7.3 Tone Selection 

 

The  D1x  Alarm Horn Sounders have 64 different tones that can be 
selected independently for the first and second stage alarms. The 
tones are selected by operation of the tone setting DIP switch 1 & DIP 
2witch 2 (see figures 6  and  7) on the PCB, for stage 1 and stage 2 
respectively.  
 

Default = Switch 2   

S2 - Tone 1 

0 0 0 0 0 0 

Default = Switch 1  

S1 – Tone 44 

1 1 0 1 0 1 

 

 

(ON = 1, OFF = 0) 

Figure 7: DIP switch configuration 

 

The sounder can also be switched to sound the third and fourth stage 
alarm tones.

 

 

The tone table (D221-95-001-IS) shows the switch positions for the 64 
tones on first and second stages and which tones are available for the 
third and fourth stages dependent on the Stage 1 DIP switch setting. 

 
Following table (Table 3) is a summary of DC: D190-06-001; AC: 
D190-06-005 wiring options.

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 

 

Config. 

Voltage 

Configuration Description 

Features  

Product 
Option 
Identifier 

1a 

DC 

Single Stage Configuration 

 

Line monitoring 

 

Positive Switching 

1b 

DC 

Two Stage Configuration 

 

Common Negative  

 

Positive Switching 

1c 

DC 

Three/Four Stage Configuration 

 

Common Negative  

 

Positive Switching 

DC 

Three/Four Stages. Voltage Free 2nd, 3rd & 
4th Stage Activation Configuration 

 

Common Positive 

 

Customer Set H1 & H2 to Negative 
Switching  

DC 

Two Stage Configuration 

 

Independent Stage Input 

 

Reverse Polarity Stage Monitoring 

DC 

Two Stage Configuration 

 

Line Stage Monitoring (Use suitable 
monitoring relays/ modules) 

 

Not to be used in reverse polarity 
monitoring 

DC 

Two/Three Stage Voltage Free Activation 
Configuration 

 

DC 

Three/Four Stage Configuration 

 

Independent Stage Input 

 

Line Stage Monitoring (Use suitable 
monitoring relays/ modules) 

 

Positive Switching (Default) 

1a 

AC 

Single Stage Configuration 

 

1b 

AC 

Three/Four Stage Configuration 

 

AC 

Two/Three Stage Voltage Free Activation 
Configuration 

 

Table 3: Summary of Wiring Options. See Document D190-06-001 for DC Schematic Diagrams; D190-06-005 for AC Schematic 
Diagrams. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание D1xS1FAC230-D

Страница 1: ...KEEP TIGHTLY CLOSED WHEN IN OPERATION WARNING FIT SEALING FITTING IN CONDUIT RUNS WITHIN 18 INCHES FROM ENCLOSURE EQUIPMENT MUST NOT BE INSTALLED WITH THE HORN FACING UPWARDS OF HORIZONTAL DO NOT OPE...

Страница 2: ...housing using a ring crimp terminal to secure the earth conductor under the earth clamp The earth conductor should be at least equal in size and rating to the incoming power conductors but at least a...

Страница 3: ...threads in the process 6 Installation Requirements 6 1 Safe Installation Requirements Warning High voltage may be present risk of electric shock DO NOT open when energised disconnect power before open...

Страница 4: ...range can be supplied with the following types of adapters M20 to NPT M20 to NPT M20 to M25 It is important to note that stopping plugs cannot be fitted onto adapters only directly onto the M20 entri...

Страница 5: ...005 wiring options Config Voltage Configuration Description Features Product Option Identifier 1a DC Single Stage Configuration Line monitoring Positive Switching 1 1b DC Two Stage Configuration Commo...

Страница 6: ...8 End of Line Resistor placement 8Custom DC Multi Stage End Of Line Monitoring An optional 12 way terminal module is available to enable up to four alarm stages to be activated from three DC voltage...

Страница 7: ...Only End of Line Devices may be fitted between the ve ve terminals of the PCBA Please ensure that the device legs meet the wire size range stated for the connection terminals and are fitted correctly...

Страница 8: ...0 0 0 1 0 1 0 0 0 0 1 1 0 0 0 1 1 1 0 0 0 0 0 0 1 0 0 1 0 0 1 0 0 0 1 0 1 0 0 1 1 0 1 0 0 0 0 1 1 0 0 1 0 1 1 0 0 0 1 1 1 0 0 1 1 1 1 0 0 0 0 0 0 1 0 1 0 0 0 1 0 0 1 0 0 1 0 1 1 0 0 1 0 0 0 1 0 1 0 1...

Страница 9: ...INE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120 MIN 2W MIN OR 1K MIN 0 5W MIN 28V MAX SYSTEM 470 MIN 2W MIN OR 2 4K MIN 0 5W MIN RECOMMENDED MINIMUM VALUES R1 Stage 1 ve IN Stage 1 ve OUT...

Страница 10: ...n ve OUT Stage 1 ve OUT Stage 3 ve Stage 1 ve IN H2 H1 Stage 1 ve Stage 1 ve Stage 2 ve Stage 2 ve OF 2 3 R1 S2 S3 R1 S2 R2 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120 MIN 2...

Страница 11: ...er to Stage 2 ve Stage 2 ve Two Three Stage Voltage Free Activation Configuration Config 5 Customer Set H1 H2 to Negative Switching See Below Power ve ve Stage 1 Connect Stage 1 ve to Common ve Stage...

Страница 12: ...5 R S RAIT B ISARD R N POTTS OF NTS 1 SWITCHES FOR STAGE OPERATION CUSTOMER SUPPLIED 1 Earth Earth Stage 2 Stage 3 Common Live IN Live OUT Neutral IN Neutral OUT Earth Stage 1 Stage 2 Common N N L L E...

Отзывы: