INSTRUCTION MANUAL 

D1xL1 & D1xL2 
Loudspeaker

 

Class I, Zone 1, 2, 21 & 22

 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH

 

www.e2s.com

 

Tel: +44 (0)208 743 8880

 

Document No. D190-00-201-IS

 

Issue 1

 

16-03-2022

 

Sheet 1 of 6

 

D1xL1F 

D1xL2F 

D1xL2H 

1)

Product Table

Unit Type Code 

Input 

Power (Watts) 

Max I/P Volts 

Sound 

Pressure Level 

dB(A) 

Max 

Rated 

Pink 

Noise 
@ 1W 

D1xL1FV100-A 

100V Line 

15 

100 

113 

106 

D1xL1FV070-A 

70V Line 

15 

70 

D1xL1FR008-A 

8 Ohm 

15 

10.95 

D1xL1FR016-A 

16 Ohm 

15 

15.49 

D1xL2FV100-A 

100V Line 

25 

100 

118 

108 

D1xL2FV070-A 

70V Line 

25 

70 

D1xL2FR008-A 

8 Ohm 

25 

14.14 

D1xL2FR016-A 

16 Ohm 

25 

20 

D1xL2HV100-A 

100V Line 

25 

100 

121 

111 

D1xL2HV070-A 

70V Line 

25 

70 

D1xL2HR008-A 

8 Ohm 

25 

14.14 

D1xL2HR016-A 

16 Ohm 

25 

20 

Frequency Range: 400Hz to 8000Hz 

The table shows the input current taken by the various Loudspeakers. 

Nominal current at nominal voltage. 

Table 1: Electrical Ratings. 

2)

Warnings

CAUTION 
TO  REDUCE  THE  RISK  OF  IGNITION  OF  HAZARDOUS 
ATMOSPHERES: 
DISCONNECT FROM SUPPLY BEFORE OPENING. 
KEEP TIGHTLY CLOSED WHEN IN OPERATION. 
WARNING 
FIT  SEALING  FITTING  IN  CONDUIT  RUNS  WITHIN  18  INCHES 
FROM ENCLOSURE. 
EQUIPMENT MUST NOT BE INSTALLED WITH THE HORN FACING 
UPWARDS OF HORIZONTAL 
DO  NOT  OPEN  WHEN  AN  EXPLOSIVE  ATMOSPHERE  IS 
PRESENT  
DO NOT OPEN WHEN ENERGISED  
POTENTIAL  ELECTROSTATIC  CHARGING  HAZARD  -  CLEAN 
ONLY WITH A DAMP CLOTH  
ENCLOSURE ENTRIES: TWIN M20 X 1.5 / SINGLE 1/2” NPT 
ATEX/IECEx  &  UKEx  INSTALLATIONS:  IF  TEMPERATURE 
EXCEEDS 70°C AT ENTRY OR 80°C AT BRANCHING POINT USE 
SUITABLE RATED CABLE AND GLANDS 

ATTENTION 
POUR 

REDUIRE 

LE 

RISQUE 

D’INFLAMMATION 

DES 

ATMOSPHÈRES DANGEREUSES : 
COUPER L 'ALIMENTATION AVANT OUVERTURE. 
CONSERVER FERMÉ PENDANT LE FONCIONNEMENT. 
AVERTISSEMENT 
CONDUITS DOIVENT ETRE SCELLES EN MOINS DE 18 POUCES. 
ÉQUIPEMENT  NE  DOIT PAS  ETRE INSTALLE  AVEC  LE  KLAXON 
TOURNEE VERS LE HAUT DE HORIZONTAL. 
NE PAS OUVRIR UN PRESENCE D’ATMOSPHERE EXPLOSIVE  
NE PAS OUVRIR ENERGIE  
DANGER POTENTIEL CHARGE ÉLECTROSTATIQUE - NETTOYER 
UNIQUEMENT AVEC UN CHIFFON HUMIDE  
ENTRÉES DE BOÎTIER: 2 x M20 X 1.5 / 1 x 1/2” NPT 
ATEX/IECEx  &  UKEx  INSTALLATIONS :  SI  LA  TEMPÉRATURE 
DÉPASSE  70  °C  À  L'ENTRÉE  OU  80  °C  AU  POINT  DE 
BRANCHEMENT,  UTILISER  UN  CÂBLE  ET  DES  JOINTS 
D'ÉTANCHÉITÉ APPROPRIÉS 

Содержание D1xL1FR008-A

Страница 1: ...BEFORE OPENING KEEP TIGHTLY CLOSED WHEN IN OPERATION WARNING FIT SEALING FITTING IN CONDUIT RUNS WITHIN 18 INCHES FROM ENCLOSURE EQUIPMENT MUST NOT BE INSTALLED WITH THE HORN FACING UPWARDS OF HORIZO...

Страница 2: ...ne 21 AEx tb IIIC 91 C Db Ta 55 C to 75 Class Zone Ratings for Canada CEC Model No Rating D1xL1 V100 A D1xL1 V070 A D1xL1 R008 A D1xL1 R016 A Ex db IIC T5 Gb 55 C to 75 C Ex db IIC T6 Gb 55 C to 60 C...

Страница 3: ...made using conduit openings must have a sealing fitting connected as close as practical to the wall of the enclosure but in no case more than the size of the conduit or 50mm whichever is the lesser A...

Страница 4: ...ole in the enclosure and connect the field wiring to the appropriate terminals as shown in D190 06 201 The power supply terminals are duplicated so that units may be connected in parallel An end of li...

Страница 5: ...minals great care should be taken to dress the wires so that when the cover is inserted into the chamber the wires do not exert excess pressure on the terminal blocks This is particularly important wh...

Страница 6: ...atts or a minimum resistance value of 500 ohms and a minimum wattage of 2 watts On the low impedance units care must be taken with the polarity of the monitoring voltage If an end of line resistor is...

Страница 7: ...SCALE ALL DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B D190 06 201 D HOWGILL R N POTTS R N POTTS 18 11 20 OF NTS 1 3 A INTRODUCTION D H 18 11 20 18 11 20 18 11 20 D...

Страница 8: ...SCALE ALL DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B D190 06 201 D HOWGILL R N POTTS R N POTTS 18 11 20 OF NTS 2 3 18 11 20 18 11 20 D1xL1 D1xL2 LINE IN LOW IMPED...

Страница 9: ...LAR DIMENSIONAL TOLS STANDARDS MOD No REASON INITIAL DATE ISSUE DATE APPROVED CHECKED DATE DATE DRAWN WEIGHT Kg SURFACE FINISH MATERIAL ALTERNATIVE MATERIAL SHEET SCALE TITLE A3 IF IN DOUBT ASK DO NOT...

Страница 10: ...warden Industrial Park Hawarden Deeside CH5 3US UK Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 2G Ex db IIC T6 T3 GB II 2D Ex tb IIIC T82 C 145 C...

Страница 11: ...e and Place of Issue London 10 02 2022 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the m...

Страница 12: ...CH4 9JN UK Quality Assurance Notification Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 2G Ex db IIC T6 T3 GB II 2D Ex tb IIIC T82 C 145 C Db Standards applied EN 60079 0 2018 EN...

Страница 13: ...te and Place of Issue London 24 02 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on th...

Страница 14: ...Page left Intentionally blank...

Отзывы: