INSTRUCTION MANUAL (ATEX / IECEx) 

BExDTS110D   

Flameproof Sontel 

For use in Flammable Gas and Dust Atmospheres 

 

 
 
 
 
 
1)  Introduction 

 
The  BExDTS110D  is  a  flameproof  Sontel telephone sounder 
which  is  certified  to  meet  the  requirements  of  the  ATEX 
directive 94/9/EC and IECEx scheme. The Sontel produces a 
loud  audible  signal  when  triggered  by  a  telephone  ringing 
signal and can be used in hazardous areas where potentially 
flammable gas and dust atmospheres may be present.  Thirty-

two different sounds can be selected by internal switches (

see 

tone  table  on  Page  4

).    The  BExDTS110D  unit  produces 

output levels in the 110dB(A) range. The unit can be used in 
Zone 1 and Zone 2 areas with gases in groups IIA, IIB and IIC 
and  temperature  Classifications  of  T1,  T2,  T3  and  T4.  For 
ambient temperatures over +55ºC the gas groups are limited to 
IIA and IIB.  They can also be used in Zone 21 and Zone 22 
areas for combustible dusts and have an IP rating of IP 67 and 
a  surface  temperature  rating  of  T100ºC  up  to  +55ºC  and 
T115ºC over +55ºC.  
  

2)  Marking 

 
All  units  have  a  rating  label,  which  carries  the  following 
important information:- 
 
Unit Type No.     

BExDTS110D

 

 
Input Voltage:      DC Units:    

    12V  or  24V  or  48V 

AC Units:        

230V  or  110V  or  115V 

 

        

Codes:   

 

Ex d IIC T4 for T

a

 –50°C to +55

°

Ex d IIB T4 for T

a

 –50°C to +70

°

        Ex tD A21 IP67 T115°C based on max Ta of +70°C 

 

Certificate No’s

    KEMA 99ATEX6312 

 

 

IECEx KEM 10.0003

 

 

 

 

 

 

 

 
“Warnings”

 

 DO NOT OPEN WHEN AN EXPLOSIVE  

                               GAS OR DUST ATMOSPHERE IS PRESENT 

 

      COVER BOLTS CLASS A4-80 

 

     USE HEAT RESISTING CABLES AND CABLE GLANDS 

 

       (Rated 110ºC) AT AMB. TEMPERATURES OVER 40ºC 

 
Year of Construction /  

Serial No.       

 

 i.e.  10 / 1DTS23000001 

 

 
 
 
 

3) 

Type Approval Standards

 

 

The  Sontel has EC Type Examination  and  IECEx certificates 
issued  by  KEMA  and  has  been  approved  to  the  following 
standards:- 
 

EN60079-0:2006   IEC60079-0:2004 (Ed4)

      

General Requirements

 

EN60079-1:2007   IEC60079-1:2007

 

(Ed6)

        Flameproof Enclosure ‘d’ 

EN61241-0:2006   IEC61241-0:2004 (Ed1)       Dust General 

          Requirements 

EN61241-1:2004   IEC60079-1:2004 (Ed1)       Dust Enclosures tD 

 

4) 

Installation Requirements

 

 

The  Sontels  must  be  installed  in  accordance  with  the  latest 
issues of the relevant parts of the EN 60079 standards or the 

equivalent  IEC  standards  –  Selection,  Installation  and 
maintenance  of  electrical  apparatus  for  use  in  potentially 
explosive  atmospheres  (other  than  mining  applications  or 
explosive processing and manufacture):- 
 

EN60079-14:2008

    

Electrical Installations in Hazardous 

IEC60079-14:2007 (Ed4) 

Areas (other than mines)

 

EN60079-10:2003

   

Classification of Hazardous Areas

 

IEC60079-10:2008 (Ed1) 
 
The  installation of  the  units  must also  be in  accordance  with 
any local codes that may apply and should only be carried out 

by  a  competent  electrical  engineer  who  has  the  necessary 
training. 

 

5) 

Zones,  Gas  Group,  Category,  IP  Rating  and 
Temperature Classification 

 

The BExDTS110D Sontels have been certified Ex d IIC T4 for 
Ta –50°C to +55ºC and Ex d IIB T4 for Ta –50°C to +70ºC for 

gas and Ex tD A21 IP67 T115ºC based on max. Ta of +70ºC 
for dust. This means that the units can be installed in locations 
with the following conditions:- 
  

Area Classification Gas: 

 

Zone 1 

Explosive  gas  air  mixture  likely  to  occur  in 
normal operation. 

Zone 2 

Explosive  gas  air  mixture  not  likely  to  occur, 
and if it does, it will only exist for a short time. 

  

Gas Groupings: 

 

Group IIA 

Propane 

Group IIB 

Ethylene 

Group IIC  (Up to +55ºC only) 

Hydrogen and Acetylene 

 

 

Temperature Classification: 

 

T1 

400

o

 C  

T2 

300

o

 C 

T3 

200

o

 C 

T4 

135

o

 C 

0518 

II 2G/D 

Epsilon x: 

Equipment Group and 
Category: 

CE Marking 
Notified Body No. 

 