E2S D2xB1X05 Series Скачать руководство пользователя страница 1

 

 
 
 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH

 

www.e2s.com

 

Tel: +44 (0)208 743 8880

 

Document No. D211-00-201-IS

 

Issue 1

 

20-08-22

 

 

Sheet 1 of 6

 

 

INSTRUCTION MANUAL 

D2xB1X05 & D2xB1X10 Xenon Beacons 
For use in Hazardous Locations

 

 

 

D2XB1X05 
D2XB1X10 
 

 

1)  Product Table 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
2)  Warnings 
 

 DO NOT OPEN WHEN AN EXPLOSIVE 

ATMOSPHERE IS PRESENT 

 DO NOT OPEN WHEN ENERGISED 

 POTENTIAL ELECTROSTATIC CHARGING 

HAZARD - CLEAN ONLY WITH A DAMP 
CLOTH 

 HIGH VOLTAGE SHOCK HAZARD. WAIT 5 

MINUTES AFTER REMOVING POWER 
BEFORE OPENING THE ENCLOSURE 
 

Avertissement: 

 NE PAS OUVRIR UN PRESENCE 

D’ATMOSPHERE EXPLOSIVE 

 NE PAS OUVRIR ENERGIE 

 DANGER POTENTIEL CHARGE 

ÉLECTROSTATIQUE - NETTOYER 
UNIQUEMENT AVEC UN CHIFFON HUMIDE 

 HAUT TENSION, RISK DE CHOC. 

ATTENDEZ 5 MINUTES APRES AVOIR 
DEBRANCHE L’ALIMENTATION AVANT 
D’OUVRIR LA BOITIER 

 
 
 
 

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
3)  Rating & Marking Information 

 

All units have a rating label, which carries the following 
important information: 
 
• 

Unit Model. 

• 

Voltage Range 

• 

Nominal Voltage 

 
See Table 1 for electrical ratings of each Unit Model. 
 

3.1. Fire Alarm Ratings  

 

The Following models are certified as visual alarm devices for 
private  mode  visual  alarm  devices  in  accordance  with 
UL1638  Fifth  Edition  /  CAN/ULC-S526  Fourth  Edition  when 
used with clear or red lens covers: 

 

D2XB1X05DC024 ; D2XB1X05DC048 
D2XB1X10DC024 ; D2XB1X10DC048 

 

See fire instruction manual D211-00-201-IS-SC-UL 

 

Model 

Nom. Voltage 

Voltage Range 

Operating 

rms Current

 

D2xB1X05DC024 

24Vdc 

20-28Vdc 

296mA 

D2xB1X05DC048 

48Vdc 

48Vdc 

145mA 

D2xB1X05AC115 

115Vac 

115-120Vac 50/60Hz 

80mA  

D2xB1X05AC230 

230Vac 

220-230Vac 50/60Hz 

30mA 

D2xB1X10DC024 

24Vdc 

20-28Vdc 

609mA 

D2xB1X10DC048 

48Vdc 

48Vdc 

260mA 

D2xB1X10AC115 

115Vac 

115-120Vac 50/60Hz 

185mA 

D2xB1X10AC230 

230Vac 

220-230Vac 50/60Hz 

107mA 

Table 1: Electrical Ratings. 

Содержание D2xB1X05 Series

Страница 1: ...IMENTATION AVANT D OUVRIR LA BOITIER 3 Rating Marking Information All units have a rating label which carries the following important information Unit Model Voltage Range Nominal Voltage See Table 1 f...

Страница 2: ...FG T4A Ta 40 C to 50 C Class II Div 2 FG T5 Ta 40 C to 45 C Class III Div 1 2 Ta 40 C to 50 C D2xB1 X10DC048 X10AC115 X10AC230 Class I Div 2 ABCD T2B Ta 40 C to 50 C Class II Div 2 FG T5 Ta 40 C to 50...

Страница 3: ...ain the ingress protection rating the two off cable entries must be fitted with suitably rated certified cable entry and or blanking devices during installation Type Rating Per UL50E NEMA250 4 4X 3R 1...

Страница 4: ...IP6X must be maintained For use in explosive gas atmospheres a minimum ingress protection rating of IP54 must be maintained NPT plugs should be greased before insertion 8 Cable Connections Electrical...

Страница 5: ...e PCBA as shown in Fig 8a or 8b A spacing of at least 1 16 1 58mm must be provided through air and over surfaces between uninsulated live parts Fig 7 End of Line Resistor Forming Fig 8a End of Line Re...

Страница 6: ...rhaul of the equipment should only be carried out by suitably qualified personnel in accordance with the current relevant standards EN60079 19 IEC60079 19 Explosive atmospheres Equipment repair overha...

Страница 7: ...rm Ratings The Following models are certified as visual alarm devices for private mode visual alarm devices in accordance with UL1638 Fifth Edition CAN ULC S526 Fourth Edition when used with clear or...

Страница 8: ...27 06 2019 27 06 2019 27 06 2019 MOD No REASON INITIAL DATE ISSUE 1 INTRODUCTION RSR 02 01 2020 D2x DC XENON D2XB1X05 X10 UNITS Line Monitoring Power ve ve AC D2XB1X05 X10 UNITS Power Live Neutral 2...

Страница 9: ...herlands B V Utrechtseweg 310 6812 AR Arnhem Netherlands Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 3G Ex ec IIC T6 T4 T3 T2 T1 Gc II 3D Ex tc I...

Страница 10: ...e and Place of Issue London 22 08 2022 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the m...

Страница 11: ...Lane Eccleston Chester CH4 9JN UK Quality Assurance Notification Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 3G Ex ec IIC T6 T4 T3 T2 T1 Gc II 3D Ex tc IIIC Ex tc IIIC T55 75 80...

Страница 12: ...Place of Issue London 22 08 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the marke...

Отзывы: