correct NFPA standards and guidelines 15 1 Horizontal Light Output Dispersion for wall mounting public mode 0 15 15 30 45 60 75 90 90 30 45 60 75 Fig 13 Horizontal dispersion angles for wal...

Страница 8: ...sion for wall mounting public mode 75 60 45 30 15 0 90 Fig 14 Vertical dispersion angles for wall mounting Table 4 Vertical Light Output Dispersion for Wall Mounting Viewing Angle Of Rating Intensity...

Страница 9: ...per UL 1971 UL1638 CAN ULC S526 at worst case min input voltage 15 4 On axis light output rating private mode Table 5 Vertical Light Output Dispersion for Ceiling Mounting Viewing Angle Of Rating Inte...

Страница 10: ...z 47 4mA 47 4mA Flashing 1 5Hz 50 3mA 50 3mA Flashing 2Hz 51 1mA 51 1mA Flashing Double Strike 62 2mA 62 2mA Flashing Triple Strike 69 2mA 69 2mA D2xC2LD2AC115 115Vac 60Hz 115 120Vac 50 60Hz Steady Hi...

Страница 11: ...0 208 740 4200 Document No D211 00 611 IS SC Issue E 02 03 2020 Sheet 11 of 13 17 Sound Directional Characteristics for Canadian Fire CAN ULC S525 Horizontal Axis Angle OSPL Angle OSPL Reference 90 10...

Страница 12: ...n 0 5s off x3 1s gap ISO 8201 Temporal Pattern 0 1 0 1 0 0 44 1 8 12 1000Hz 0 5s on 0 5s off x3 1s gap ISO 8201 Temporal Pattern 1 1 0 1 0 0 44 1 8 13 422 775Hz 0 85 on 0 5 off x3 1s gap NFPA Temporal...

Страница 13: ...1 44 24 12 49 560 1055Hz 0 18Hz Sweeping 0 0 0 0 1 1 44 24 12 50 560 1055Hz 3 3Hz Sweeping 1 0 0 0 1 1 44 24 12 51 600 1250Hz 0 125Hz Sweeping 0 1 0 0 1 1 44 24 12 52 660 1200Hz 1Hz Sweeping 1 1 0 0 1...

Отзывы: