E2S BExL15D Скачать руководство пользователя страница 1

INSTRUCTION MANUAL 

BExL15D & BExL25D 
Loudspeakers

 

ATEx/IECEx & UKEx Gas & Dust

 

 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH

www.e2s.com

 

Tel: +44 (0)208 743 8880

Document No. D210-00-101-IS

 

Issue 6

 

12-09-2022

Sheet 1 of 5

 

 

BExL15D 

BExL25D

1.  Product Table 

 

Unit Type Code 

Input  

Power 

Max I/P Voltage  

Sound 

Pressure Level 

dB(A) 

Max* 

Nom

.†

 

BExL15DFV070

70V Line 

15W

70V

102dB(A)  113dB(A) 

BExL15DFV100

100V Lie 

15W

100V

BExL15DFR008

8Ω 

15W

10.95

BExL15DFR016

16Ω 

15W

15.49V

BExL25DFV070

70V Line 

25W

70V

105dB(A)

 

119dB(A)

 

BExL25DFV100

100V Lie 

25W

100V

BExL25DFR008

8Ω 

25W

14.14

BExL25DFR016

16Ω 

25W

20V

The table shows the input current taken by the various loudspeakers. 
Nominal current at nominal voltage. 

Table 1: Electrical Ratings. 

 

It is important that the loudspeakers are connected to power amplifiers that have outputs that are compatible to the type of loudspeaker 
being used. Loudspeakers with a 70V or 100V line matching transformer fitted must be connected to a power amplifier with a 70V or 
100V line output. Low impedance 8 ohm or 16 ohm loudspeakers must be connected to amplifiers with a suitable low impedance 
output.  

 

The above table shows the maximum AC signal voltages at which the loudspeakers can be operated

 

The input current will vary according to the voltage input level and the frequency of the tone selected. 

 

The current levels taken by the each loudspeaker will depend on which output tapping has been selected (see section 12 & 13 of this 
instruction manual). BExL25D 70V and 100V Line units have output levels of 25W, 12.5W, 6W and 2W; BExL15D 70V and 100V Line 
units have output levels of 15W, 7.5W, 3W and 1W. 

 

2.  Warnings 

  

 

  DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS PRESENT 

  DO NOT OPEN WHEN ENERGIZED 

  POTENTIAL ELECTROSTATIC CHARGING HAZARD – CLEAN ONLY WITH A DAMP CLOTH 

  COVER BOLTS CLASS A4-80 

  USE HEAT RESISTING CABLES AND CABLE GLANDS (RATED 110°C) AT AMB. TEMPERATURES OVER 

40°C 

 
 
 
 

Содержание BExL15D

Страница 1: ...o the type of loudspeaker being used Loudspeakers with a 70V or 100V line matching transformer fitted must be connected to a power amplifier with a 70V or 100V line output Low impedance 8 ohm or 16 oh...

Страница 2: ...operation and if it does it will only exist for a short time Gas Groupings Group IIA Propane Group IIB Ethylene Group IIC Hydrogen and Acetylene up to 55 C ambient Temperature Classification for Gas A...

Страница 3: ...ghtened to ensure that the unit cannot move in service Fig 1a Fixing Location for BExL15D Sounder Fig 1b Fixing Location for BExL25D Sounder 7 Access to the Flameproof Enclosure To access the Ex d cha...

Страница 4: ...the unit Fig 3 Internal View of Cover When using the internal earth terminal ensure that the stainless steel M4 flat washer is between the incoming earth wire and the enclosure Internal earthing conne...

Страница 5: ...st have a minimum resistance value of 4k7 ohms and a minimum wattage of 2 5 watts On low impedance units the end of line resistor used must have a minimum resistance value of 2k ohms and a minimum wat...

Страница 6: ...HEET SCALE TITLE A3 IF IN DOUBT ASK DO NOT SCALE ALL DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B D210 06 101 R S RAIT R N POTTS R N POTTS 05 08 2022 OF BExL15 BExL...

Страница 7: ...LINEAR DIMENSIONAL TOLS ANGULAR DIMENSIONAL TOLS STANDARDS MOD No REASON INITIAL DATE ISSUE DATE APPROVED CHECKED DATE DATE DRAWN WEIGHT Kg SURFACE FINISH MATERIAL ALTERNATIVE MATERIAL SHEET SCALE TIT...

Страница 8: ...nds B V Utrechtseweg 310 6812 AR Arnhem Netherlands Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 2G Ex db IIB or IIC T4 Gb II 2G Ex db eb IIB or I...

Страница 9: ...are in accordance with the restriction of the use of hazardous substances in electrical and electronic equipment including amendment by Directive 2015 863 EU Regulation EC 1907 2006 Registration Evalu...

Страница 10: ...duction process Module D Sira Certification Service Notified Body No 0518 Rake Lane Eccleston Chester CH4 9JN UK Quality Assurance Notification Module D CSAE 22UKQAN0046 Provisions fulfilled by the eq...

Страница 11: ...and Place of Issue London 12 09 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the...

Страница 12: ...Page left Intentionally blank...

Отзывы: