INSTRUCTION MANUAL 

D1xS2 
Alarm Horn Sounder

 

Class I, Zone 1, 2, 21 & 22

 

 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH

www.e2s.com

 

Tel: +44 (0)208 743 8880

Document No. D190-00-101-IS

 

Issue 3

 

28-11-2022

Sheet 1 of 8

 

 

 
 

D1xS2F

 

D1xS2H

 

 

1)  Product Table 

 

Unit Type Code 

Nominal 

Input Voltage 

Nominal 

Current P2 

Nominal 

Current P3 

Voltage Range 

Sound 

Pressure Level 

dB(A)

Max* 

P2/P3

Nom

.†

P2/P3

 

D1xS2FDC024-A 

12Vdc 

289mA

356mA

11.5-54Vdc 

120/123

 

115/118

 

24Vdc 

324mA

740mA

48Vdc 

195mA

391mA

D1xS2FAC230-A 

115Vac 

125mA 

282mA 

100-240Vac 50/60Hz 

230Vac 

78mA

167mA

D1xS2HDC024-A 

12Vdc 

289mA

356mA

11.5-54Vdc 

124/127

 

119/122

 

24Vdc 

324mA

740mA

48Vdc 

195mA

391mA

D1xS2HAC230-A 

115Vac 

125mA 

282mA 

100-240Vac 50/60Hz 

230Vac 

78mA

167mA

*Max = Tone 4 

Nom. = Tone 44 

 
The table shows the input current taken by the various sounders. 
The current levels shown above are for the 440Hz Continuous tone @ nominal input voltage.  
Nominal current at nominal voltage.
Table 1: Electrical Ratings. 

 

2)  Warnings   

 

 
 
CAUTION 
TO  REDUCE  THE  RISK  OF  IGNITION  OF  HAZARDOUS 
ATMOSPHERES: 
DISCONNECT FROM SUPPLY BEFORE OPENING. 
KEEP TIGHTLY CLOSED WHEN IN OPERATION. 
WARNING 
FIT  SEALING  FITTING  IN  CONDUIT  RUNS  WITHIN  18  INCHES 
FROM ENCLOSURE. 
EQUIPMENT MUST NOT BE INSTALLED WITH THE HORN FACING 
UPWARDS OF HORIZONTAL 
DO  NOT  OPEN  WHEN  AN  EXPLOSIVE  ATMOSPHERE  IS 
PRESENT  
DO NOT OPEN WHEN ENERGISED  
POTENTIAL  ELECTROSTATIC  CHARGING  HAZARD  -  CLEAN 
ONLY WITH A DAMP CLOTH  
ENCLOSURE ENTRIES: TWIN M20 X 1.5 / SINGLE 1/2” NPT 
ATEX/IECEx  &  UKEx  INSTALLATIONS:  IF  TEMPERATURE 
EXCEEDS 70°C AT ENTRY OR 80°C AT BRANCHING POINT USE 
SUITABLE RATED CABLE AND GLANDS 

 

 
 
 

ATTENTION 
POUR 

REDUIRE 

LE 

RISQUE 

D’INFLAMMATION 

DES 

ATMOSPHÈRES DANGEREUSES : 
COUPER L 'ALIMENTATION AVANT OUVERTURE. 
CONSERVER FERMÉ PENDANT LE FONCIONNEMENT. 
AVERTISSEMENT 
CONDUITS DOIVENT ETRE SCELLES EN MOINS DE 18 POUCES. 
ÉQUIPEMENT NE DOIT PAS ETRE INSTALLE AVEC LE KLAXON 
TOURNEE VERS LE HAUT DE HORIZONTAL. 
NE PAS OUVRIR UN PRESENCE D’ATMOSPHERE EXPLOSIVE  
NE PAS OUVRIR ENERGIE  
DANGER POTENTIEL CHARGE ÉLECTROSTATIQUE - NETTOYER 
UNIQUEMENT AVEC UN CHIFFON HUMIDE  
ENTRÉES DE BOÎTIER: 2 x M20 X 1.5 / 1 x 1/2” NPT 
ATEX/IECEx  &  UKEx  INSTALLATIONS :  SI  LA  TEMPÉRATURE 
DÉPASSE  70  °C  À  L'ENTRÉE  OU  80  °C  AU  POINT  DE 
BRANCHEMENT,  UTILISER  UN  CÂBLE  ET  DES  JOINTS 
D'ÉTANCHÉITÉ APPROPRIÉS 

Содержание D1xS2 Series

Страница 1: ...S ATMOSPHERES DISCONNECT FROM SUPPLY BEFORE OPENING KEEP TIGHTLY CLOSED WHEN IN OPERATION WARNING FIT SEALING FITTING IN CONDUIT RUNS WITHIN 18 INCHES FROM ENCLOSURE EQUIPMENT MUST NOT BE INSTALLED WI...

Страница 2: ...C Ex tb IIIC T95 C Db Ta 55 C to 75 C D1xS2 AC230 A Ex db IIC T5 Gb Ta 55 C to 75 C Ex db IIC T6 Gb Ta 55 C to 60 C Ex tb IIIC T93 C Db Ta 55 C to 75 C See Product table for electrical ratings of eac...

Страница 3: ...arges on non conducting surfaces Only the explosionproof cover is to be used for access to the enclosure for installation service and maintenance 6 Specific Conditions for Safe Use Flameproof threaded...

Страница 4: ...connected to the line AC 1 0 2 5mm2 AWG18 AWG12 DC 0 2 2 5mm2 AWG24 AWG12 Fig 3 Wire Preparation When connecting wires to the terminals great care should be taken to dress the wires so that when the c...

Страница 5: ...ders See schematic diagram D190 06 001 for details 9 1 Configuration See Table 1 for product power supply and Sound Pressure Levels SPL Configuration for DC Units Fig 5 DC PCBA Configuration for AC Un...

Страница 6: ...iring options Config Voltage Configuration Description Features Product Option Identifier 1a DC Single Stage Configuration Line monitoring Positive Switching 1 1b DC Two Stage Configuration Common Neg...

Страница 7: ...Resistor placement Optional 12 Way Terminal Module 11 Maintenance Overhaul and Repair Maintenance repair and overhaul of the equipment should only be carried out by suitably qualified personnel in acc...

Страница 8: ...ces may be fitted between the ve ve terminals of the PCBA Please ensure that the device legs meet the wire size range stated for the connection terminals and are fitted correctly in order to avoid a s...

Страница 9: ...0 1 0 1 0 0 0 0 1 1 0 0 0 1 1 1 0 0 0 0 0 0 1 0 0 1 0 0 1 0 0 0 1 0 1 0 0 1 1 0 1 0 0 0 0 1 1 0 0 1 0 1 1 0 0 0 1 1 1 0 0 1 1 1 1 0 0 0 0 0 0 1 0 1 0 0 0 1 0 0 1 0 0 1 0 1 1 0 0 1 0 0 0 1 0 1 0 1 0 1...

Страница 10: ...US 100 2dB A CA 108 5dB A P3 US 103 5dB A CA 111 6dB A at 10 feet 24Vdc For Fire Alarm applications the Sounder Volume must be at the highest setting see volume control section For fire alarm use Ton...

Страница 11: ...al Axis 3dB A 39 41 38 41 6dB A 45 47 64 69 D1xS2FDC024 A D1xS2FDC024 S Sounder Directional Characteristics for Canadian Fire CAN ULC S525 P3 OSPL Horizontal Axis Vertical Axis 3dB A 46 48 46 47 6dB A...

Страница 12: ...INE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120 MIN 2W MIN OR 1K MIN 0 5W MIN 28V MAX SYSTEM 470 MIN 2W MIN OR 2 4K MIN 0 5W MIN RECOMMENDED MINIMUM VALUES R1 Stage 1 ve IN Stage 1 ve OUT...

Страница 13: ...n ve OUT Stage 1 ve OUT Stage 3 ve Stage 1 ve IN H2 H1 Stage 1 ve Stage 1 ve Stage 2 ve Stage 2 ve OF 2 3 R1 S2 S3 R1 S2 R2 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120 MIN 2...

Страница 14: ...er to Stage 2 ve Stage 2 ve Two Three Stage Voltage Free Activation Configuration Config 5 Customer Set H1 H2 to Negative Switching See Below Power ve ve Stage 1 Connect Stage 1 ve to Common ve Stage...

Страница 15: ...5 R S RAIT B ISARD R N POTTS OF NTS 1 SWITCHES FOR STAGE OPERATION CUSTOMER SUPPLIED 1 Earth Earth Stage 2 Stage 3 Common Live IN Live OUT Neutral IN Neutral OUT Earth Stage 1 Stage 2 Common N N L L E...

Страница 16: ...warden Industrial Park Hawarden Deeside CH5 3US UK Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 2G Ex db IIC T6 T3 GB II 2D Ex tb IIIC T82 C 145 C...

Страница 17: ...e and Place of Issue London 10 02 2022 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the m...

Страница 18: ...CH4 9JN UK Quality Assurance Notification Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 2G Ex db IIC T6 T3 GB II 2D Ex tb IIIC T82 C 145 C Db Standards applied EN 60079 0 2018 EN...

Страница 19: ...te and Place of Issue London 24 02 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on th...

Страница 20: ...Page left Intentionally blank...

Отзывы: