INSTRUCTION & SERVICE MANUAL
AL112NX AlertAlight Combined Sounder Xenon
E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH [email protected] e2s.com D221
-
00
-
201
-
IS Issue 3 30/06/2022
•
All models are approved for use as Audible Signal Appliance
for use as General Signaling: UL464A & CSA C22.2 No 205
-
17
•
Type 4 / 4X / 3R / 13, IP66
•
-
40°C to +66°C /
-
40°C to +151°F
General Signaling Canada:
AL112NXDC024:
-
40°C to +55°C /
-
40°F to +131°F
AL112NXAC230:
-
40°C to +40°C /
-
40°F to +104°F
•
To maintain Ingress Protection, cable entries must be fitted with suitably rated cable glands or stopping plugs
•
Mounting
-
Units can be mounted using 2
-
off ø9mm holes in the mounting lugs or through the back of the housing using the supplied
gasket.
•
EOL Monitoring (DC Only): End of Line Devices may be fitted between the +ve &
-
ve terminals of the PCBA. Please ensure that the device
legs meet the wire size range stated for the connection terminals and are fitted correctly in order to avoid a short. Refer to the compatible
control panel specification for EOL device values and ratings.
Model
Nominal
Voltage
Voltage Range
Nominal Operating Current*
Max Operating RMS
#
Beacon
Sounder
P1 / P2
Beacon
Sounder
P1 / P2
AL112NXDC012
12V dc
11.5
-
14Vdc
341mA
280mA / 376mA
531mA
280mA / 430mA
AL112NXDC024
24V dc
20
-
28Vdc
250mA
225mA / 430mA
271mA
AL112NXDC048
48V dc
42
-
52Vdc
170mA
122mA / 223mA
170mA
AL112NXAC115
115 Vac
103.5
-
126.5 Vac 50/60Hz
70mA
100mA / 173mA
58mA
181mA / 383mA
AL112NXAC230
230 Vac
207
-
240 Vac 50/60Hz
35mA
65mA / 105mA
*Nominal Voltage, 1Hz Flash Pattern & Tone 12
#
Worst
-
case input voltage and worst case flash pattern
floor area covered by the VAD.
maximum length of the sides of the square
mounting height from the floor and y is the
Wall mounted, where x is the maximum
Category W-x-y (Wall mounted):
V=55.3m
³
V=62.5m
³
11W
Power
14W
AL112NXDC024 & AL112NXDC048 LIGHT OUTPUT
Note: CPR aproved units must be
positioned sounder on top,
beacon below.
table are VdS Approved)
(Only units in the following
Coverage Area According to EN54-23
AL112NXDC024
AL112NXDC048
Category W
Unit
W-2.4-4.8
W-2.5-5
x
y
y
AL112NXDC024 & AL112NXDC048 LIGHT OUTPUT
Approved Beacon for EN54
-
23 Applications:
Clear lenses are compliant with EN54
-
23
The units have been tested and approved to DNVGL
-
CG
-
0339 & EN54
-
3:2014
incl. A1:2019 for the installation on ships in the following locations:
Temperature:
A, B, C & D (Machinery spaces, control rooms,
accommodation, bridge, inside cubicles,
desks, etc..., pump rooms, holds, rooms with no
heating, Open deck, masts)
Humidity:
A & B (All locations)
Vibration:
A (Bulkheads, Beams, Deck, Bridge)
EMC:
A & B (All locations Including Bridge & open deck)
Enclosure:
A, B & C (Control rooms, accommodation, bridge,
engine room, open deck masts, below floor plates in
engine room)
The units comply with Solas 74 Chapter II
-
2, Regulation 7 & Chapter X,
Regulation 3 for installation on ships in the following locations:
Temperature:
D (Location
-
25° to +70°C)
Vibration:
A (General Applications)
EMC:
B (Bridge & Open Deck Zone)
Enclosure:
IP56, Salt mist
Attention: Installation must be carried out by an electrician in compliance with the National Electrical Code, NFPA 70 or CSA 22.1 Canadian Electrical
Code, Part I, Safety Standard for Electrical Installations, Section 32. / L'installation doit exclusivement être réalisée par du personnel qualifié, conformé
ment au code national d'électricité américain, NFPA 70 ou CSA 22.1 Code canadien de l'électricité, première partie, norme de sécurité relative aux
installations électriques, Section 32