INSTRUCTION & SERVICE MANUAL 

D1xL1 & D1xL2 LOUDSPEAKER 

For Use In Hazardous Locations - Gas 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

1)  Introduction 

 
The  D1xL1  & D1xL2  are  UL  certified  loudspeakers which 
produce  a loud warning signal in a hazardous area.  The 
loudspeaker are approved for use in Gas applications in Class I 
Division 1 & 2 as well as Class I Zone 0, 1 and 2.  
D1xS1 & D1xS2  alarm horns and D1xC1 & D1xC2 Combined 
alarm horn & Strobe  are  also available  as well as variants for 
Explosive Dust Atmospheres. 

 

2)  Warnings 

 
CAUTION 
TO REDUCE THE RISK OF IGNITION OF HAZARDOUS 
ATMOSPHERES: 
DISCONNECT FROM SUPPLY BEFORE OPENING. 
KEEP TIGHTLY CLOSED WHEN IN OPERATION. 
WARNING 
FIT SEALING FITTING IN CONDUIT RUNS WITHIN 18 
INCHES FROM ENCLOSURE. 
EQUIPMENT MUST NOT BE INSTALLED WITH THE HORN 
FACING UPWARDS OF HORIZONTAL 
 
ATTENTION 

P

OUR REDUIRE LE RISQUE D’INFLAMMATION  DES 

ATMOSPHÈRES DANGEREUSES: 
COUPER L 'ALIMENTATION AVANT OUVERTURE. 
CONSERVER FERMÉ PENDANT LE FONCIONNEMENT. 
AVERTISSEMENT 
CONDUITS DOIVENT ÊTRE SCELLÉS EN MOINS DE 18 
POUCES. 
ÉQUIPEMENT NE DOIT PAS ÊTRE INSTALLÉ AVEC LE 
KLAXON TOURNÉE VERS LE HAUT DE HORIZONTAL. 
 
 
 
 
 
 
 
 
 
 
 
 

3)  Ratings and Markings 

 

3.1 Class / Division Ratings for US and Canada 

 
The D1x Loudspeakers comply with the following standards for 
hazardous locations:  
 
UL 1203 
CSA C22.2 NO. 30-M1986 
 
The D1xL1 & D1xL2  Loudspeakers also comply with the 
following standards for signaling equipment:  
UL1480 
CSA C22.2 NO. 205-12 
 

3.1 Class / Division Ratings for US & Canada 

 
Class I Div 1 

ABCD 

T6 

Ta -40°C to +70°C 

 
Installation must be carried out in compliance with the National 
Electric Code / Canadian Electric Code 

 

3.2 Class / Zone ratings US and Canada

 

 

Class I Zone 1  

IIC T6 

 

Ta -40ºC to +70°C 

 

Installation must be carried out in compliance with the National 
Electric Code / Canadian Electric Code. 
 

3.3 Ambient Temperature Range: 

 
-40ºC to +70ºC 
 

3.4 Enclosure Ratings 

 
The product is rated for ingress protection as follows: 
IP rating per EN60529: 

 

IP66 

Type rating per UL50E / NEMA250: 4 / 4X / 3R / 13  

  
3.5 Electrical Ratings 

 

Model No. 

Input  

Power 
(Watts) 

Max I/P 
Volts 

D1xL1-V070 

70V Line 

15 

70 

D1xL1-R008

 

8 Ohm 

15 

10.95 

D1xL1-R016

 

16 Ohm 

15 

15.49 

D1xL2-V070

 

70V Line 

25 

70 

D1xL2-R008 

8 Ohm 

25 

14.14 

D1xL2-R016 

16 Ohm 

25 

20 

 

3.6 Frequency Range 

 
All models: 400Hz to 8000 Hz 
 

4)  Installation 
 

4.1 Safe Installation Requirements 
 

The product must only be installed by suitably qualified 
personnel in accordance with the latest issues of the relevant 
standards. 
 
The installation of the units must also be in accordance with the 
NEC / CEC and any local regulations and should only be carried 

The D1xL1 & D1xL2 Loudspeakers are certified 

by UL as Audible-signal Appliances for Use in 

Hazardous Locations 

 