background image

 

 

_______________________________________________________________________________________________________________________________ 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)208 743 8880 

                                                                                                                                                             www.e-2-s.com             Fax: +44 (0)208 740 4200 
Document No. IS 2442-P      Issue E        23-04-10                       

Sheet 1 of 5

 

  

  

INSTRUCTION MANUAL (ATEX / IECEx) 

BExCL15-05D 

Flameproof Combined Loudspeaker / Beacon 

 
 
 
 
 
 

1)  Introduction 

 
The BExCL150-05D is a flameproof combined loudspeaker / 

beacon  which  is  certified  to  meet  the  requirements  of  the 
ATEX  directive  94/9/EC  and  the  IECEx  Scheme.  The 

loudspeaker section produces a 15 watt audio signal and the 
beacon  section  produces  a  synchronised  visual  warning 

signal. There are three loudspeaker section versions, 8 ohm, 
16 ohm or 100V Line transformer. On 100V line transformer 

units  there  are  four  output  tappings  and  the  unit  produces 
output levels in the 112dB(A) range. The unit can be used in 
hazardous  areas  where  potentially  flammable  atmospheres 

may be present.  The unit can be used in Zone 1 and Zone 2 
areas with gases in groups IIA and IIB and with Temperature 

Classifications of T1, T2, T3 and T4.  
 

2)  Marking 

 
All  units  have  a  rating  label,  which  carries  the  following 

important information:- 
 
Unit Type No.  

BExCL15-05D

 

 

Loudspeaker 

8 ohm or 16 ohm   

Impedance: 

100V Line 

 
Beacon Input 

DC Units    12V  or 24V  or  48V 

Voltage:     

AC Units         230V or 115V 

                    

Code:           

Ex d IIB T4 for T

a

 –50

°

C to +70

°

C

  

 

Certificate No.

     KEMA 01ATEX2223X 

 

 

IECEx KEM 10.0025X

 

 

 

 

 

 
 

“Warnings”

 

 

DO NOT OPEN WHEN AN EXPLOSIVE  

                         

     GAS ATMOSPHERE IS PRESENT 

 

      COVER BOLTS CLASS A4-80 

 

                    USE HEAT RESISTING CABLES AND        

                   CABLEGLANDS (Rated 110ºC) AT  

                       AMB. TEMPERATURES OVER 40ºC 

 
Year of Construction /  

Serial No.       

 

 i.e.  10 / 1CL21000001 

 

3) 

Type Approval Standards

 

 

The units have an EC Type examination certificate issued by 
KEMA and have been approved to the following standards:- 

 
 

 
 

 

 
 
 

 

EN60079-0:2006   IEC60079-0:2004 (Ed4)

      

General Requirements

 

EN60079-1:2007   IEC60079-1:2007

 

(Ed6)

        Flameproof Enclosure ‘d’ 

 

4) 

Installation Requirements

 

 
The  unit  must  be  installed  in  accordance  with  the  latest 
issues of the relevant parts of the EN60079 specifications or 

the equivalent IEC specifications – Selection, Installation and 
maintenance  of  electrical  apparatus  for  use  in  potentially 

explosive  atmospheres  (other  than  mining  applications  or 
explosive processing and manufacture):- 

 

EN60079-14:2008

    

Electrical Installations in Hazardous 

IEC60079-14:2007 (Ed4) 

Areas (other than mines)

 

 

EN60079-10:2003

   

Classification of Hazardous Areas

 

IEC60079-10:2008 (Ed1) 

 
The  installation  of  the  unit  must  also be  in  accordance  with 

any  local  codes  that  may  apply  and  should  only  be  carried 
out  by  a  competent  electrical  engineer  who  has  the 

necessary training. 

 

5) 

Zones, Gas Group, Category and Temperature 
Classification 

 

The BExCL15-05D unit has been certified Ex d IIB T4 for Ta 

–50ºC to +70ºC. This means that the units can be installed in 
locations with the following conditions:- 

  

Area Classification: 

 

Zone 1 

Explosive  gas  air  mixture  likely  to  occur  in 
normal operation. 

Zone 2 

Explosive  gas  air  mixture  not  likely  to  occur, 

and if  it does, it will only exist for a short time. 

  

Gas Groupings: 

 

Group IIA 

Propane 

Group IIB 

Ethylene 

 

 
Equipment Category:

 

2G 

 

Temperature Classification: 

 

T1 

400

o

 C  

T2 

300

o

 C 

T3 

200

o

 C 

T4 

135

o

 C 

 
 

Ambient Temperature Range: 

 

   

         -50

°

C to +70

°

0518 

II 2G 

Epsilon x: 

Equipment Group 
and Category: 

CE Marking: 

Notified Body No. 
 

Отзывы: