INSTRUCTION MANUAL 

A141 High Level Audible Warning System / Battery backup 

European Safety Systems Ltd.

  

Impress House, Mansell Road, Acton, London W3 7QH    

 

 

[email protected]

     Tel: +44 (0)208 743 8880 

                                                                                                                                                        

www.e2s.com

    Fax: +44 (0)208 740 4200 

Document No. D161-00-201-IS_Issue_E 12-02-13 
 Sheet 

of 

 

 
1) Introduction 

 
The A141 high level audible warning system is an 
effective wide area warning alarm system and 
can be used where there is a requirement to 
attract attention over large areas and also where 
potential high levels of background noise exist. 
 
The system comprises of a central control unit 
which is configured to drive an audible horns 
containing four driver units. 
The control unit produces forty five different alarm 
sounds (tones) that are selectable using an 
internal dipswitch (see tone table page 3 for 
available tones) including a stage 2 and stage 3 
alarm option. 
 
Each audible horn is capable of producing a 
range of loud warning signals with output levels 
at one meter of approximately 141dB(A) 
depending on tone selected.  
 
Both the control unit and horns are suitable to 
mount either indoors or outdoors in a number of 
mounting configurations with ingress protection to 
IP65. 
 
This particular unit is also fitted with a Battery 
backup system with fault monitoring with relay 
terminals and a set of remote start and stop 
terminals. 
 

2) Operating 

and 

Marking 

 
All units have the following operating 
requirements and limitations. 
 
Audible Horn Units 
Unit Type No.: 

A141 

Operating Temp:  -20 to +55

IP Rating: 

IP65 

Horn weight: 

14kg 

 
 
Control Panel 
Unit Type No.       A141AC230GB 
Input Voltage: 

 

 

115 or 230VAC (90V to 264V AC range) 

Operating Temp:  -20 to +55

IP Rating: 

IP65 

 

 

Marking:  

 

 
Control Unit weight : 23kg 
 

3) 

Installation Requirements

 

 
Always de-energize control unit before removing 
cover. 
The installation of the units must be in 
accordance with any local codes that may apply 
and should only be carried out by a competent 
electrical engineer who has the necessary 
training. 
 

3)  Power Supply Selection 
 

It is important that a suitable power supply is run 
the control unit. The power supply selected must 
have the necessary capacity to provide the input 
current to the control unit. 
  
The following table shows the input current taken 
by the various control unit configurations units:- 

 

AC Unit Type 

Input  

Input 

Range.   

No. 

Horns 

Voltage Current I/P 

Volts

 

 
A141AC230GB

  

 

90-264V 

AC 

  115V 

AC 

4.2A 

  230V 

AC 

1.95A 

 
Table 1: Variants and power requirements 

 
Current levels shown above are for the nominal 
input voltage.

 

The input current will vary 

according to the voltage input level and the tone 
selected. 

 

The above table also shows the maximum and 
minimum voltages at which the control units can 
be operated. 
 
 

4) Cable 

Selection 

 

When selecting the cable size consideration must 
be given to the input current that the control unit 
draws (see table above) and the length of the 
cable run. 
 
 