Installing and operating manual
DrivE-Tech
015, 030, 022, 040, 055, 075, 110, 150
Страница 1: ...Installing and operating manual DrivE Tech 015 030 022 040 055 075 110 150...
Страница 2: ...rivE Tech Installation for constant pressure control 12 5 1 1 Pressure tank 12 5 1 2 Pressure sensor 12 6 DrivE Tech Use and Programming 13 6 1 DrivE Tech display 13 6 2 Initial configuration 13 6 3 I...
Страница 3: ...stallation maintenance and repair must be carried out by trained skilled and qualified personnel Failure to observe and follow the instructions in this manual may result in dangerous and potentially l...
Страница 4: ...20 Power frequency 50 60 Hz 2 Max ambient temperature at nominal current 40 C 104 F Max altitude at nominal current 1000 m Grade of protection IP55 NEMA 4 RS485 serial communication PWM configurable...
Страница 5: ...supply LINE L1 L2 earth It is recommended to use cable lugs Output 3 ph motor earth U V W 1 ph motor earth U running V common It is recommended to use cable lugs 230 V AC auxiliary fans wall mounting...
Страница 6: ...L1 L2 L3 It is recommended to use cable lugs Motor output MOTOR U V W GND It is recommended to use cable lugs 12 V dc auxiliary fan wall mounting kit 0VE VE WARNING respect the polarity Cable strippi...
Страница 7: ...E L1 L2 L3 GND It is recommended to use cable lugs Motor output MOTOR U V W GND It is recommended to use cable lugs 12 V dc auxiliary fans wall mounting kit VENT WARNING respect the polarity Cable str...
Страница 8: ...COM3 closed contact with DOL1 running NC3 COM3 opened contact with DOL1 running DOL2 pump relay NO4 COM4 closed contact with DOL2 running NC4 COM4 opened contact with DOL2 running Relays are no voltag...
Страница 9: ...wer supply cables Note To enable the restoration of the display screen when there are electromagnetic interference DrivE Tech periodically provides some fast refresh of the display 4 3 Installation wi...
Страница 10: ...Tech 015 030 022 040 DrivE Tech 055 075 110 150 n 4 rods n 4 M5 nuts n 4 hooks n 1 cooling ring n 4 M5 screws n 4 clamps n 4 clips to add if necessary n 1 centre pin Use the cooling ring for best cool...
Страница 11: ...racket in AISI 304 n 4 screws to fix DrivE Tech to wall bracket n 2 12 V DC fans n 1 fans cover n 2 fans cover fixing screws n 2 wall fixing brackets n 4 M5 screws for DrivE Tech fixing to the bracket...
Страница 12: ...s 50 liters min the pressure tank should have a capacity of 5 liters If the max water flow is 20 gpm the pressure tank should have a capacity of 2 gallons Pre charge pressure of the pressure tank shou...
Страница 13: ...therwise it is impossible to set up and or modify any parameters they can be only displayed 6 1 DrivE Tech display Screen is a back lit LCD displaying 2 rows of 16 digits each Alarms are indicated by...
Страница 14: ...rated frequency Warning make sure to run the system without damaging pump and system If during the test the motor runs in reverse it is possible to change the wiring sequence via software without phy...
Страница 15: ...e absorbed motor current cosphi index means the angle phi between the voltage and current absorbed by the motor P is the power in Watts supplied to the pump NORMAL status means no alarms If an alarm o...
Страница 16: ...ng the Initial Configuration chapter 6 2 Initial Configuration However through the Installer Parameters menu it is possible to change the set parameters or set others in order to perfect the calibrati...
Страница 17: ...ted if the readen value goes higher than the minimum value for a period of at least 5 seconds OFF Enabling of set value changing by analog input AN3 3 The set value to be kept constant 0 Value compens...
Страница 18: ...gauges When using a group of pumps the pressure compensation to be applied to each pump is equal to the total pressure compensation when all the pumps are running at full speed divided by the number o...
Страница 19: ...e pump Kp and Ki parameters allow the dynamic control of system by DrivE Tech set values Ki 50 Kp 005 are usually enough to get a valid dynamic control OFF Function to activate ON the first auxiliary...
Страница 20: ...and checking the value on the DrivE Tech display a value can be set by assuming a dry cosphi equivalent to 60 of the rated cosphi specified by the manufacturer 10 Restart delay after a dry running al...
Страница 21: ...le to modify individual parameters or modify the password 2 Parameters Default Description XXX Motor rated voltage as shown in the motor plate Average voltage drop due to the inverter is between 20 V...
Страница 22: ...er frequency switching frequency It is possible to chose PWM in the range of 2 5 4 6 8 10 kHz Higher values give a more sinusoidal wave with fewer losses If long cables are used 20 m 76 ft submersible...
Страница 23: ...apter 1 Indipendent Function logic for analog input AN1 AN2 20 Zero correction for analog input 1 20 mA x 20 4 mA 20 Zero correction for analog input 2 20 mA x 20 4 mA 20 Zero correction for analog in...
Страница 24: ...e than ambient temperature is less than 40 C 104 F Check if auxiliary cooling fan is working properly and if mounting space is adequate for proper cooling Reduce the PWM value Advance Parameter Menu N...
Страница 25: ...RM SLAVE XX slave XX error detected by master check the status of the slave If pumps cosphi is lower than the dry running cosphi for at least 2 seconds DrivE Tech will stop the pump DrivE Tech will tr...
Страница 26: ...the second pump is controlled by the relay DOL1 allowing a third pump to be controlled by the relay DOL2 If pump 1 P1 is already running to maintain the desired set pressure red line an additional wat...
Страница 27: ...OMBO function that allows serial communication between up to 8 DrivE Techs each one connected to a pump The operating principle switch on off of pumps is similar to as stated in chapter 8 1 To achieve...
Страница 28: ...ech must be connected to each other by using a tripolar cable 0 5 mm 2 wired on S S G pins on control board MASTER address 00 SLAVE 1 address 01 SLAVE 2 address 02 Master setup 1 Supply power to the D...
Страница 29: ...set ON 4 Press STOP red button 5 Press STOP again Whenever the user accesses the Menu screen of the DrivE Tech master the communication between DrivE Techs is automatically interrupted In case of alar...
Страница 30: ...the ki kp parameters Installer Parameters menu At first it is suggestable to increase the Ki value If it not enough reduce of one unit the Kp value DOL pump stops and starts continuously Increase delt...
Страница 31: ...le phase three phase submersible surface if submersible cable lenght m _____ if sommersible cable section mm 2 ____ P2 motor kW ____ rated motor Volt V ___ rated motor Amp A __ rated motor Hz ___ if s...
Страница 32: ...Il prodotto conforme alle seguenti normative EN 55011 Classe A EN 61000 EN 60146 EN 50178 EN 60204 1 DECLARATION OF CONFORMITY In according with Machine Directive 2006 42 EC EMC Directive 2004 108 CE...
Страница 33: ...33 NOTE manDrivE Tech_eng_10 docx...